DOL 434 LPV
Technical Manual
49
Exhaustion %
Air inlet %
Sec.
Figure 15: When the ventilation requirement exceeds the capability of the cycle time function, the house controller will again
regulate the ventilation in relation to the inside temperature and air humidity.
6.5.2.5 Comfort
Comfort ventilation
Day
At batch production. Setting the comfort temperature as a curve over two day num-
bers.
Start
[%]
Ventilation degree at which comfort is activated.
Maximum
[%]
Ventilation degree at which maximum comfort temperature is reached.
Comfort factor
Small factor: Slow reaction.
High factor: Immediate reaction.
6.5.3 Heating
6.5.3.1 Room heating and stand-alone heater
Heating is supplied while ventilating. This makes the temperature adjustment as stable as possible and at the
same time it is ensured that ventilation or heating is supplied as soon as it is needed.
However, please note that the ventilation is limited as long as heating is supplied. The more heat is supplied,
the less ventilation is used.
• At 1% heat, ventilation can run up to 10% above the minimum ventilation.
• At 100% heat, the ventilation can only run at minimum ventilation.
Control mode
Setting of control mode: PID - user settings or Adaptive - self learning.
Select Adaptive - self learning for the heating to continuously adapt to the changing
conditions in the house.
When using the adaptive control mode an adaption time can be set (in the menu
Climate | Temperature| Heating
). This will affect how quickly the controller
will react to changed conditions in the house.
See section
for a general description of adaptive control.
Relay control
Cycle time
ON + OFF-time of the heating relay.