MouNTiNg CoNSiDerATioNS
3.1 General Mounting
Each type of mounting system requires a specific mounting bracket. Most are available from Skyblade
Fans. Check with the contractor, building owner, or architect to ensure the structure is sound and
will support the weight of the fan before beginning installation. Skyblade Fans provides guidelines for
mounting fans; however, it is the sole responsibility of the building owner and installer to ensure the
safety of the mounting system, that the building structure is sound, and the installation complies with
all federal, state, and local codes.
3.2 Weight
A Standard 1.35-horsepower, TurboProp Series 14 foot 8-blade fan and mounting assembly weighs
about 206 pounds. In inverted-blade applications designed to blow air upward, there is an additional
downward force of about 80 pounds due to fan thrust. We recommend applying a safety factor of 2
times the stated hanging weight of the fan when determining the capabilities of the building structure.
3.3 Safety Cable
A Skyblade fan should never be run without proper installation of Safety Cables. These are supplied
with every fan. You must install safety cable for warranty to be in effect.
3.4 Guy Wires
While in operation a fan can sway due to minor imbalance or because of wind. Since the mounting
system is capable of swiveling, it will not stop fan movement, so it is important that the guy wires be
installed properly. Proper installation includes the angle and tension of the guy wires. See page 22-23
for more information.
3.5 Universal Mounting Hardware
We recommend mounting the fan to a horizontal structural beam, however, this is not always possible
in buildings with pitched roof construction. For this reason, our universal mounting system is designed
to allow the fan to hang in a level position perpendicular to the ground by rotating the upper yoke 90
degrees.
When cutting or drilling into a wall or ceiling, take care not to damage electrical wiring or other utilities.
Lorsque vous coupez ou percez un mur ou un plafond, prenez garde à ne pas endommager les fils
électriques ou d’autres services publics.
Select a location that is free from obstructions that may interfere with the fan’s operation.
Choisissez un emplacement qui est libre de tout obstacle pouvant interférer avec le fonctionnement
du ventilateur.
CAUTION/ATTENTION
!