SJE Rhombus Installer Friendly Series Installation Instructions And Operation/Troubleshooting Manual Download Page 6

C-Level Sensor

1.

  Verify that the black tube is not kinked or has any 

holes in it. If either condition exists, the pressure 
sensor may fail or give inaccurate level readings.

2.

  Vent must be above water and unobstructed. 

This is required to compensate for barometric 
pressure changes. Obstructing the vent will result 
in inaccurate level readings.

3.

  The black diaphram is located on the end of the 

sensor body. The diaphragm must not be damaged 
or deformed. A damaged or deformed diaphragm 
will result in inaccurate level readings.

4.

  Verify the bottom of the C-Level Sensor is not resting 

on the bottom of the tank or on any other obstacle.

5.

  Verify that the electrical cable is not damaged or 

severed.

6.

  Verify that the shielding for cable is properly 

attached to ground.

7.

  If the panel includes the optional redundant off fl oat, 

verify that the fl oat is properly wired to the panel.

Fuse

To check the continuity of the fuse, pull the fuse out 
of the fuse holder.  With the ohmmeter on the R X 1 
scale, measure resistance.  A reading of infi nity (high 
resistance) indicates a blown fuse that must be replaced 
with a fuse of the same type, voltage, and amp rating.

Alarm Light

With power on, hold the test/normal/silence switch in 
the “test” position. The alarm light should turn on.  If not, 
replace the light with that of the same type.

Alarm Horn

With power on, hold the test/normal/silence switch in 
the “test” position. The alarm horn should turn on.  If 
not, replace the horn with that of the same type.

Troubleshooting

Operations

Selecting Time Dose or Demand Dose 
-Panels in the field

To set the panel to either Timed Dose or Demand Dose 
in the fi eld:

1.   Turn the control/alarm power off to the control panel.
2.   Turn the pump power off to the control panel.
3.  Place a small screwdriver or pen into the slot in the  
 

label on the inner door marked “DEMAND DOSE     

 TIMED 

DOSE”.

 

 

 Move the dip switch (up) for demand dose

 

 

 Move the dip switch (down) for Timed dose

4.    Turn the control/alarm power on to the control panel.
 

After the display goes blank press the “NEXT” switch.

 

 

 The display will show d-dose for demand dose.

 

 

 The display will show t-dose for timed dose.

 WARNING:

 Changing the dip switch positions    

 

will change the operation of the panel.

 WARNING:

 If changing to timed dose, be sure    

 

to set the off and on times.

5.   Turn on the pump power after all the settings are  
  

changed.

6.   

WARNING: 

Check the panel for correct operation 

 

before leaving the site.

-6-

Summary of Contents for Installer Friendly Series

Page 1: ... may be subject to submersion 1 Determine mounting location for panel If distance exceeds the length of either the sensor or float cables or the pump power cables splicing will be required Note For splicing C Level cord use only shielded cable Splice conductors as well as shielding Maximum total cable length is 300 feet For outdoor or wet instal lation we recommend the use of an SJE Rhombus liquid...

Page 2: ...etween 0 and 39 9 inches of water pressure for the CL40 or between 0 and 99 9 inches of water pressure for the CL100 The C Level sensor reads 0 inches at the approximate point shown in Figure 2 As the liquid level rises the IFS display shows depth of liquid from the zero point The minimum set point for the stop demand or redundant off timed dose level is 4 inches measured from 0 see Figure 2 The m...

Page 3: ...4 inch minimum set level Figure 1 Figure 2 Installation Instructions Figure 3 Timed Dose Figure 4 Demand Dose 3 ...

Page 4: ...ill turn off after five minutes of non use Viewing Panel Settings and Cycle Data To view panel settings and cycle data press the NEXT button Each time the NEXT button is pressed the display will advance to the next setting or cycle data Information will be displayed in the following order in Level of the liquid measured from the zero point on the sensor This will be shown in inches or centimeters ...

Page 5: ...UP button to change the value of the flashing digit When the desired value of the flashing digit is reached push the NEXT button to advance to the next digit Use the UP and NEXT buttons to set the total value of that parameter 4 When done setting the parameter push the set button and the parameter will flash along with its new value If an ERROR message is received check above conditions to ensure ...

Page 6: ... fuse of the same type voltage and amp rating Alarm Light With power on hold the test normal silence switch in the test position The alarm light should turn on If not replace the light with that of the same type Alarm Horn With power on hold the test normal silence switch in the test position The alarm horn should turn on If not replace the horn with that of the same type Troubleshooting Operation...

Page 7: ...ed must be cleaned sanitized or decontaminated as necessary prior to shipment to ensure that employees will not be exposed to health hazards in handling said material All applicable laws and regulations shall apply NOTES __________________________________________________________________________________________________________ ________________________________________________________________________...

Page 8: ..._____________________________________________________________________ __________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________ ____________________________________________________________________________________________________...

Reviews: