![Sinexcel PWS2-30M-EX User Manual Download Page 26](http://html1.mh-extra.com/html/sinexcel/pws2-30m-ex/pws2-30m-ex_user-manual_1280588026.webp)
- 22 -
Step 4: Connect the positive cable of the battery pack to the “DC+” of the DC terminal block
so that the angle between the cable and the terminal block is 90 degrees.
Step 5: Connect the negative cable of the battery pack to the “DC-” of the DC terminal
block so that the angle between the cable and the terminal block is 90 degrees.
Step 6: Confirm wiring firmness and lock of DC cable.
Remark: The angle of 90 degrees between the cable and the terminal is for convenient
installation of the DC side protective case.
DANGER
Turn off AC and DC distribution switches and ensure that there is no
dangerous voltage in the system during wiring.
CAUTION
The positive and negative poles of batteries cannot be connected
inversely. Before wiring, a multi-meter needs to be used for
measurement.
WARNING
Only qualified professional can conduct wiring work.
3.6.5 AC wiring
Step 1: Use a phase-sequence meter for measurement, and ensure that the phase
consequence of wires should be correct.
Step 2: Turn off the AC breaker connected to energy storage inverter.
Step 3: Use a multi-meter to measure and confirm that the cables connected to the
terminals are electrically neutral.
Step 4: Use a wire stripper to strip the AC cable in a proper length, cover a cord end
terminal and use wire crimpers to compress it. Recommended AC cable 16mm
2
(AWG 5)
with copper cord.
Step 5: Connect AC cable to “L1”, “L2”, “L3” and “N” of AC wire terminal block;
Step 6: Confirm wiring firmness and lock the waterproof tube of AC cable.
WARNING
Ensure that there is no dangerous voltage at connection points during
wiring.
WARNING
Only qualified professional can conduct wiring work.