Recommendations for cables and installation 

 

Flexible cables are recommended to connect the camera. 

 

For larger distances, or in case of an already installed rigid (tunnel) cable, the use of a junction box is 
recommended as interface to the camera. In this case a prefabricated patch-cable with molded 
connectors can be used. (MOQ applies) 

 
For tunnel applications a shielded CPR B2ca rated cable is recommended: 

 

For example: Jobarco Ecoflex CPR HCH-JZ B2ca (suitable for patch-cable use) 

 

 

Power cable: maximum length table 

Power supply 
type 

Total cable 
resistance 

Cable length for copper wire size 

1.5mm² 

0.75mm² 

0.5mm² 

24VAC 

50/60Hz 

< 1.2 Ohm 

< 50m 

< 25m 

< 17m 

24VDC 

< 2.3 Ohm 

< 100m 

< 50m 

< 33m 

100 - 240VAC 

50/60Hz 

 

< 300m 

< 150m 

0.75mm² 
minimum 

 
Power cable: length and overvoltage protection 

 

The camera 24V power input is compliant with EMC standard EN 50130-4. This standard sets 
requirements for surge voltage immunity in clause 13. The 24V power supply lines and signal lines are 
tested for line-to-ground surge voltage levels up to 1kV (1.2/50 µs). There is no requirement for line-to-
line surge voltage testing on 24V inputs. 

 

 

The 24V power supply inputs may not be grounded.

 

 

For cable lengths up to 10m no additional surge protection is recommended. For longer cables, 
additional surge protection (SPD type T3 according IEC 61643, or equivalent) is recommended to 
ensure that the camera overvoltage category (IEC 60664-1) is reduced to class II.  

 

The installer is required to provide additional protection to reduce the overvoltage if the equipment is 
subject to transient overvoltages exceeding those for overvoltage category II. 

Ethernet cable:  

 

Shielded CAT5E S/FTP, wire size AWG24, solid or stranded, cable length up to 100m. 

 

For PoE powering of the XCU cameras the Ethernet cable must comply with the IEEE 802.3at 
requirements for PoE+ (up to 25,5W power at the camera). This means the maximum cable resistance 
per pair set is limited to 12.5 Ohm. The recommended size AWG24 typically meets this requirement for 
cable lengths up to 100m. 

 

For larger wire diameters the use of a junction box is recommended. 

 

 

 