background image

General

MIDI SMOKE 2 is a supervision system for up to
200   distributed   damper   control   modules.   If   the
software   SMOKE   EDIT   is   used   they   may   be
grouped in up to 99 fire cells. Each cell may have
one   or   several   alarm   points   from   e.g.   smoke
detectors or an external fire alarm system. Please
note   that   a   bus   amplifier   (8R30:004)   should   be
used after approximately 100 damper modules.

MIDI SMOKE 2 has eight built-in digital I/O (four
inputs and four relay outputs). 

MIDI SMOKE 2 has a display and key pad to check
current status, set up the system, carry out function
tests and reset smoke detectors.

MIDI   SMOKE   2   may   be   accessed   as   a   slave
module via Ethernet (SioxNet or Modbus TCP) to
connect to other systems.

This document describes the functionality of the
MIDI   SMOKE   2   central   unit.   Please   refer   to   the

Installation

  section   for   detailed   installation

information.

System setup

There are two ways to setup the system. The MIDI
SMOKE   2   is   normally   preloaded   with   a
configuration   file   (“MIDISMOKE_02.cfg”)   intended
for simpler systems where the key pad is used for
setup. These systems support up to a maximum of
59   damper   modules   (addressed   from   1-59)  

in   a

single   fire   cell

.   Single   or  dual  damper   modules

can   be   used.   Default   names   are   used   for   the
dampers and alarm points. By using the keypad it
is possible to set for each module the number of
dampers   (0-2)   and   also   activate   it   as   an  Alarm
Point if there is a Smoke Detector connected to it.
However, be careful to document any configuration
changes for future reference.

For more advanced systems the software SMOKE
EDIT   should   be   used.  SMOKE   EDIT   is   a   PC
program (Windows) used to define an installation
and to set up the MIDI SMOKE 2 central unit by
generating   a   project   file   and   downloading   a
compiled version to the unit.

Key legends

Generally   the   following   usage   of   the   key   pad
applies:

Up  

and  

Down  

arrows  step   between   menus   or

increases/decreases values.

Right  

and

  Left  

arrows  changes configurations and

moves the cursor within a menu.

Enter

  selects   a   menu/sub   menu,   saves  changes

and carries out commands.

“C”

  backs one step in the menu tree or aborts a

command.

Digital I/O

MIDI SMOKE 2 includes four digital inputs to be
connected   to   external   open/close   contacts.   DI1,
terminals 1-2, is the External Fire Input. When the
contact 

opens

 it will indicate Fire Alarm to the MIDI

SMOKE   2.   This   status   will   be   latched.   DI2,
terminals 3-4, when closed, (>1,5 s) will reset the
latched Fire Alarm. By jumpering DI2 with a wire
automatic reset of fire alarms via DI1 is achieved.
But if there still exists an active Fire Alarm on DI1,
it   will   remain.   DI3,   terminals   5-6,   when   closed,
indicates night mode when dampers are held in a
closed state. DI4, terminals 7-8, when momentarily
closed   (>1,5   s)   requests   a   Function   Test   Cycle
(exercise) where all dampers will close and then
open.   In  

Night

  mode  the  dampers will  open  and

then close again. In Service Mode no Function Test
Cycle is requested upon activation of DI4.

Further,   the   central   has   four   relay   outputs   with
breaking capacity 1A at 30V AC/DC.
DO1, terminals 15-16, opens when there is a Sum
Alarm  active   (damper   failure   or   communications
failure). DO2, terminals 17-18, opens when there is
a  Fire Alarm. DO3, terminals 19-20, opens when
there   is   a  Smoke   Detector   Service  Alarm.   DO4,
terminals   21-22,   is   the  Operation   Output.   The
different events and combinations for the output to
open   is   fully   configurable   via   the   corresponding
menu, see 

Run indication relay output

 menu.

Central unit panel

The panel of the central unit consists of a display,
eight   keys   and   three   LEDs.  The   LEDs   indicates
system   status.  The   yellow  

Error

  LED  is   lit   if   the

status for the system is B-ALARM (see 

Main menu

for  details).   It   will   flash   if   there   is   no   application
loaded  or if   it is stopped.  

Alarm

  LED is lit  if  the

system indicates fire. The green  

OK

  LED is lit  if

there are no errors or fire indication in the system.

If the unit is in 

Service Mode

 then the 

OK

 LED

will always be off

.

Introduced with system software version 1.61 the
green  

OK

  LED   will   be   off   if   the   communication

watchdog   is   not   set.   The  

Error

  LED   will   flash

syncronously with the warning text “

WATCHDOG

INACTIVE

” in the 

Main

 menu.

Menus

Most menus have a keyboard inactivity timeout of
3   minutes   after   which   the   display   returns   to   the

Main 

menu

E.g. the 

Module addressing

 menu has

no timeout because the operation will take some
time to accomplish.

Profcon AB

Page 3

www.smokecontrol.net

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: