4
–
Associations
This has the effect that when the sensor detects the smoke, all devices associated with the sensor will re-
ceive the relevant reports and can be controlled by the sensor, e.g. fire extinguishing equipment, alarm
device, etc. This device supports five linkage groups:
Association group 1
is Lifeline.
Association group 2
is assigned to the devices status - sending BASIC SET control frame to the associated
devices having detected the smoke alarm.
Association group 3
reports the detection's status smoke alarm to the associated devices.
Association group 4
is assigned to the devices status - sending BASIC SET control frame to the associated
devices having detected the heat alarm.
Association group 5
reports the detection's status to the associated devices.
The alarm will send a “BASIC SET (0xFF)”message to associated groups 2 and 4 when pressing test button to
check the function.
The alarm will also send a “BASIC SET (0x00)”message to associated groups 2 and 4 when
the test button is released.
The alarm will also send a “BASIC SET (0xFF)” message to associated group 2, when the alarm detects the
smoke and the alarm will also send a “BASIC SET (0x00)” message to associated group 2, when the smoke is
cleared. The alarm wil
l send a “BASIC SET (0xFF)” message to associated group 4, when the heat function is
over heat alarm and the alarm will also send a “BASIC SET (0x00)” message to associated group 4, when the
overheat alarm is cleared.
The maximum number of devices that can be added to the association group 1 is 1
The maximum number of devices that can be added to the association groups 2, 3, 4 and 5 is 4.
Command classes:
This sensor supports Command Classes as below:
COMMAND_CLASS_ZWAVEPLUS_INFO(V2)
COMMAND_CLASS_ASSOCIATION(V2)
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION(V3)
COMMAND_CLASS_ASSOCIATION_GRP_INFO(V3)
COMMAND_CLASS_VERSION(V2)
COMMAND_CLASS_MANUFACTURER_SPECIFIC(V2)
COMMAND_CLASS_DEVICE_RESET_LOCALLY(V1)
COMMAND_CLASS_POWERLEVEL(V1)
COMMAND_CLASS_BATTERY(V1)
COMMAND_CLASS_NOTIFICATION(V8)
COMMAND_CLASS_WAKE_UP(V2)
S2 supported Command Classes:
COMMAND_CLASS_VERSION COMMAND_CLASS_ASSOCIATION
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION COMMAND_CLASS_ASSOCIATION_GRP_INFO
COMMAND_CLASS_MANUFACTURER_SPECIFIC COMMAND_CLASS_DEVICE_RESET_LOCALLY
COMMAND_CLASS_POWERLEVEL COMMAND_CLASS_BATTERY
COMMAND_CLASS_NOTIFICATION COMMAND_CLASS_WAKE_UP
COMMAND_CLASS_SUPERVISION
Supported Notification Type:
Smoke Alarm
Smoke Alarm Supported Event:
1. Smoke detected, unknown location (0x02)
2.
Smoke Alarm Test (0x03)
3.
Replacement required, unspecified reason (0x04)
4.
Alarm silenced (0x06)