Slant/Fin VHS-180 Installation And Operating Instructions Manual Download Page 16

V

ICTORY 

II 

VHS Models

16

Summary of Contents for VHS-180

Page 1: ...is under positive pres sure when it is connected to the outdoors with 3 diameter pipe Leakage from this system can be hazardous and if not avoided can result in death or serious injury In addi tion to...

Page 2: ...b Gas Type 2000 3000 4000 5000 6000 7000 8000 9000 10000 Orifice Size for Sea Level Orifice Sizes for High Altitudes Includes 4 Reduction for Each 1000 Feet Elevation Feet Orifice sizes indicated for...

Page 3: ...ces so fueled shall not be installed in an above grade under floor space or basement unless such loca tion is provided with an approved means for removal of unburned gas Consult Chapter 5 of the 1994...

Page 4: ...g with a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances input IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT THE AREA OF FREE OPENINGS MUST BE APPR...

Page 5: ...mble Part Numbers and more information B Vertical Venting Figure 7 shows typical vertical venting A fire stop is required for each ceiling and floor penetration An existing chimney see Figure 8 may be...

Page 6: ...Ft Altitudes 5500 to 7000 Ft Altitudes 7000 to 10 000 Ft Altitudes Equivalent Length of each 90 Elbow Ft Max Equivalent Length Ft VHS 30 30 30 30 6 2 60 90 and 120 VHS 150 30 30 15 6 2 VHS 180 30 15 1...

Page 7: ...of Snow Line Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to The height should be used as the SNOW LINE Definition of Snow Line Knowledge of local co...

Page 8: ...VICTORY II VHS Models 8 Figure 7...

Page 9: ...VICTORY II VHS Models Figure 8 9...

Page 10: ...to an unlined masonry chimney If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exposed chimney it must be re lined with a UL listed metallic liner system See Ta...

Page 11: ...ey height VHS 180 and connector length restrictions 10 9 1999 edition 2 Connector may have to be upsized to 6 diameter to meet requirement of 10 9 Additional National Fuel Gas Code Boiler Gas Applianc...

Page 12: ...VICTORY II VHS Models 12 Figure 9...

Page 13: ...VICTORY II VHS Models Figure 10 13...

Page 14: ...dix C of National Fuel Gas Code ANSI Z223 1 latest edition C The boiler and its gas connection must be leak tested before placing the boiler in operation Use liquid soap solution for all gas leak test...

Page 15: ...sizes see dimensions on page 2 Shut off valves are recommended 2 Circulating Systems Victory II boilers are equipped with a water circulating pump mounted to the return water connection on the boiler...

Page 16: ...VICTORY II VHS Models 16...

Page 17: ...VICTORY II VHS Models Figure 14 Figure 15 Piping Arrangement 17...

Page 18: ...er equipment PIPING A HEATING COOLING SYSTEM TO A WATER BOILER AND CHILLER Figure 16 illustrates a method of piping a heating cooling sys tem to a water boiler and a chiller Hand valves shown or autom...

Page 19: ...9 Set thermostat to desired setting 10 If appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service or gas supplier To Turn Off Gas to Appliance 1 Set therm...

Page 20: ...ports are on top of main burner tube C Main Burner Ignition Checkout and Pilot Adjustment 1 The pilot flame must not smother or snuff out when tested as follows a Main burner ignition from cold start...

Page 21: ...This section must be brought to the attention of the owner by the installer so that the owner can make the necessary arrangements with a qualified service agency for the periodic care and maintenance...

Page 22: ...d on burners to collect any foreign material in cleaning flues 1 Remove control box see instruction under Safety Check See Figure 20 2 Remove jacket top 3 Remove inducer assembly 4 Remove flue collect...

Page 23: ...OR CONTINUES TO RUN NATURAL GAS S8600F IGNITION SPARK CONTINUES PILOT VALVE REMAINS OPEN UNTIL SYSTEM IS RESET SPARK GENERATOR OFF MAIN VALVE OPENS MODULE MONITORS PILOT FLAME NO NO NO NO YES YES YES...

Page 24: ...e blower motor 8 Check voltage 120V at motor connector Replace defective motor 9 Defective transformer 9 Replace Aquastat 10 Defective gas valve 10 Replace BURNERS WILL NOT SHUT OFF CAUSE REMEDY 1 Def...

Page 25: ...nd venting system 4 Condensation trap is not full of water 4 Check and fill with water 5 Venting system is physically damaged 5 Check carefully and repair Also see Venting System Regular Inspection 6...

Page 26: ...ystem b Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe...

Page 27: ...SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com...