8.7
Setting the Tripping Threshold of the Residual-Current
Device
If a residual-current device with a tripping threshold of 30 mA is specified and installed, you must
set the parameter
RCD adjustment
to
30 mA
(for further information, see the Technical
Information ""Leading Leakage Currents"" at www.SMA-Solar.com).
The basic procedure for changing operating parameters is explained in another section (see
Section 8.5 "Changing Operating Parameters", page 49).
• Select the parameter
RCD adjustment
and set it to
30 mA
.
8.8
Changing the Operating Mode of the Multifunction
Relay
The default operating mode of the multifunction relay is
Fault indication (FltInd)
. If you decide to
use another operating mode and have established the correct electrical connection for this
operating mode and the associated connection variant, you will have to change the operating
mode of the multifunction relay and make other settings, if necessary.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.5 "Changing Operating Parameters", page 49).
Procedure:
1. Select the parameter
Operating mode of multifunction relay
or
Mlt.OpMode
and set the
desired operating mode.
2. Once you have set the operating mode
Self-consumption
or
SelfCsmp
, you can configure
other settings:
• Select the parameter
Minimum On power for MFR self-consumption
or
Mlt.MinOnPwr
and set the desired value. This will configure the power threshold from
which a load is to be activated.
• Select the parameter
Minimum power On time, MFR self-consumption
or
Mlt.MinOnPwrTmm
and set the desired value. This will configure the minimum time for
which the power must have exceeded the minimum switch-on power threshold in order to
trip activation of the load.
• Select the parameter
Minimum On time for MFR self-consumption
or
Mlt.MinOnTmm
and set the desired value. This will configure the minimum time for
which the load remains activated.
3. If you have set the operating mode
Control via communication
or
ComCtl
, select the
parameter
Status of MFR with control via communication
or
Mlt.ComCtl.Sw
and set the
desired value. This will configure the status at which the multifunction relay is controlled via a
communication product.
4. If you have set the operating mode
Battery bank
or
BatCha
, make further settings:
8 Configuration
SMA Solar Technology AG
Operating Manual
51
STP5-12TL-20-BE-en-15