14 Technical Data
SMA Solar Technology AG
Operating manual
STP15-25TL-30-BE-en-17
86
AC Output
STP 15000TL-30 STP 17000TL-30 STP 20000TL-30 STP 25000TL-30
Rated power at
230 V, 50 Hz
15000 W
17000 W
20000 W
25000 W
Maximum appar-
ent AC power
15000 VA
17000 VA
20000 VA
25000 VA
Rated grid voltage
230 V
230 V
230 V
230 V
Nominal AC volt-
age
220 V / 230 V /
240 V
220 V / 230 V /
240 V
220 V / 230 V /
240 V
220 V / 230 V /
240 V
AC voltage
range*
180 V to 280 V
160 V to 280 V
180 V to 280 V
180 V to 280 V
Nominal AC cur-
rent at 230 V
21.7 A
24.6 A
29 A
36.2 A
Maximum output
current
29 A
29 A
29 A
36.2 A
Maximum output
current under fault
conditions
50 A
50 A
50 A
50 A
Total harmonic
distortion of the
output current with
total harmonic dis-
tortion of the AC
voltage <2%, and
AC power >50%
of the rated power
≤3%
≤2.6%
≤3%
≤3%
Rated power fre-
quency
50 Hz
50 Hz
50 Hz
50 Hz
AC power fre-
quency*
50 Hz / 60 Hz
50 Hz / 60 Hz
50 Hz / 60 Hz
50 Hz / 60 Hz
Operating range
at AC power fre-
quency 50 Hz
44 Hz to 55 Hz
44 Hz to 55 Hz
44 Hz to 55 Hz
44 Hz to 55 Hz
Operating range
at AC power fre-
quency 60 Hz
54 Hz to 65 Hz
54 Hz to 65 Hz
54 Hz to 65 Hz
54 Hz to 65 Hz
Power factor at
rated power
1
1
1
1