![Smart temp Falcon SMT-880 User'S And Installer'S Manual Download Page 30](http://html1.mh-extra.com/html/smart-temp/falcon-smt-880/falcon-smt-880_users-and-installers-manual_1296340030.webp)
Page 30
DRAFT
Zone Setup Button
Value
Option
Zone name
Enter the name of the zone using the Keyboard. Upper/ lower case can be
sued as well as numerals and other characters
Zone Control Method
Select zone control Method as described on page 26 of this manual
Zone Sensor
Select the temperature sensor used for this zone (if any)
Zone Size
Select the relative size of the zone when compared to other zones in the
system
Zone priority
Set the zone priority when compared to other zones in the system
Minimum Damper
If using 0-10V dampers set the minimum closed damper position when the
zone does not require heating or cooling
Maximum Damper
If using 0-10V dampers set the Maximum damper open position when the
zone is being heated or cooled
Zone run alone
Check this box if you wish this zone to be able to run without the normal
minimum score rules being met.
Advanced Tab
Value
Option
Economy Cooling
If enabled, an assignable relay can be used to draw in cool outside when
suitable to cool the building. This replaces first stage cooling only.
Economy Temp
The economy cooling set temperature to use.
Economy Span
The difference between economy cooling on and off points.
Economy Comp
Select Compressor run status during economy cooling
Humidifier
If enabled, an assignable relay can be used to change state at the RH set
value
Humidly Settings
RH threshold for assignable relay function
Filter Reminder
Enable / disable filter clean warning and set period.
Display C/F
Falcon display units
Aux Relay 1
Assignable relay 1 function
Aux Relay 2
Assignable relay 2 function
0-10v 1
Assignable 0-10V 1 Function
–
Typically used for digital scroll capacity
control.
0-10V 2
Assignable 0-10V 2 Function
O-10V 3
Assignable 0-10V 3 Function
0-10V Heat Span
Sets the range of the assignable 0-10V output when used for heating valve
control
0-10V Cool Span
Sets the range of the assignable 0-10V output when used for cooling valve
control
Event Tab
Value
Option
System Daily Events
Set number of daily events (active in programmable mode only)
Event 1 Name
Set event 1 name with keyboard
Event 2 Name
Set event 2 name with keyboard
Event 3 Name
Set event 3 name with keyboard
Event 4 Name
Set event 4 name with keyboard
Event 5 Name
Set event 5 name with keyboard
Event 6 Name
Set event 6 name with keyboard
PIN Tab
Value
Option
Change PIN
Enter a new pin, then re-enter to confirm PIN. Sets new installer PIN