HOT WATER/GAS
MULTIPLE AND
CASCADING BOILERS
APPLICATION GUIDE
Printed in the U.S.A. 711
Publication No. CJ-10-HWG
www.slantfin.com
Guidelines for the design, purchase and installation of Slant/Fin Jaguar J-390C Caravan gas-fired, hot water multiple boiler systems.
®
CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . .2
Boiler room design & layout . . . . . . . . . . . . . . . . . . . . . .4
Fresh air and contamination prevention . . . . . . . . . . . . .6
Piping and Wiring Flow
Boiler room air supply & ventilation . . . . . . . . . . . . . . . . .6
Venting requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Water piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Condensate removal . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Gas line sizing and layout . . . . . . . . . . . . . . . . . . . . . . .16
Jaguar Multiple Boiler System Control . . . . . . . . . . . . .18
Cascading – Jaguar link method and wiring . . . . . . . . .19
Reset curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
External signal & energy management (Tekmar 275) . . . . . . .28
Hybrid Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . .34
CODES AND STANDARDS
All Caravan installations must comply to local codes or, in the
absence of local codes, to the National Fuel Gas Code, ANSI,
Z223.1-latest edition.
In addition where required by the authority having jurisdiction, the
installation must conform to American Society of Mechanical
Engineers Safety Codes for controls and safety devices for
automatically fired boilers, No. CSD-1. The installation must also
conform to the additional requirements of Slant/Fin Instruction Book
publication no. J-40 latest edition.
All electrical wiring is to be done in accordance with the National
Electrical Code ANSI/NFPA No. 70-latest edition and all local electri-
cal codes. The unit must be electrically grounded if an external
power source is used.
In Canada, the installation must be in accordance with standards
CGA B149.1 and B149.2, installation codes for gas burning
appliances and equipment and/or local codes. All electrical
connections are to be made in accordance with Standard C.S.A.
C22.1 Canadian Electrical Code Part 1 and/or local codes.
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can
cause scaling and leave deposits in the boiler and the surrounding
pipes. This will lead to inefficient boiler operation and breakdown.
Fresh water will enter the system as a result of hidden leaks such
as may occur in underground piping. Relief valves should be piped
to a location that shows visible signs of relief.
Process applications that use fresh water, require the use of heat
exchangers. Any process application that results in introduction of
fresh water into a boiler can cause scaling with deposits forming in
the boiler and surrounding piping. This will damage the boiler.
Introduction of fresh water from leaks will cause similar damage.
In some areas it may be necessary to use a feed water treatment to
control the corrosive makeup of the feed water. Check with the local
authority, to determine if the feed water will need a conditioning
treatment before being supplied to the boiler.