AXP1440-C07 Shelf Installation
AXP1440-C07 Installation and Use (6806800V18A)
103
5.8
Power Cable Termination
Custom lugs are used with large gauge wires for up to 80 Amps DC (4 AWG) when
connecting to the PEM. These are shipped with the product.The lugs are angled to allow
the cables to be dressed below the cable management tray, thus protecting the circuit
breakers from accidental tripping.
Terminating this lug is identical to terminating standard lugs. To minimize shorting of the
terminals, the lugs must be insulated according to
5.9
Connecting the Cables to the PEM
In a redundant configuration, each PEM must be connected to a separate DC power
source. The two separate inputs on a single PEM should be connected to the DC same
source. Power is introduced to each PEM’s terminal block on the front of the module (power
input cable and return cable). The lugs provide secure contact for the cable and prevent the
Figure 5-5 DC Power Connection Detail
Heat shrink should be placed as close to the hole as possible (0.15") apart. The heat
shrink tube should be cut approximately at a 30° angle.
Summary of Contents for 6806800V18A
Page 1: ...AXP1440 C07 Installation and Use P N 6806800V18A February 2020...
Page 8: ...6 AXP1440 C07 Installation and Use 68068000V18A Table of Contents...
Page 10: ...List of Figures 8 AXP1440 C07 Installation and Use 68068000V18A...
Page 12: ...List of Tables 10 AXP1440 C07 Installation and Use 68068000V18A...
Page 40: ...38 AXP1440 C07 Installation and Use 6806800V18A Notice de S curit Notice de S curit...
Page 52: ...50 AXP1440 C07 Installation and Use 6806800V18A Sicherheitshinweise Sicherheitshinweise...
Page 90: ...88 AXP1440 C07 Installation and Use 6806800V18A Site Preparation Site Preparation...
Page 163: ...1...