  ENDA ATSD02 

Rail Mounted Star-Delta Analog Timer.

*

 Separate contacts for star and delta connections (OUT1 - OUT2).

*

 Star connection to remain active time can be adjusted.

*

 Star-delta switching time can be adjusted.

*

 6 Different timing unit for star connection (S, 10S, M, 10M, H, 10H).

*

 Rail Mounted.

*

 Screw-terminal connection.

*

 CE marked according to European Norms.

 1 / 2

 ATSD02-

EN-02-220103

0 ... +50°C/-25 ... +70°C (With no condensation and icing).

OUTPUT CONTROL

ATSD02 - xV

ORDER CODE

     E

ND

A

 

     A

TS

D0

2

   Y T

IME

OFF T

IME

    Y R

ANGE

10

0

20

0

40

0

0

50

0

20

10M

10H

 H

10S

M

S

.4

.6

.8

0

1

.2

Power Led

Power

OUT2 NO

OUT1 Led

OUT2 Led

t Y

Power

OUT1 NO

t off

t Y=Y RANGE x Y TIME

 

t off=OFF TIME

 

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 

Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-

TURKEY

Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:

18

Thank you for choosing 

ENDA  AT

SD

0

2

 

R

ail mount

ed

 

star-delta 

analog timer. 

Product Basic Code
Rail Mounted Star-delta
Analog Timer

Technical Specifications

Read this document carefully before using this device. The guarantee will be expired by device demages if you don't 
attend  to  the  directions 

in

  user  manual. Also  we  don't  accept  any  compensations  for  personal  injury,  material 

damage or capital disadvantages.  

Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.

ENVIRONMENTAL CONDITIONS

 Max. 2000m

IP20, According to EN 60529 
                                              

 Do not use the device in locations subject to corrosive and flammable gasses.

 Height

 Ambient/storage temperature

 Max. relative humidity

Rated pollution degree

ELECTRICAL CHARACTERISTICS

 Scale

 EMC

 İnsulation test voltage

 Supply voltage
 Power consumption
 Connection

 Reset time

 Accuracy

 Safety requirements

 90-250V AC 50/60Hz ; 24V AC/DC  50/60Hz

Max. 10VA
Screw-terminal connection.

   Depending on the effect of voltage: max %0.2 

  EN 61326-1: 

 

2012 

  EN 61010-1: 2010 (pollution degree 2, overvoltage category II)

 3kV AC min. 1 minute, 4,2kV DC min. 1 minute.

For Star connection 0-1. For OFF delay time

 0, 20, 100, 200, 400, 500 milliseconds. 

Max. 0.04 seconds.

   Depending on the set value settings:max %4.5 
   Depending on the effect of temperature :max %1

OUTPUTS

 Control outputs (OUT1/OUT2)

  Control output state

  Life expectancy for relays

 Relay: 250V AC, 

10

A (for resistive load), NO+NC 

 Without load 

1

0.000.000 operation; 250V AC, 10A resistive load 

5

0.000 operation.

OUT1 LED lights up when OUT1 relay is turned on, OUT2 LED lights up when OUT2 relay is turned on. 
OUT1 and OUT2 LEDs blinks during OFF time.

CONTROL

 Timing function 

 Timing unit

Y TIME : ON time duration for OUT1 Relay. OFF TIME: OFF time duration for OUT1 and OUT2 relays. 
Can be adjusted on device.
For Y TIME Second, 10 seconds, minute, 10 minutes, hours, 10 hours can be selected on device.

HOUSING

 Mounting
 Dimensions  
 Weight 
 Enclosure material

 Rail mounted (EN 60715, Th35)

 W18xH90xD66mm 

 Approx.  90g (after packaging)

Self extinguishing plastics.

 While cleaning the device,solvents (thinner,benzine,acid etc.) or corrosive materials must not be used.

90-250V AC
24V AC/DC

UV

LV

ATSD02 - xV 

Supply Voltage