DOL 100 I/O Box
Technical User Guide
11
4.4 I/O type 15
I/O type 15 # 1
(A)
I/O type 15 # 2
(B)
(C)
Item
Function
Description
(A)
CAN TERM
The modules are controlled via CAN bus communication. It is important that the CAN
termination jumpers are set correctly in order to achieve secure communication between
the modules. The jumper must be ON on the module where communication ends.
Type 15 # 1
Type 15 # 2
DOL 100 I/O 10RL
Jumper setting ON
Address 7.
-
DOL 100 I/O 20RL
Jumper setting OFF Ad-
dress 7
Jumper setting ON
Address 8.
(B)
CAN-ad-
dress
Each I/O module must have a specific CAN address for the controller to commu-
nicate with it. The address of the individual module corresponds to the address in the
controller’s
Technical | Setup | Installation | I/O Modules | Additional I/O Modules
menu.
(C)
Relays
10 relays for controlling flushing valves