Section 5
5.1
TECHNICAL CHARACTERISTICS
Functional Specifications
Process Fluid
Liquid, gas or steam.
Output Signal
Digital only. Fieldbus Foundation
TM
, 31.25 kbit/s voltage mode with bus power.
Power Supply
Bus power 9 - 32 VDC.
Current consumption quiescent 12 mA.
Output impedance: nonintrinsic safety from 7.8 kHz - 39 kHz should be greater or equal to 3 kOhm.
Intrinsic safety output impedance (assuming an IS barrier in the power supply) from 7.8 kHz - 39
kHz should be greater or equal to 400 Ohm.
Indicator
Optional 4½-digit numerical and 5-character alphanumerical LCD indicator.
Hazardous Area
Certifications
Explosion proof (FM, NEMKO, CEPEL), dust ignition proof and non-incendive (FM) and intrinsic
safety (FM, CSA, NEMKO, EXAM, CEPEL, NEPSI).
European Directive
Information
Authorized representative in European Community
Smar Gmbh-Rheingaustrasse 9-55545 Bad Kreuzanach
PED Directive (97/23/EC)
– Pressure Equipment Directive
This product is in compliance with the directive and it was designed and manufactured in
accordance with sound engineering practice using several standards from ANSI, ASTM, DIN and
JIS.
EMC Directive (2004/108/EC) - Eletromagnetic Compatibility
The EMC test was performed according to IEC standard: IEC61326-1:2006, IEC61326-2-3:2006,
IEC61000-6-4:2006, IEC61000-6-2:2005. For use in environment only.
Keep the shield insulated at the instrument side, connecting the other one to the ground if necessary
to use shielded cable.
ATEX Directive (94/9/EC)
– Equipment and protective systems intended for use in potentially
explosive atmospheres.
This product was certified according European Standards at NEMKO and EXAM (old DMT). The
certified body for manufacturing quality assessment is EXAM (number 0158).
LVD Directive 2006/95/EC
– Electrical Equipment designed for use within certain voltage
limits
According the LVD directive Annex II the equipment under ATEX “Electrical equipment for use in an
explosive atmosphere” directive are excluded from scope from this directive.
The EC declarations of conformity for all applicable European directives for this product can be
found at
Temperature Limits
Ambient:
-40 to 85
o
C (-40 to 185
o
F)
-15 to 85 ºC (-59 to 185 ºF)
LD290I
Process:
-40 to 100
o
C (-40 to 212
o
F) Silicone Oil
0 to 85
o
C (-32 to 185
o
F) Inert Fluorolube Oil
-25 to 85 ºC (-
13 to 185 ºF) Viton O’ring
-40 to 150
o
C (-40 to 302
o
F)
LD290L
-15 to 150
o
C (-59 to 302
o
F)
LD290I
Storage:
40 to 100
o
C (-40 to 212
o
F)
Display
-20 to 80 ºC (-4 to 176 ºF)
-40 to 85
o
C (-40 to 185
o
F) without damage
Turn-on Time
Performs within specifications of less than 10 seconds after power is applied to the transmitter.
Configuration
Basic configuration may be done using local adjustment magnetic tool if device is fitted with display.
Complete configuration is possible using Syscon.
Volumetric
Displacement
Less than 0.15 cm
3
(0.01 in
3
).
Overpressure and
Static Pressure
Limits (MWP
–
Maximum Working
Pressure)
14 MPa (138 bar) for ranges 2, 3, 4.
31 MPa (310 bar) for range 5.
For Level Ranges ANSI/DIN (models
LD290L
):
150#: 6 psia to 235 psi (-0,6 to 16 bar) to 199,4 °F (93 °C)
300#: 6 psia to 620 psi (-0,6 to 43 bar) to 199,4 °F (93 °C)
600#: 6 psia to 1240 psi (-0,6 to 85 bar) to 199,4 °F (93 °C)
PN10/16: -60 kPa to 1,02 MPa to 212 °F (100 °C)
PN25/40: -60 kPa
to
2,55 MPa
to
212 °F (100 °C)
Overpressures above will not damage the transmitter, but a new calibration may be necessary.
Summary of Contents for LD292
Page 1: ......
Page 2: ......
Page 8: ...LD292 Operation and Maintenance Instruction Manual VIII...
Page 11: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD292 Sanitary...
Page 13: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD292 Level...
Page 24: ...LD292 Operation and Maintenance Instruction Manual 2 4...
Page 44: ...LD292 Operation and Maintenance Instruction Manual 3 20...
Page 54: ...LD292 Operation and Maintenance Instruction Manual 4 10...
Page 73: ...Appendix A A 7 CEPEL Centro de Pesquisa de Energia El trica...
Page 74: ...LD292 Certifications Information A 8 FM Approvals...
Page 76: ...LD292 Service Request Form B 2...