background image

Configuration Manual

SC8100
SC8110

Summary of Contents for SC8100

Page 1: ...Configuration Manual SC8100 SC8110 ...

Page 2: ......

Page 3: ...de USB upgrade Restoring appliance settings Disposal Battery replacement Cleaning of appliance Electrical characteristics Physical characteristics Environmental characteristics Battery backup Access Administrator account user ID and pass word Root account user ID and password Settings recovery Password recovery Quick configuration Alert actions Message format Object map Timer Server ping IP camera...

Page 4: ... from Firefox and Chrome browser per form additional configuration tasks and begin to monitor the environment Analog sensors Temperature sensor SC500 Outdoor temperature sensor SC501 Humidity sensor SC510 AC voltage monitor SC520 Access sensor SC530 Vibration sensor SC540 Smoke sensor SC560 Related documents Unless otherwise noted the following documen tation is available on the CD provided with t...

Page 5: ...C591 Current loop converter 4 20 mA SC420 CAN modules Airflow and tempera ture control CAN unit SC450 with water leak cable SC559 Modules Dry contacts unit SC16 GSM modem SC920 CAN sensors PIR vibration tem perature CAN sensor SC470 Smoke humidity and temperature CAN sen sor SC460 3 ...

Page 6: ... 6 LEDs ACT indicates appliance status CN1 indicates CAN1 bus traffic CN2 indicates CAN2 bus traffic ERR indi cates error and traffic 7 CAN two equivalent digital connectors RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus with auto sensing 8 TR CAN terminator required for a con nection of large amount of sensors or for long distance connection of CAN sensors 9 A1 A8 8 RJ12 a...

Page 7: ...nnector IEC C13 Maximum output power for each relay 10A 240V 17 RLY1 RLY4 4 relays output connectors The relays maximum power output 5A 240V 18 SMA optional hole for mounting SMA antenna of GSM modem 19 DC 12V backup power socket to con nect a battery or a battery backup 20 Dry contacts empty slot for dry contacts module SC16 used to connect dry con tacts on doors windows etс ...

Page 8: ... transportation contact the appropriate delivery service Inventory Description Monitoring unit SC8100 19 rack brackets 2 pcs M3 x 8 Phillips flat head screws 6 pcs Self adhesive rubber foot 4 pcs Description 1 8 m NEMA 5 15P to IEC 320 C13 power cord 1 8 m NEMA 5 15P to IEC 320 C13 power cord only SC8110 RJ45 1m patch cable USB miniUSB cable Backup battery 3 5mm terminal plug 6 ...

Page 9: ...Inventory Description Relay terminal plug 5 08 mm 1 pc only SC8100 Relay terminal plug 5 08 mm 1 pcs only SC8100 CD ROM with documen tation and software Configuration manual Warranty card 7 ...

Page 10: ...d Network cable con nection 8 Installation of appliance The unit can be installed in the front or rear of the rack or can be put on the shelf using self adhesive rubber feet It takes up 1U of 19 rack When installing consider the following condi tions nect approved devices to ports on the unit as di rected in this manual Plugging in other devices may result in equipment damage Connect the unit only...

Page 11: ...tion This procedure applies to the following sensors which are supported by the appliance and are connected to the analog ports Icon Analog sensors Temperature sensor SC500 Outdoor temperature sensor SC501 Humidity sensor SC510 Voltage detector SC520 Access sensor SC530 Smoke sensor SC560 Appliance connections 3 Plug the power cable into the power source 9 ...

Page 12: ...re shown on p 3 Connect CAN sensors to any CAN port CN1 or CN2 on the appliance using an FTP CAN RJ 12 6P6C cable supplied CAN sensors can also be connected to the port of another Sky Control CAN sensor or CAN device connected to appli ance by CAN bus Determination of the sensor type and connection will occur automatically You can connect up to maximum 40 digit al CAN sensors and CAN devices toget...

Page 13: ...ppliance The reader is determined automatically of the device type and connection will occur automatically I Touch Button connection Readers I BUTTON have two wires 1 Ground GND 2 Data wire BUS I BUTTON reader ground is connected to the GND pin on RJ9 connector Data wire of I BUTTON reader is connected to the BUS contact on RJ9 connector 11 ...

Page 14: ... relays have independent separate entrances and exits In case of SC8110 Connection of loads to SC8100 To connect an external load connect the wires from the external power supply to the appropri ate medium 2 clamps of the relay terminal plug the load to the left 1 or right 3 clamps of the plug Insert the plug into the relay socket terminal RLY1 RLY4 By command relay will switch on or off the load ...

Page 15: ...attery voltage exceeds over the appliance USB camera connection If necessary by means of attached cable USB A MiniUSB AB you can connect any USB camera of class Linux UVC Webcam to connector HS Determination of camera and connection will occur automatically List of possible USB cameras We recommend 1 Logitech С160 Logitech С270 Logitech С510 Extension units connection To install and to connect ext...

Page 16: ...ontacts module on 3 steel spacing sleeves inside the appliance case attach the board with three M3 screws from supply to the sleeves 3 Connect 10 pin flat cable to the connector on the module card and on the appliance motherboard Close and fasten the cover 4 If necessary connect dry contacts to the module with appropriate 3 5 mm terminals from supply 14 Installation ...

Page 17: ...nut from the supply holding SMA con nector with one key securely tighten the nut with the other key Do not tighten SMA connector with one key you can break the cable and the con nection would be lost 4 Connect 16 pin flat cable to the connectors on the modem card and on the appliance motherboard Close and fasten the cover If necessary install the SIM card into the appropriate hole 2 3 4 2 Set up t...

Page 18: ...ce are 1 IP address 192 168 0 193 2 Netmask 255 255 255 0 3 Other parameters are not set Network settings configuration If you accidentally lost the IP address of your current appliance and you need to know it simply connect an empty USB flash drive to the appliance USB connector the system will automatically copy the file dumplog with some settings including IP address onto the flash drive Wait u...

Page 19: ...ame Plug the USB flash drive into the appliance socket USB and wait The update process is displayed on the front panel with flashing LED ERR If successful the ERR LED will go off and ACT LED will blink for a while with increased frequency If unsuccessful ERR LED will remain lit Test the appliance IP address will be in the first lines of this file In the appliance interface go to the folder Pref er...

Page 20: ...nistrator as follows In such case you may get the following mes sage Message format Logic scheme name if S N iButton id 13 in state alarm then Email id 302 changes to state on im mediately Relay 0 id 31 changes to state pulse immediately S N iButton id 13 in state alarm 12 40 36 2012 01 18 By default a map of some object is shown in the appliance interface To change the map go to the folder System...

Page 21: ...nd click Fill in empty fields give name to created element and save Server ping IP cameras 19 Initial Configuration To add an IP camera go to the folder Add in the upper left corner of the web interface select item Add IP camera and click Fill in empty fields give name to created camera and save To create a group go to the folder Add in the upper left corner of the web interface select item Add Gr...

Page 22: ...t or Delete Save If necessary the existing user access database can be saved to a file or this file can be used to create new database in another device or to restore the database In order to do so go to the folder Preferences in the appliance web interface select folder Access control click on appropriate item Download users database or Upload users database 20 Initial Configuration Sensor config...

Page 23: ... sky25firmware sky the system settings file sky25settings sky or and reset the pass word file sky25resetusers sky into the root of USB flash drive without changing the file names Plug in USB flash drive into the input USB and wait The files have predefined names and are analyzed in the order listed when connecting to USB input Running the upgrade script will be recorded in the log Test the system ...

Page 24: ...cover turn the power on and test the system motherboard If the appliance has a GSM mo dem it must be turned off disconnect modem cable from modem connector J5 Close the cover of appliance turn the power on connect cable USB A miniUSB port to PC USB input and NS input of appliance The PC will detect the new USB device and will report that it can run faster Start the New Hardware Wizard Cancel the s...

Page 25: ...emove it Check the place of battery installation for the absence of water stains or other damages insert a new battery close the unit cover and connect the power supply After connecting synchronize the date and time If you can not use the SR44 battery it is pos sible to install LR44 batteries however bare in mind that these batteries can have a shorter period of storage and use and that the alcali...

Page 26: ...sical characteristics Value Dimensions W x H x D 440 x 44 x 70 mm Weight SC8100 2 1 kg Weight SC8110 2 3 kg Environmental characteristics Value Operating temperature 0 to 70 C Storage temperature 25 to 85 C Operating humidity 0 to 90 non condensing Storage humidity 0 to 95 non condensing Battery backup Value Backup battery voltage nominal 10 12V DC The maximum backup current 1 5 А 24 Technical par...

Page 27: ......

Page 28: ...www skycontrol com ...