background image

5  Settings of Grid Management Services

SMA Solar Technology AG

Technical Information

17

STP60-SHP75-10-Parameter-TI-en-12

5.3

Control Modes

The general approach for the control modes is based on the structure in the technical report of the standard
IEC 61850-90-7 (see the figure below).

Up to five parameters are used to program the local modes depicted above. The parameter 

RmpTmsPT1

 is the rise

time from 0% to 95% (equal to 3τ) for the low-pass filter applied on the independent variable (e.g. grid voltage). The
reference table is made of two characteristic curves each containing up to ten break-points. One characteristic curve is
used when the independent variable is increasing and the other when decreasing. In this way, hysteresis can be
included in the reference table. Finally, the parameters 

RmpIncTmm

 and 

RmpDecTmm

 are the ramp rates for

increasing and decreasing output values (dependent variable) from the reference table.

Independent ramp rates are only available for control modes for active power, whereas for reactive power the ramp
rates are always given by the parameters 

RmpDecTmm_Q

 and 

RmpIncTmm_Q

. If the input value (independent

variable) of the reference table exceeds the values defining the characteristic curves, the output value (dependent
variable) of the reference table is given as the first or last value in the characteristic curve respectively.

5.3.1

Q(U) - Reactive Power as a Function of Grid Voltage

This control mode uses the grid voltage to generate a reference value for the reactive power so that the grid voltage
can be controlled at the point of common coupling. The control mode contains two additional parameters for
activation. The mode is activated when the active power is above the set threshold and deactivated again when the
active power is below the set threshold. The threshold for activation must be larger than or equal to the threshold for
deactivation. If this control mode shall always be available, set 

lock_in_UQ

 = 

lock_out_UQ

 = 0% (only available if

control mode 1 has been selected in the parameter 

ModeSelect

).

Parameter name

Setting range

Step size

RmpTmsPT1_UQ

0.6 s to 3600 s

0.01 s

lock_in_UQ

0% to 100% of active power

0.1%

lock_out_UQ

0% to 100% of active power (must be smaller than lock_in_UQ)

0.1%

Q_of_U

U: Grid voltage (independent values) from 80% to 120% of nominal
voltage

-

Q: Reactive power (dependent values) from -100% to 100% of nomi-
nal power

-

5.3.2

Q(P) - Reactive Power as a Function of Active Power

This control mode uses the active power to generate a reference value for the reactive power so that the grid voltage
can be controlled at the point of common coupling. The independent variable (grid power) can be negative if an
external energy meter is installed and the PV system must compensate for a local load (only available if control mode
2 has been selected in the parameter 

ModeSelect

).

Parameter name

Setting range

Step size

RmpTmsPT1_PQ

0.6 s to 3600 s

0.01 s

Summary of Contents for SHP 75-10

Page 1: ...2 F3 F4 Hom e Back OK F1 F2 F3 F4 Hom e Back OK STP60 SHP75 10 Parameter TI en 12 Version 1 2 ENGLISH Technical Information SUNNY TRIPOWER 60 SUNNY HIGHPOWER PEAK1 Description of the Operating Paramet...

Page 2: ...4 Settings of Grid Management Services Fault Ride Through FRT 9 5 Settings of Grid Management Services 12 5 1 Default Settings 13 5 1 1 Selecting the Control Modes for Reactive Power Provision 13 5 1...

Page 3: ...STP60 SHP75 10 Parameter TI en 12 5 3 6 PF U Power Factor as a Function of Grid Voltage 18 5 3 7 PF ext Power Factor as a Function of an External Setpoint 18 5 3 8 P V Active Power as a Function of Gr...

Page 4: ...minal Voltage This parameter refers to the nominal grid voltage of a country In most countries only one official grid voltage is valid For countries with several official grid voltages additional grid...

Page 5: ...the three key values is used in your file Parameter name Setting range Step size UMAX UNOM to 350 Vac L N 0 1 Vac L N T_UMAX 0 05 s to 90 0 s 0 01 s 2 4 Manual Restart With the function Manual Restar...

Page 6: ...e key values is used in your file Parameter name Setting range Step size FMIN 45 Hz to FNOM 0 01 Hz T_FMIN 0 05 s to 90 0 s 0 01 s 2 5 2 Disconnection due to Overfrequency The overfrequency disconnect...

Page 7: ...to alarm is the period which the inverter must wait before generating an alarm event This is to prevent the inverter from generating alarm events all the time Parameter name Setting range Step size T_...

Page 8: ...tails can be found in the settings for grid management services under parameter Connection reconnection ramp rate 3 3 Rate of Change of Frequency The parameter RoCoF or Rate of Change of Frequency mea...

Page 9: ...gs to grid management services it is stored in the inverter The FRT function is set to cope with voltage dips down to 0 UNOM without time limit This is confirmed in the FRT performance test which was...

Page 10: ...e compared with the average root mean square values before the fault The relevant time frame for the average voltage before the grid fault can be set via the parameter FRT_T_U_AVG default 10 minutes F...

Page 11: ...as the total current does not exceed the limit After fault clearance reactive current feed in stays active for a certain transition period This period can be set with the grid code parameter FRT_T_TR...

Page 12: ...1 to 10 0 1 FRT_DIDU_POS_HVRT 1 to 10 0 1 FRT_DIDU_NEG_LVRT 1 to 10 0 1 FRT_DIDU_NEG_HVRT 1 to 10 0 1 FRT_IQ_MODE 0 or 1 FRT_T_BLK 0 s to 10 s 0 01 s FRT_T_TRANS 0 s to 10 s 0 01 s FRT_T_U_AVG 0 s to...

Page 13: ...for Reactive Power Provision Reactive power references can either be given as a direct reference for reactive power Q or as an indirect reference via the power factor PF The references are based on th...

Page 14: ...ng option P_LIM_IF_Q 80 to 100 default 100 5 1 4 Nominal Apparent Power at Point of Common Coupling PCC All grid management services in the inverter are based on the nominal apparent power at the poin...

Page 15: ...onnection see Section 2 Grid Protection Settings page 4 Parameter name Setting option Explanation ReleaseToStart 0 Immediate disconnection 1 Connection when grid parameter is in the permissible range...

Page 16: ...dicates the setpoint for the power factor PF only available if control mode 9 has been selected in the parameter ModeSelect Parameter name Setting range Step size PF_ref 0 8 to 1 0 for overexcitation...

Page 17: ...espectively 5 3 1 Q U Reactive Power as a Function of Grid Voltage This control mode uses the grid voltage to generate a reference value for the reactive power so that the grid voltage can be controll...

Page 18: ...w the lock out threshold The threshold for activation must be larger than or equal to the threshold for deactivation If this control mode shall always be available set lock_in_PPF lock_out_PPF 90 only...

Page 19: ...ose of this time delay is to reach a lower sensitivity in terms of transient frequency changes and higher reliability when detecting grid failures The amount of generated active power is still sampled...

Page 20: ...c curves in the reference table contain equal co or dinates x y B Example of programming the FP_of_f characteristic curve when hysteresis is required e g as per BDEW Thus the two characteristic curves...

Page 21: ......

Page 22: ...www SMA Solar com...

Reviews: