SI-700 –EIA-232/EIA-485 Interface
3
Cabling and Applications
For each application, Smar also produces a set of cables to be used accordingly. See the
specifications below.
Technical Specifications
Number of Communication Channels
1
Data Communication Interface
EIA-232 / EIA-485
Baud rate
Up to 200 Kbps enable
EIA-232 side
Enables EIA-232 Half-Duplex or Full-
Duplex mode
EIA-485 side
Enables Embedded Bus Terminator
activation
Protection EIA-485
No transmission when the bus is in
break state.
Isolation
1600 V
RMS
@1 minute, typical
Power Supply
Supplied by the IMB bus, +5 Vdc, @
100 mA, typical
NOTE
In the interconnection of the 485 network, to attend the EMC standard (Electromagnetic capability), it is
necessary to use a 3-wire shielded twisted pair cable. Where, two wires are used to communication and
the third is used as reference. The shielding must be connected in one of the housing endings.