Notice
Connector cable must be ordered
separately.
Refer to
service parts list, page 7
for
more information.
!
Notice
Detector requires a controller that
accepts digital signal via a connector
assembly part no. 280137.
Installation
Installation guidelines
• Units are non-directional.
• Use thread sealant on all pipe threads.
• Do not overtighten line connections.
• Perform system tests, checking for proper
functioning and connection sealing.
Installation procedure
1
Shut off all grease flow through grease
line.
2
Attach inlet and outlet connections to flow
detector.
3
Attach one end of connector cable to flow
detector.
4
Attach remaining end of connector cable
to controller.
5
Test detector by opening grease line to
supply grease flow to detector.
6
Verify LED is blinking, indicating that the
flow detector is working properly.
!
Notice
Electronic controller module is non-
repairable. Replace detector if electronic
controller module is found to be damaged
or faulty.
Do not disassemble detector with fluid
supplied to detector or line pressurized.
Remove pressure and supply before
disassembly.
Failure to comply may result in death or
serious injury.
W A R N I N G
!
Notice
Grease flow detector is to be in-
stalled in-line with grease line so that
flow of lubricant is directed through
sensor.
Assembly has an IP67 environmental
rating and does not require additional
enclosures.
Sensor is approved for indoor/outdoor
use.
4