background image

 

ENVIRONMENTAL CONDITIONS

-

25... +60 °C / -30... +100 °C (Shouldn't be icing and condensation in ambient.)

50% Relative humidity for +40°C temperature increases up to 90% at +20°C. (Shouldn't be condensation)
2
II
Max. 1000m
IP20 According to EN60529
 

Ambient/storage temperature
Relative humidity
Pollution degree
Overvoltage category
Altitude
Protection

Do not use the device in locations subject to corrosive and flammable gases.

OUTPUT

INPUT

 

 

 

ERFA1-240

40
180 - 280
150
400
1,6
5
880
50 - 60

>

0,75

160

Order code
Load Current, AC51/25ºC (Arms)
Load voltage (Vrms)
Overload current t=1s/25°C (Arms)
Non rep.surge current/25°C (Arms)
On-state voltage drop (Vrms)
Leakage current (mArms)
I²t for fusing t=10ms (A²s)
Frequency (Hz)
Power factor (CosΦ)
Minimum operating current (mArms)

Input signal
Transmission signal
Drop-out signal
Turn-on time
Dynamic input impedance
Protection

                                                                        

ENDA ERFA1 SERIES FAN SPEED CONTROLLER

ERFA1-240-

EN-01-170420

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

1/4

ENDA

TM

ORDER CODE : 

ERF  A  1   2  40 - F

-

Product Base Code

Fan Speed Control

Load Current

40A AC

Load Voltage

AC

Number of Pole

Single Pole

Load Voltage

180-280V AC

ERF

A

1

40

2

Fan

Fan

F

0/4-20mA, 0/1-5V DC, 0/2-10V DC or 

 ~ 10k  potentiometer. 

   0,2mA   (for mA input),    0,08V   (for V input)
   0,18mA (for mA input),    0,075V (for V input)
15ms
   100Ω (for mA input),   10k  (for V input)

1k

(Device may be damaged at ±12V DC and above voltages)

Ω

Ω

Ω

Please read this document carefully before using this product. The guarantee will be invalidated if the device is damaged by not 
following instructions detailed in the manual. The company shall not be responsible for any damage or losses however caused, which 
may be experienced as a result of the installation or use of this product.  

Thank you for choosing 

ENDA ERFA1

 Series fan speed controller devices.

Protection feature for reverse connection is available.

 

While cleaning the device,

 

solvents (thinner,

 gasoline

,

 

acid etc.) or corrosive materials must not be used.

Dimensions                                                 

 

Weight

GENERAL

Order code                                                 
Power supply                                                 

Isolation Voltage
Connection

Terminal screw torque
Product standard

 Mo

unting

 

Enclosure material

Fan (Optional)

40A  AC Load current
280V AC Load voltage

CE Marked according to European Norms

0/4-20mA, 0/1-5V DC, 0/2-10V DC  or  1kΩ ~ 10kΩ Potentiometer input
24V DC Sensor supply
4 Digits LED display
Phase angel or zero-cross controlled
Soft Start or Kick Start feature
Varistor protection for peak voltages

Sensor supply                                                 

ERFA

1-240

90-250

V

 

AC

50/60

Hz

.

 

 

7

VA

 Max.

24V DC, 30mA
W46 x H110 x D117mm
Approx. 450g (boxed)
2500 Vrms between I/O terminals for 1 min.
For power line 16mm² cable (with 25mm² cable terminal) cable, for signal line can be connected 4mm² cable.
Max. 1,2Nm
EN 60947-4-3

Fan is controlled with thermostat and works at temperatures over 50°C.

Rail mount (EN60715,TH35)
Self extinguishing plastics (According to EN 60695-11-10 V-O)

Summary of Contents for ENDA ERFA1 Series

Page 1: ...A for mA input 0 075V for V input 15ms 100Ω for mA input 10k for V input 1k Device may be damaged at 12V DC and above voltages Ω Ω Ω Please read this document carefully before using this product The guarantee will be invalidated if the device is damaged by not following instructions detailed in the manual The company shall not be responsible for any damage or losses however caused which maybeexper...

Page 2: ...kΩ to 10kΩ 0 10V 0 4 20mA 8 680407 713981 _ _ ENDA ERFA single phase fan speed controller SET 1 2 3 4 5 10 9 8 7 6 INSTALLATION To mount the device on rail By using a screwdriver pull the lockplate in direction 1 to lock it Assemble the device on the rail and push it in the direction 2 sideways 2 To remove the device from the rail By using a screwdriver pull the lockplate in direction 1 to lock it...

Page 3: ...E p yES p no nonE p yES p no Default values out phaS Soft 4 auto p yES p yES 100 0 0 SET SET SET If held down key the selected parameter will flash and can be adjusted to desired value with the keys Parameter Adjustment Method ou hi 51 50 50 If keys are pressed for 0 4 seconds parameter changes faster SET SET SET SET SET cu hi Running Mode a 3 0 o 30 diSp curr Output as Current diSp out Output as ...

Page 4: ...sadvantage of this method is that it causes high electrical noise It is a control method used in capacitive and variable resistive loads cosØ 1 The advantage of this method is that it does not causes high electrical noise With Phase Angle Control With Zero Crossing Control Start Method t Start time St ti Output Ratio Max 100 Max 100 0 0 t t Second Soft Start Kick Start Output Ratio Manually set or...