11 Decommissioning the Inverter
Risk of injury when lifting the inverter, or if it is dropped
The inverter weighs 38 kg. There is risk of injury if the inverter is lifted incorrectly or dropped while
being transported or when attaching it to or removing it from the wall mounting bracket.
• Carry and lift the inverter upright with the help
of several people. Use both hands to grasp the
recessed grips at the top and bottom, or use a
steel rod (diameter: 30 mm at maximum). This
will prevent the inverter from tipping forward.
Procedure:
1.
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources (see Section 2.2, page 7).
2. Remove the AC cable from the inverter. Press the locking levers all the way upward and pull
the conductors out of the connecting terminal plate for the AC cable.
3. Press down the locking levers of the connecting terminal plate for the AC cable.
4. If an Ethernet cable is connected for Speedwire communication, remove the cable from the
inverter.
5. If the multifunction relay, the SMA Power Control Module or the 485 Data Module Type B are
used, remove the connection cable from the inverter.
6. Attach the enclosure lid as follows:
• Fit one conical spring washer to each
screw. The grooved side of the conical
spring washer must face the screw head.
11 Decommissioning the Inverter
SMA Solar Technology AG
Service Manual for Installers
STP5-12TL-20-SG-en-13
30