background image

6. Use the flue brush to clean the pinned flueways

between the sections.† A wire brush may be used
to remove any carbon accumulation that may have
developed in the combustion chamber. Vacuum the
loose soot and debris from the boiler.

7. Inspect the burner combustion head. Clean if nec-

essary and make sure all the adjustments are cor-
rect. (See burner data pages for the burner
installed.) Replace oil nozzle with new one and
readjust electrodes. To insure proper burner opera-
tion ONLY THE NOZZLES SPECIFIED IN THIS
MANUAL OR ON THE BURNER LABEL SHOULD
BE USED FOR REPLACEMENT.

8. Protect all of the fireside surfaces by swabbing with

neutral mineral oil.

9. Close main cast iron burner door (door on which

burner is mounted). Make sure that the entire seal
(fiberglass rope) is making good contact with the
boiler casting when replacing 3/8-16 x 1” long hex
head bolt and tightening.

10. Check the flue collector seal. This is the flat rope

seal on top of the heat exchanger. The rope must
be in place adjacent to the long bosses on front and
rear sections and adjacent to the short bosses on
the intermediate sections. The rope should be
directly under the flue collector flanges when the
flue collector is replaced. Use the two 1/4-20 x 3/4”
washer hex head screws to fasten the flue collector.
In order to assure a proper seal be sure that the
flue collector is compressing the flat rope and not
hanging up on the section bosses. Tighten the two
screws.

D.If boiler room is damp, provide ventilation.

II. PROVIDING PROTECTION FOR FREEZING

Anti-freeze is sometimes used in hydronic heating sys-
tems to protect against freeze-up in the event of power
failure, or safety control shutdown when the building is
unoccupied. It should be recognized that unless the
building is kept above freezing temperature by some
means, the plumbing system is not protected.

PROPYLENE GLYCOL is used in the quick-freeze food
industry; it is practically non-toxic. Its use may be permit-
ted when indirect water heaters are used. When anti-
freeze must be used, inhibited propylene glycol is recom-

mended. Useful information on the characteristics, mixing
proportions, etc. of glycol in heating systems is given in
Technical Topics No. 2A, available from the Hydronics
Division of GAMA, 35 Russo Place, Berkeley Heights, NJ
07922. Consult glycol manufacturers for sources of propy-
lene glycol.

DO NOT USE ETHYLENE GLYCOL BECAUSE IT IS TOXIC.

III. OIL BURNER

Inspect and clean annually and following any period of
improper operation. Recheck and adjust settings as speci-
fied for burner model and nozzle size.
Set burner air and draft regulator, using test instruments
to obtain recommended CO

2

and draft without smoke.

See the Burner Data page in this manual that corre-
sponds to the burner installed.

IV. GENERAL MAINTENANCE

These operations are recommended to be performed at
regular intervals:
A.BOILER HEATING SURFACES: clean off all coatings

found. Reseal covers.

B.BOILER CONTROLS: check contacts, settings, correct

functioning.

C.PIPING: check piping and accessories for leaks.
D.CHIMNEY or  STUB VENT and BREECHING: check for

obstructions and leaks.

E.COMBUSTION AIR TO BURNER: check for continued

POSITIVE supply of air as required. Air needs are
greatest in coldest weather. Refer to AIR SUPPLY,
page 3.

F. WATER SYSTEM: check

1. System to be full of water and pressure to remain

stable (between 12 psi and 25 psi).

2. Air-control system: noise and air binding in radiation

should not occur.

3. Water lines: slightest leaks should be corrected.

G.BOILER ROOM AIR SUPPLY: air vents should be open

and free of obstruction. See page 3.

A flue brush (2-1/4" dia.) is supplied with boiler.
Replacements are available from dealer or
hardware stores.

XL-2000

9

Summary of Contents for XL-2000

Page 1: ...must con form to the requirements of the authority having jurisdiction or in the absence of such requirements to the Installation of Oil Burning Equipment ANSI NFPA 31 latest edition and to the National Electrical Code ANSI NFPA 70 latest edition The installation must also conform to the additional require ments in this Slant Fin Instruction Manual Where there is any difference the more stringent ...

Page 2: ...y output The net I B R output ratings shown are based on an allowance for piping and pickup of 1 15 water or 1 33 steam D O E capacity output is divided by the allowance to obtain net rating The Slant Fin Technical Service department should be consulted before selecting a boiler for unusual piping and pickup requirements such as intermittent system oper ation extensive piping etc Ratings apply to ...

Page 3: ...models and rating table shown on page 2 for chimney sizes B Check chimney condition Existing chimneys and stacks may have deteriorated with out repairs their use would be hazardous Before connect ing to an old chimney or stack 1 Clean it 2 Inspect it thoroughly 3 Remove obstructions 4 Replace worn sections of metal stacks 5 Seal bad masonry joints 6 Repair damaged lining C Where more than one appl...

Page 4: ...space If there is NOT sufficient air for combustion due to tight construc tion or other conditions it REQUIRES AIR FROM OUT DOORS SEE ACTION REQUIRED column at right See NOTE 2 below Action Required NONE Provide air from outdoors directly through a permanent out side wall opening or openings with a free open area of not less than 1 sq in per 4000 Btu hr of TOTAL input of ALL fuel burning appliance...

Page 5: ...s located in confined spaces Air from out doors See Table 2 2 4 Figure 3c Appliances located in confined spaces Air from out doors through ventilated attic See Table 2 2 4 Figure 3d Appliances located in confined spaces All air from outdoors through ventilated crawl space and outlet air to ventilated attic See Table 2 2 4 ...

Page 6: ...e are used to control system pressure in an AIR COLLECTING SYSTEM Within the system after initial start up and venting air is collected in the tank and acts in contact with the water to control pres sure see dashed area in figure 5 and paragraph E Air is not vented from this system except at radiation high points see C If system pressure needs further control add another tank in parallel with the ...

Page 7: ... E Install barometric draft regulator on horizontal breeching near chimney with hinge horizontal and face vertical condi tions permitting as in Figure 3a See Figure 3b as a second choice See manufacturer s instructions packed in carton with barometric draft regulator F If two or more appliances are used on the same chimney see CHIMNEY page 3 G Make up all joints with minimum air leaks secure with ...

Page 8: ... high limit switch should open and the burner should shut off automatically If the high limit does not operate to shut off the burner the high limit or the wiring is faulty Repair or replace immediately CARE AND MAINTENANCE I EXTENDED SHUTDOWN CLEANING OR REMOVAL OF BOILER FROM SERVICE DANGER Use CAUTION when handling chemicals and draining hot water from a boiler Scalding water and or chemicals c...

Page 9: ... the building is kept above freezing temperature by some means the plumbing system is not protected PROPYLENE GLYCOL is used in the quick freeze food industry it is practically non toxic Its use may be permit ted when indirect water heaters are used When anti freeze must be used inhibited propylene glycol is recom mended Useful information on the characteristics mixing proportions etc of glycol in...

Page 10: ...XL 2000 10 ...

Page 11: ... 4 65 Closed XL 50 99 FRD 1 80 1 75 60 B DELAVAN 105 4 20 Open 71399 00F XL 50 2 00 1 75 60 B DELAVAN 130 5 40 Open BOILER MODEL CARLIN BURNER MODEL 2 3 FIRING RATE NO 2 OIL GPH SIZE GPH ANGLE AND TYPE MFR NOZZLES OIL PUMP PRESSURE SETTING PSIG A APPROXIMATE HEAD SETTING NO APPROXIMATE AIR BAND OPENING 1 SHUTTER NON ADJUSTABLE NOTES 1 Single slotted air band for XL 20 and XL 30 double slotted air ...

Page 12: ...ATE NO 2 OIL GPH SIZE GPH ANGLE AND TYPE MFR NOZZLES OIL PUMP PRESSURE SETTING PSIG APPROXIMATE AIR SHUTTER SETTING NO 1 APPROXIMATE AIR BAND SETTING NO STATIC DISK DIAMETER INCHES NOTES 1 Blank closed air band for XL 20 2 slot band for XL 30 4 slot band for XL 40 and 8 slot air band for XL 50 2 See PRECAUTIONS BEFORE STARTING OIL BURNERS and START UP on page 7 and burner figures on this page 3 Al...

Page 13: ...E MFR OIL PUMP PRESSURE SETTING PSIG APPROX HEAD SETTING NO APPROX AIR SHUTTER SETTING NO XL 20 R 40 F 3 48 0242 100 XL 30 R 40 F 5 48 0243 100 XL 40 R 40 F 5 48 0244 100 XL 50 R 40 F 10 48 0245 100 70 SS 80 ES 1 1 0 85 70 ES 1 1 15 0 85 70 ES 1 1 35 1 2 80 B 1 1 5 1 2 80 B 1 1 8 1 5 60 B DELAVAN 145 1 3 8 HAGO 170 1 3 1 2 HAGO 140 1 2 6 HAGO 185 1 3 2 DELAVAN 130 3 4 DELAVAN 160 4 4 75 Figure 7A ...

Page 14: ... manual AIR ADJUSTMENT PLATE 4 should line up with the SETTING INDICATOR 2 on the fan housing cover Once set the air adjustment plate should be secured in place by tightening SCREWS 3 and 5 For F 10 model manually open and release the hydraulic air shutter to ensure it has free movement 3 The final position of the air adjustment plate will vary on each installation Use instruments to establish the...

Page 15: ...SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Slant Fin Corp 1996 ...

Reviews: