Finished Wall
4.
Use the Water Level to make sure the Valve is level. F
inish the wall. Use
marks on mudguard to make sure finished wall is in
between 2” (51 mm)
and 3” (76 mm) from centerline of the inlet pipe.
5.
Only Remove the mudguard when installing Wall Plate
.
For more information
Refer Wall Plate Installation Manual (08160044).
Note: Removing the Mudguard beforehand might result in
damge to the solenoid
from debris.
2. CONNECT FLUSHOMETER (HARDWIRE CONNECTION)
TRANSFORMER NOT PROVIDED. IT IS VERY IMPORTANT THAT THE
OUTPUT VOLTAGE OF THE TRANSFORMER MUST BE 6VAC FOR THE UNIT
TO FUNCTION PROPERLY. SLOAN EL-386 OR EL-451 IS RECOMMENDED
(120 VAC/6VAC) OR ELG-220 (220VAC/6VAC).
1.
Remove
one of the knockout caps and route the transformer wire trough it inside
wall box.
NOTE: Use a conduit pipe to protect the transformer wire from damage during
installation.
2
.
Finish the wall
as instructed above.
!!! IMPORTANT !!!
3