background image

2

P/N 473921000

Vent Terminal Installation Requirements

Through the wall termination installation shall conform to 

requirements of authority having jurisdiction or in absence 

of such requirements 

• Canada

 Current Edition of Canadian Standards 

Association CSA B139, 

• United States

 ANSI/NFPA 31. 

Canadian Installation

Refer to figure 2, vent terminal shall not terminate :

A.  Directly above paved sidewalk or paved driveway that 

is located between two buildings, and serves both. 

B.  Less than 7 feet (2.13m) above any paved sidewalk or 

paved driveway.

C.  Within 6 feet (1.80m) of a window, door, or 

mechanical air supply inlet to any building, including 

soffit openings.

D.  Above gas/regulator assembly within 3 feet (1m) 

horizontally of center-line of regulator.

E.  Within 6 feet (1.80m) of any gas service regulator 

vent outlet or within 3 feet (1m) of any oil tank vent 

or any oil tank fill inlet.

Introduction

• Direct Vent refers to sealed combustion system.
• Draft regulator (furnished with standard chimney vent 

boiler) is not used for direct venting.

• Direct Vent series is ideal for applications where a 

conventional chimney is unavailable, not easily installed; 

electrically heated home being retrofit for oil forced air 

heating for example.

• Direct vented appliances require planning, the range 

of flue lengths is restricted, clearances are critical, and 

national and local codes are strict with respect to safety. 

• Be sure the Boiler can be installed within homes 

physical limitations, and accordance with local codes 

and regulations. Physical limitations include sufficient 

clearance to grade. Avoid vent termination locations 

subject to frequent strong wind gusts. 

• See Table 1

 

for approved venting.

Oil Burners

Riello’s 40BF series Oil burners, are certified for venting 

through the wall using ducted outdoor air for combustion.
Standard Riello 40F Series are not certified for use, in 

direct vent applications.
The oil burner contains a probe to measure overfire 

pressure and a pressure switch which does not permit 

burner to operate if intake or exhaust are blocked.

Figure 1  - Standard Vent Terminal Assembly

DIRECT VENTING OF OIL FIRED BOILERS

F.  Less than 1 foot (0.3m) above grade level within 

6 feet (1.80m) of any combustion air inlet, unless 

appliance is otherwise certified.

G.  Within 6 feet (1.80m) of property line.
H.  Underneath veranda, porch, or deck.
I.  So the flue gases are directed at combustible material 

or at any openings of surrounding buildings that are 

within 6 feet (1.80m).

J.  Less than 3 feet (1m) from inside corner of L-shaped 

structure.

K.  So the bottom of the vent termination opening is 

less than 1 foot (0.3m) above any surface that may 

support snow, ice, or debris.

L.  So the flue gases are directed towards bricks, siding, 

or other construction, in such a manner that may 

cause damage from heat or condensate from flue gas.

M.  Within 4 feet (1.2m) of power venter.

USA Installation

Refer to figure 3, vent terminal shall not terminate:

A.  Less than 7 feet (2.13m) above any adjacent public 

walkway.

B.  Less than 4 feet (1.22m) below, 4 feet horizontally, or 

1 foot (0.3m) above door, window, or gravity air inlet 

of the structure.

C.  Less than 1 foot (0.3m) above grade.
D.  Less than 1 foot (0.3m) from soffit or roof of 

structure.

E.  Less than 3 feet (0.9m) from inside corner of L shaped 

structure.

F.  Less than 5 feet (1.6m) of gas regulator vent outlet, 

or oil tank vent outlet.

G.  Underneath veranda, porch or deck.

Summary of Contents for Q3-4

Page 1: ...ing 12 French Manual 15 P N 473921000 240011797 Rev D 06 07 2018 Information contained in this manual pertains to direct vent boilers equipped with manufacturer installed blocked vent safety control s...

Page 2: ...mination locations subject to frequent strong wind gusts See Table 1 for approved venting Oil Burners Riello s 40BF series Oil burners are certified for venting through the wall using ducted outdoor a...

Page 3: ...3 P N 473921000 Figure 2 Vent Terminal Locations Canada Figure 3 Vent Terminal Location USA VENT TERMINAL LOCATIONS...

Page 4: ...1 As close to appliance as possible 2 Maintains clearance to combustibles 3 Maintains minimum 1 4 inch per foot slope back to appliance 4 Install vent terminal in wall having minimum thickness of 5 a...

Page 5: ...onform to requirements of authority having jurisdiction or in absence of such requirements NFPA 31 Installation Of Oil Burning Equipment U S or CSA B139 Canada and applicable provisions of local build...

Page 6: ...e end of appliance adapter See figure 8 Slip adapter over boiler s cast iron flue collar until it stops Appliance adapter has three screw holes Attach appliance adapter to flue collar using furnished...

Page 7: ...nt hole before any measurements Blocked Vent Safety Shut Off System BVS Oil burners used with this direct vent boiler are equipped with a Blocked Vent Safety shutoff system BVS utilizing a pressure sw...

Page 8: ...mary control characteristics electric spark across electrode tips stops combustion continues 7 Boiler continues to operate and reaches steady state the point at which the system temperature stabilizes...

Page 9: ...ain electrical panel 2 Where Boiler switch is located and switch on and off positions if not obvious 3 Where oil shut off valve from oil storage tank is located 4 To keep area around vent terminal fre...

Page 10: ...Burner Model Slant Fin Oil Burner Part Number Q3 4 40BF3 473024000 Q3 5 40BF5 473025000 Q3 6 40BF5 473026000 Table 1 THIS HIGH EFFICIENCY BOILER IS CERTIFIED FOR USE AS DIRECT VENT BOILER ONLY WITH T...

Page 11: ...10 Riello Wiring Diagram With Post Purge Timer And Blocked Flue Pressure Switch Safety If a neutral or ground lead is attached to terminal 4 the CONTROL BOX on the burner will be damaged should lockou...

Page 12: ...or runs Verify reduced voltage 42 52 Vac between terminals 3 and 7 Ensure good contact between control box spades and sub base terminals Defective control box Replace Motor does not run Verify electri...

Page 13: ...citor Thermal overload Hot motor Burner Starts Burner stays in Pre purge Faulty CAD cell or seeing light before trial for ignition Coil wires on terminals 1 and 2 or 1 and 8 reversed Open coil circuit...

Page 14: ...NCE TABLE Model No Serial No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 0933 Canada Slan...

Page 15: ...nstallation d une chaudi re ou autre appareil au gaz l aide de m thodes ou de composants inappropri s peut entra ner des blessures graves ou m me la mort en raison d un incendie ou de l asphyxie caus...

Page 16: ...quentes et fortes rafales de vent Consulter le tableau 1 pour une vacuation autoris e Br leurs mazout Les br leurs mazout de s rie Riello 40BF sont homologu s pour une vacuation traversant le mur l ai...

Page 17: ...S EXTR MIT S D VENT Entr e d air souffl Min 3 pi 1 m Entr e d air souffl Min 12 po 30 cm Min 7 pi 2 13 m Niveau du sol Min 4 pi 1 2 m Extr mit Moins de 10 pi 3 m Entr e d air souffl Remarque les dista...

Page 18: ...ON DES CANALISATIONS D ENTR E D AIR Installation des canalisations d entr e d air pour les syst mes vacuation directe Ne pas utiliser de conduits souples pour l apport d air n cessaire la combustion L...

Page 19: ...nts fines 24 dents par pouce 6 Les extr mit s m le et femelle des raccordements et adaptateurs de l appareil doivent tre nettoy es l aide d un solvant de nettoyage freins qui ne laisse pas de r sidus...

Page 20: ...onte le collier de serrage du tuyau jusqu ce qu il s arr te L adaptateur pour appareil a trois trous de vis Fixer l adaptateur pour appareil au collet d vent l aide de la m che fournie pour pr forer l...

Page 21: ...o R ins rer le couvercle de plastique dans l orifice de r glage de l apport d air avant toute mesure Dispositif de s curit en cas d obstruction de l vacuation BVS Br leurs huile vacuation directe util...

Page 22: ...ncipale l tincelle lectrique entre les pointes d lectrodes cesse et la combustion se poursuit 7 La chaudi re continue de fonctionner et atteint son tat d quilibre c d le moment o la temp rature du sys...

Page 23: ...ral de la maison 2 L endroit o se trouve l interrupteur de la fournaise et l organisation des positions de marche on et d arr t off si a n est pas vident 3 L endroit o se trouve la soupape d arr t pri...

Page 24: ...ucteur simple paroi du tuyau d air d Connexion br leur Riello Tableau 2 R glages pr liminaires du br leur RIELLO 40BF VACUATION DIRECTE Mod le de chaudi re Type de r gulateur Profondeur d insertion Ta...

Page 25: ...lectrique est r alis la borne 4 o sur la BASE En cas de d rangement la BO TE DE COMMANDE 530SE fournira une source d nergie de 120 V ca la borne de raccordement L appel de courant maximum permis sur l...

Page 26: ...r l alimentation lectrique Le moteur fonctionne V rifier la tension r duite 42 52 V ca entre les bornes 3 et 7 S assurer du bon contact entre les bornes embrochables de la bo te de commande et les bor...

Page 27: ...ume Le br leur s allume lors du pr balayage La cellule au sulfure de cadmium est d fectueuse ou la lumi re est visible avant l essai d allumage Les fils bobiner sur les bornes 1 et 2 ou 1 et 8 sont in...

Page 28: ...N de mod le N de s rie Date d installation Installateur Contact Adresse Code postal N de t l phone N d urgence SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 0933 Canada Sla...

Reviews: