SJE Rhombus Three Phase Duplex Installation And Operation Manual Download Page 4

4

Technical Support: +1-800-746-6287

[email protected]

www.sjerhombus.com

Technical Support Hours: Monday - Friday, 7 A.M. to 6 P.M Central Time 

PROGRAMMING INSTRUCTIONS

WITH POWER ON, HOAs OFF, FLOATS OFF OR DISCONNECTED, PRESS DESIRED FLOAT BUTTON RAPIDLY 4 TIMES AND HOLD

**PUMP LEDs WILL FLASH UPON SUCCESSFUL PROGRAMMING**

OPTIONS

FLOAT BUTTON

DEFAULT

OPERATION

PUMP FAIL ALARM

STOP

ON

ACTIVATES IF A PUMP CAUSES “LAG” 3 CYCLES IN A ROW

MANUAL ALARM RESET LEAD

OFF

LATCHES HIGH ALARM: CLEAR WITH EXTERNAL TEST SWITCH

SEAL FAIL HORN

LAG

OFF

ACTIVATES HORN UPON SEAL FAIL

ALARM FLASHER

ALARM

OFF

FLASHES BEACON UPON HIGH ALARM

ALARM CONDITIONS

ALARM

BEACON

CONTROLLER LED

HORN

PUMP FAIL

FLASHING

RED PUMP LIGHT

NO

SEAL FAIL

FLASHING

SF1, SF2

PROG

FLOAT FAIL

FLASHING

BAD FLOAT NOT LIT

NO

HIGH ALARM

SOLID

ALARM FLOAT

YES

1-2  ALT  2-1

SF1

SF2

SEAL FAIL

LEAD / LAG

SELECTOR

25K

5K

NC

150K

100K

125K

50K

15K

100K

AUX

ACTS

NO C NC

TB2

H

O

H

O

PUMP 1

PUMP 2

H

O

A

PUMP 1

PUMP 2

H

O

A

H

O

A

H

O

A

TM

ON  OFF

STOP

LEAD

LAG

ALARM

TEST

TEST

TEST

TEST

TEST

TEST

TEST

CONT

NO C NC

4

5

6

7

8

9

10

3

TB1

ON  OFF

L1  N

1

2

AUX

CONTACTS

NO C NC

10

NO C NC

NO C NC

L1  N

H

O

A

H

O

A

OFF   ON

®

a

b

c

e

d

f

g

l

k

i

j

h

COMPONENTS

a. ON/OFF Switch - Control/Alarm Power

g. Simulate Float Buttons x4

b. 120V Incoming Power Terminals

h. Float Terminals x8

c. Power LED - (Green)

i.  Lead/Lag Selecter Switch

d. Pump HOA Switches

j.  Dual Seal Fail Pot - (Optional)

e. Float LEDs - (Red) x4

k. Dual Seal Fail LEDs - (Red) - (Optional)

f.  Pump LEDs x2
      Pump Run - (Green)
      Pump Fail - (Red)

l.  Aux Alarm Terminals

Model shown contains optional seal fail circuitry.

Summary of Contents for Three Phase Duplex

Page 1: ... to health hazards in handling said material All applicable laws and regulations shall apply Installation and Operation Manual Model 322 Three Phase Duplex Installation and Operation Manual This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code NFPA 70 state and local electrical codes UL Type 4X enclosures are for indoor or outdoor...

Page 2: ...t and cord end with the provided pairs of STOP LEAD LAG and ALARM stickers If the distance to the control panel exceeds the length of the float switch cords or the pump power cord splicing in a liquid tight junction box will be required For outdoor or wet installation we recommend an SJE Rhombus UL Type 4X junction box 2 Make sure hose clamp band does not interfere with float operation Do not inst...

Page 3: ...p OFF In AUTO mode commands from the float switches turn each pump ON and OFF Motor Contactors Motor contactors control pumps by switching electrical lines Transformer The transformer converts incoming three phase power to 120V to be used for control and alarm Auxiliary Contact Form C Can be wired normally open or normally closed 1 Determine conduit entrance locations on control panel as shown Che...

Page 4: ...RED PUMP LIGHT NO SEAL FAIL FLASHING SF1 SF2 PROG FLOAT FAIL FLASHING BAD FLOAT NOT LIT NO HIGH ALARM SOLID ALARM FLOAT YES 1 2 ALT 2 1 SF1 SF2 SEAL FAIL LEAD LAG SELECTOR 25K 5K NC 150K 100K 125K 50K 15K 100K AUX ACTS NO C NC TB2 H O H O PUMP 1 PUMP 2 H O A PUMP 1 PUMP 2 H O A H O A H O A TM ON OFF STOP LEAD LAG ALARM TEST TEST TEST TEST TEST TEST TEST CONT NO C NC 4 5 6 7 8 9 10 3 TB1 ON OFF L1 ...

Reviews: