18
7240
6
2022
-
E300
MG_0524
Wiring Diagram 48V Thruster
++
12V
THRUSTER
BATTERY
++
12V
THRUSTER
BATTERY
++
12V
THRUSTER
BATTERY
++
12V
THRUSTER
BATTERY
Fuse 5A
The Top wiring setup is for a single
bow or stern thruster system
Automatic Main Switch *
ANL Fuse
++
12V
THRUSTER
BATTERY
++
12V
THRUSTER
BATTERY
++
12V
THRUSTER
BATTERY
++
12V
THRUSTER
BATTERY
Fuse 5A
Automatic Main Switch *
ANL Fuse
The below represents the wiring
setup using a dual thruster system
with a bow and stern thruster.
WARNING
Battery terminal polarity must be
observed and connected correctly
IMPORTANT
AMS must be supplied with 24V only
(Use AMS serial #0 017664 or higher)
S-Link Spur cable
S-Link Spur cable
S-Link Backbone cable
S-Link Backbone cable
Refer to the User and Installation Manual of the
control panel to be installed for detailed installation
instructions.
See S-Link System Description chapter for detailed
information on installation of S-Link Power cable
and additional S-Link components.
Selection of battery, fuse, main switch and cable cross section is described in
Electrical
Installation
chapter.
S-Link Spur cable
Control
panel
*Automatic Main Switch can be replaced by a fuse holder and manual main switch.
Electrical Reference
Guide
MC_0526
Model Size
System
Voltage
Nominal
current
*Min.
battery
CCA
Rec.
fuse
Cross Section Guide for Power Cables
Unit
<7m
total + & -
7-14m
total + & -
15-21m
total + & -
22-28m
total + & -
28-35m
total + & -
36-45m
total + & -
Min.
Rec.
Min.
Rec.
Min.
Rec.
Min.
Rec.
Min.
Rec.
Min.
Rec.
E300/300
48V
360 A
DIN: 400
SAE: 760
EN: 680
ANL 325
mm²
50
70
50
70
70
95
95
120
120
120
140
NA
AWG
1/0
2/0
1/0
2/0
2/0
3/0
3/0
4/0
4/0
4/0
4/0
NA
eVision thrusters have high effi ciency and can therefore offer long run times. The proposed cable cross sections in above table are only for reference.
Dependent on system voltage, the stated nominal current is measured with 21V or 42V at the motor terminals.
Lover voltage level at the motor terminals will increase the current drawn by the thruster. To avoid signifi cant voltage drop and excessive heat
generation in cables and other system components selection of battery and cable cross section is critical.
Higher current consumption can also be caused by incorrect thruster installation and marine growth in the tunnel and on the propeller.
Current draw will depend on many factors such as but not limited to:
•
Voltage drop
•
Battery health
•
Cable lengths and dimensions
•
Performed tunnel installation
•
Ventilation
•
Obstructing marine growth
For each installation an experienced electrician should be consulted for cable cross section calculations and selection of fuses, main circuit and
batteries.