20.8 Warnings and Fault Indications
The meanings of the faults and warnings displayed by the Sunny Island are described in the following
table:
20.8.1 Category INV
Display no.
Level
Description
F109
3
Transformer overtemperature
W110
1
overtemperature on transformer on slave 1
W111
1
overtemperature on transformer on slave 2
W112
1
overtemperature on transformer on slave 3
F113
3
overtemperature on heatsink
W114
1
overtemperature on heatsink on slave 1
W115
1
overtemperature on heatsink on slave 2
W116
1
overtemperature on heatsink on slave 3
F117
2
AC current limit (short-circuit control active for too long)
W118
1
AC current limit (short-circuit control active for too long) on slave 1
W119
1
AC current limit (short-circuit control active for too long) on slave 2
W120
1
AC current limit (short-circuit control active for too long) on slave 3
F121
3
Inverter overvoltage
W122
1
Inverter overvoltage on slave 1
W123
1
Inverter overvoltage on slave 2
W124
1
Inverter overvoltage on slave 3
W137
1
derating due to temperature (heatsink or transformer)
W138
1
derating due to temperature (heatsink or transformer) on slave 1
W139
1
derating due to temperature (heatsink or transformer) on slave 2
W140
1
derating due to temperature (heatsink or transformer) on slave 3
F141
2
Inverter undervoltage
W142
1
Inverter undervoltage slave 1
W143
1
Inverter undervoltage slave 2
W144
1
Inverter undervoltage slave 3
F158
2
Voltage on output AC1
F159
2
Voltage on output AC1 slave 1
F160
2
Voltage on output AC1 slave 2
F161
2
Voltage on output AC1 slave 3