background image

DOL 534 • DOL 539

Circuit Diagrams and Cable Plans

9

1.3 Combi-Tunnel

FarmOnline Explorer

Aux. sensor

Pressure

sensor

CO2

Alarm

NH3

Stand-alone heaters Solenoid

valve

Side mode

Step 1 Step 2

Step 16 Tunnel cooling

Blow heater

Air circulator

Heating

Cooling

Tunnel mode

Step 1Step 2

Step

16

Rack & Pinion

Wall inlet

Front and Rear

High pressure cooling in tunnel inlet

Outside humidity sensor
Outside temperature
sensor

Humidity sensor

Temperature

sensor

Temperature sensor
Tunnel cooling sensor

1.4 Tunnel-Plus

FarmOnline Explorer

Aux. sensor

Pressure
sensor

CO2

Alarm

NH3

Stand-alone

heaters

Solenoid valve

Side mode

Wall fan

Blow heater

Air circulator

Tunnel cooling

Tunnel mode

Outside humidity sensor
Outside temperature sensor

Humidity sensor

Temperature sensor

Tunnel cooling sensor

Pad alarm temperature sensor

Wall inlet

Summary of Contents for DOL 539

Page 1: ...61 2021 03 26 Software version 7 3 English For other language variants of this document we refer to Espa ol Para otras variantes del idioma de este documento visite Fran ais Pour les versions dans d a...

Page 2: ......

Page 3: ...directive No 98 58 EU an alarm system must be installed in all mechanically ventilated houses We would like to draw your attention to the fact that the product liability clause of general terms and c...

Page 4: ...onnection via the installation menu of the controller 17 3 3 Automatic registrations of of extra I O modules 17 3 4 Setup of modules 18 3 5 Positioning of jumper 18 3 6 Printing the Installation Setup...

Page 5: ...700 LPC 1x230 V 44 5 6 6 DA 1700 LPC 3x400 V or 3x230 V 45 5 6 7 DA 1700 3x400 V or 3x230 V 45 5 7 Fan speed controller 46 5 7 1 Internal fan speed controller two parallel fans 46 5 7 2 DOL 31 fan spe...

Page 6: ...erature humidity sensor 65 5 13 3 DOL 53 NH3 ammonia sensor 65 5 13 4 DOL 19 CO2 sensor 66 5 13 5 Sub pressure gauge 66 5 13 6 Current sensor 67 5 13 7 Dynamic Air sensor 67 5 13 8 Auxiliary sensor 68...

Page 7: ...may therefore contain sections that are not applicable to the livestock house in question 1 1 LPV Low Power Ventilation Pressure sensor Auxiliary sensor CO2 Alarm NH3 Solenoid valve Heating Cooling S...

Page 8: ...r Aux sensor Pressure sensor CO2 Alarm NH3 Stand alone heater Solenoid valve Tunnel cooling Tunnel mode Step 1 Step 2 Step 16 Blow heater Air circulator Outside humidity sensor Outside temperature sen...

Page 9: ...ront and Rear High pressure cooling in tunnel inlet Outside humidity sensor Outside temperature sensor Humidity sensor Temperature sensor Temperature sensor Tunnel cooling sensor 1 4 Tunnel Plus FarmO...

Page 10: ...ng of house controller 1 Place the controller with the display A at eye level for the daily user 2 Remember free space around the cabinet 43 cm B so that the front panel can be placed on top of the ca...

Page 11: ...3 Mounting of auxiliary contactor Contactor or auxiliary relay must not be installed in the controller The contactors cause electrical disturbance which can make the controller reset restart Mount the...

Page 12: ...r supply A is mounted at the side or close to the controller 2 4 2 Power supply 24 V 2 1 A printed circuit board The extra power supply B power supply 24 V 2 1 A printed circuit board can be mounted i...

Page 13: ...e the sensor Cause Above housing equipment The pigs can reach them Near cooling system Water and humidity will affect the sensors In a drafty area So it is directly affected by the air intake Measures...

Page 14: ...th unstable power supply one of the following backup units may be mounted in front of the controller so as to compensate for frequent power failures With without emer gency opening Type of backup unit...

Page 15: ...sed and possibly D The A5 minus terminal is connected in parallel terminal A5 to A5 24 V max 2 1 A 24 V max 2 1 A 24 V max 0 8 A The power supply must be connected to the controller using a multi cond...

Page 16: ...es A maximum of 10 I O modules may be connected of which 2 can be weighing modules When 7 or more I O modules weighing modules are connected the flat cable is supplemented by two wires D with a minimu...

Page 17: ...y opening can override relay so inlet opens OFF Factory setting Emergency opening cannot override relay AI Analogue input DI Digital input DOL 12 DOL 12 input Displayed on I O module Pull down A 1 K p...

Page 18: ...B B15 A and B15 B can be set up to either 0 10V input or output depending on how many are re quired of each type Please note that if the setup of the main module is changed af ter the components have...

Page 19: ...can be opened using MS Excel or a text editor and be printed in the usual way Open the PC simulator and select the File System set tings menu Choose a location for the setup file to be saved Path to...

Page 20: ...The address of the individual module corresponds to the address in the controller s Technical Installation Manual installation Additional I O modules menu Set the I O Modules Rotary switches as follow...

Page 21: ...To obtain a safe communication between the mod ules it is important that the CAN termination jumpers are set correctly The jumper must be ON on the module where communication ends Example of the sett...

Page 22: ...DOL 534 DOL 539 22 Circuit Diagrams and Cable Plans 3 9 Setting CAN protocol jumper CAN protocol jumpers are factory set to CANopen...

Page 23: ...e other cable plans 4 1 Systems without emergency opening SERVICE ROOM OUTSIDE DOL 12 DOL 114 LIVESTOCK HOUSE Controller Alarm system 4 2 Systems with ON OFF emergency opening SERVICE ROOM OUTSIDE DOL...

Page 24: ...ON OFF DA 174 24 V stepless DA 175 24 V stepless DA 175 230 V ON OFF DA 175 230 V stepless DA 175 230 V stepless DA 75A 24 V ON OFF DA 75A 24 V stepless For larger systems see cable plan for MultiSte...

Page 25: ...101 165 m 4 0 mm2 166 265 m Cable dimensions for DA 175 24V DC DA 175 100 DA 175 150 DA 175 300 DA 175 600 Cross sec tion Length Length Length Length 1 5 mm2 0 290 m 0 220 m 0 135 m 0 60 m 2 5 mm2 13...

Page 26: ...n NOTE Number of conductors depends on type of fan DA 74CV stepless 1 DA 74CV stepless 2 Air outlet 1 Air outlet 2 Controller 4 7 MultiStep with external fan speed controller DA 74CV stepless 1 Supply...

Page 27: ...ided into several groups depending on how many there are and the power consumption NOTE Number of conductors depends on type of fan Air outlet 1 DA 74CV stepless 2 Air outlet 2 Controller 4 9 Three ph...

Page 28: ...DOL 534 DOL 539 28 Circuit Diagrams and Cable Plans 4 10 One phase fans Supply voltage for fans is divided into several groups depending on how many there are and the power consumption Controller...

Page 29: ...29 4 11 BF 50 wall fan BF 50 LPC ON OFF Controller Wiring box 1x230V 3x230V or 3x400V 1x230V 3x230V or 3x400V 1x230V 3x230V or 3x400V 1x230V 3x230V or 3x400V 1x230V 3x230V 3x400V 1x230V 3x230V or 3x40...

Page 30: ...DOL 534 DOL 539 30 Circuit Diagrams and Cable Plans 4 12 DA 1700 wall fan DA 1700 LPC 1x230 V Controller Wiring box DA 1700 LPC 3x230 V DA 1700 LPC 3x400 V DA 1700 3x230 V DA 1700 3x400 V...

Page 31: ...DOL 534 DOL 539 Circuit Diagrams and Cable Plans 31 4 13 DA 1700 LPC MultiStep Controller Wiring box 4 14 DA 1700 ON OFF wall fan MultiStep Controller Wiring box...

Page 32: ...nal speed controller Max 6 8 A LPC DOL 38 DOL 31 max 16A Floor heating unit Room heating 24V Room heating 230 V Blow heater Solenoid valve Cooling Tunnel cooling Tunnel cooling 0 10V Stir fan Stir fan...

Page 33: ...energy meter DOL 12 temperature sensor DOL 10 temperature sensor DOL 114 temperature and humidity sensor DOL 53 NH3 sensor DOL 19 CO2 sensor Dynamic Air sensor Pressure sensor Auxiliary sensor DOL 58...

Page 34: ...ndard BK Black Color coding on wires are in accor dance with standard IEC 60757 Letter codes to identify colors used on drawings diagrams labelling etc BN Brown RD Red OG Orange YE Yellow GN Green BU...

Page 35: ...oller GND on K1 6 Cable lead Terminal Cable name Power supply from emergency opening K1 4 DA 74CV winch motor K1 6 loop module Power supply from emergency opening 0V 1 Q1 terminal in controller Power...

Page 36: ...ay contactor solenoid coil solenoid valve or similar is activated The protective diode is mounted in the terminal box on the connected product The area around the protective diode must fit with the cu...

Page 37: ...39 Circuit Diagrams and Cable Plans 37 5 1 6 Overview of connection terminals 5 1 6 1 Power supply K1 1 5 1 6 2 Main module K1 2 5 1 6 3 I O module K1 3 5 1 6 4 Triac module K1 4 5 1 6 5 Loop modules...

Page 38: ...upply 1x230 V PE Alarm light 5 3 Alarm For cable plans see sections Systems without emergency opening 23 and Systems with ON OFF emergency opening 23 Alarm system Alarm system Example of terminal numb...

Page 39: ...1 ON OFF medium and large For cable plan see section Systems with ON OFF emergency opening 23 see also the Technical Manual for emergency opening Medium Large Emergency opening 5 4 2 ON OFF medium and...

Page 40: ...ge For cable plan see section Systems with temperature controlled emergency opening 23 see also the Tech nical Manual for emergency opening Emergency opening Medium Large 5 4 4 Emergency opening with...

Page 41: ...r correct connection see the setup menu Show connection in controller Stir fan Stir fan Example of terminal number For correct connection see the setup menu Show connection in controller 5 5 2 0 10V a...

Page 42: ...ler Fan speed controller Chill unit 5 6 Wall fan 5 6 1 BF 50 LPC ON OFF For cable plan see the section BF 50 wall fan 29 or see the Technical User Guide for BF 50 Analog signal default 10 0V Example o...

Page 43: ...number For correct connection see the setup menu Show connection in controller LPC fan Motor controller LPC 3 x 400 V Wiring box LPC actuator stepless 5 6 3 BF 50 ON OFF EL For cable plan see the sect...

Page 44: ...50 Example of terminal number For correct connection see the setup menu Show connection in controller Fan 3x400V 5 6 5 DA 1700 LPC 1x230 V For cable plan see section DA 1700 wall fan 30 or DA 1700 LPC...

Page 45: ...ignal default 10 0 V Fan Inlet flap LPC Example of terminal number For correct connection see the setup menu Show connection in controller 5 6 7 DA 1700 3x400 V or 3x230 V For cable plan see section D...

Page 46: ...eating cooling and stir fan 32 Example of terminal number For correct connection see the setup menu Show connections in the controller Fan Fan 5 7 2 DOL 31 fan speed controller For cable plan see sect...

Page 47: ...For correct connection see the setup menu show connections in the controller Frequency converter Fan 5 7 4 Frequency converter DA 74CV stepless Dynamic MultiStep For cable plan see section Fan speed c...

Page 48: ...Example of terminal number For correct connection see the setup menu Show connections in the controller LPC motor controller LPC fan 5 7 6 LPC DA 74CO ON OFF Dynamic MultiStep For cable plan see secti...

Page 49: ...DA 74CV stepless Dynamic MultiStep For cable plan see section Dynamic MultiStep with LPC 27 Analogue signal default 10 0 V Example of terminal number For correct connection see the setup menu Show con...

Page 50: ...ch motors 24 Example of terminal number For correct connection see the setup menu Show connections in the controller Fan Winch motor ON OFF 5 8 2 DA 74CV BC stepless For cable plan see section Winch m...

Page 51: ...mple of terminal number For correct connection see the setup menu show connections in the controller Winch motor ON OFF 24V 5 8 4 DA 75A stepless 24 V For cable plan see section Winch motors 24 Exampl...

Page 52: ...ors 24 Example of terminal number For correct connection see the setup menu Show connections in the controller Winch motor stepless 230V 5 8 6 DA 75A stepless 230 V For cable plan see section Winch mo...

Page 53: ...ble plan see section Winch motors 24 Example of terminal number For correct connection see the setup menu show connections in the controller Winch motor 230V winch motors for air intake and air outlet...

Page 54: ...inch motor stepless 24 V Example of terminal number For correct connection see the setup menu Show connections in the controller 5 8 9 DA 175 ON OFF 24 V For cable plan see section Winch motors 24 Win...

Page 55: ...nch motor stepless 24 V Example of terminal number For correct connection see the setup menu show connections in the controller 5 8 11 DA 175 ON OFF 230 V For cable plan see section Winch motors 24 Wi...

Page 56: ...Diagrams and Cable Plans 5 8 12 DA 175 230 V stepless For cable plan see section Winch motors 24 Winch motor stepless 230V Example of terminal number For correct connection see the setup menu Show con...

Page 57: ...with pop holes With stop relay when FreeRange ventilation is used 5 9 1 Air outlet DA 74CO ON OFF fan stop relay For cable plan see section Winch motors 24 Example of terminal number For correct conne...

Page 58: ...relays With stop relay when FreeRange ventilation is used Fans are distributed on phases L1 L2 L3 For cable plan see section Winch motors 24 Fan Winch motor ON OFF Example of terminal number For corr...

Page 59: ...r For correct connection see the setup menu Show connection in controller Detection Only if pull down is displayed in Show connections 5 10 Door opening For cable plan see section Fan speed controller...

Page 60: ...ns 5 11 Door opening using DA 175 For cable plan see the section Fan speed controller door opening heating cooling and stir fan 32 Example of terminal number For correct connection see the setup menu...

Page 61: ...and stir fan 32 Control valve Example of terminal number For correct connection see the setup menu Show connection in controller Circulation pump 5 12 2 Relay heat ON OFF For cable plan see section Fa...

Page 62: ...nd stir fan 32 Control valve Circulation pump Example of terminal number For correct connection see the setup menu show connections in the controller 5 12 4 Floor heating unit 0 10 V 0 10 V actuator D...

Page 63: ...terminal number For correct connection see the setup menu Show connection in controller Blow heater 24V external power supply 0V external power supply 5 12 6 ACU Blow heater air circulator 230 V For c...

Page 64: ...Air circulator Heating Alarm signal 230 V Alarm signal 230 V Indirect blow heater Indirect blow heater 5 13 Sensors 5 13 1 DOL 10 DOL 12 temperature sensor For cable plan see section Sensors water me...

Page 65: ...ample of terminal number For correct connection see the setup menu Show connection in controller Humidity Temperature Temperature humidity sensor 5 13 3 DOL 53 NH3 ammonia sensor For cable plan see th...

Page 66: ...rminal number For correct connection see the setup menu Show connection in controller 5 13 5 Sub pressure gauge For cable plan see section Sensors water meter 24 hour clock light and energy meter 33 S...

Page 67: ...er Current sensor 5 13 7 Dynamic Air sensor For cable plan see section Sensors water meter 24 hour clock light and energy meter 33 Example of terminal number For correct connection see the setup menu...

Page 68: ...er 33 Example of terminal number For correct connection see the setup menu Show connection in controller Auxiliary sensor 5 13 9 DOL 58 weather station For cable plan see the section Sensors water met...

Page 69: ...ct connection see the setup menu show connections in the controller Solenoid valve 5 14 2 High pressure pump 1x230V 3x230V For cable plan see section Fan speed controller door opening heating cooling...

Page 70: ...For correct connection see the setup menu Show connections in the controller 5 14 4 Tunnel cooling 1x230V 3x230V For cable plan see the section Fan speed controller door opening heating cooling and st...

Page 71: ...requency converter Example of terminal number For correct connection see the setup menu Show connection in controller 5 15 Water meter For cable plan see section Sensors water meter 24 hour clock ligh...

Page 72: ...and Cable Plans 5 16 24 hour clock Interval timers For cable plan see section Sensors water meter 24 hour clock light and energy meter 33 Example of terminal number For correct connection see the setu...

Page 73: ...yed in Show connections Example of terminal number For correct connection see the setup menu Show connection in house controller Key Press 5 18 Energy meter For cable plan see section Sensors water me...

Page 74: ...stem A distinction is made between two types of equal pressure system MultiStep air outlet The swivel shutters are controlled by the MultiStep principle and open alternately Stepless air outlet The sw...

Page 75: ...on Winch motors all positions 50 Air outlet The air outlet is connected as an ordinary MultiStep See diagrams in section Winch motors all positions 50 5 19 2 Stepless Recirculation Recirculation fans...

Page 76: ...611861 2021 03 26 en US Made in Denmark SKOV A S Hedelund 4 Glyng re DK 7870 Roslev Tel 45 72 17 55 55 www skov com E mail skov skov dk...

Reviews: