7. Electric control functions: 

7.1 Protection 

1.    3 minutes delay at restart for compressor. 

2.    Temperature protection of compressor top, compressor stops when the temp. of top of 

compressor is more than 120

, compressor runs when the temp. of top of compressor is less 

than 105

3.    When AC voltage 

 270V for 30 seconds, Outdoor Unit stops operation and alarms. 

When AC voltage 

 260V for 30 seconds, Outdoor Unit resumes operation. 

4.    Inverter module protection, Inverter module Protection itself has a protection function 

against current, voltage and temperature. 

5.    Sensor protection at open circuit and breaking disconnection. 

6.    Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High 

Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure 

information and can

t return to normal operation automatically.

 

 

7.    Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit 

stops and LED displays failure information and can

t return to normal operation automatically

 

8.    Current protection: When the current is more than 25A, the compressor stops. 

9.    Outdoor condenser high temperature protection: Under cooling mode, if T3>65  for 3 

minutes, the compressor will stop. When T3<52 , the protection is not valid.

   

10.    Outdoor low temperature protection: If the outdoor temperature is lower than -15  for 

1hour, the compressor and fan motor will stop. If the outdoor temperature is higher than -12

 

for 10 minutes and the compressor stops operation    for 1h, or the outdoor temperature is 

higher than 5

 for 10 minutes, then restart and enter into the prior operation mode. 

11.    Compressor pre-heating function: When the outdoor temperature is lower than 3

 and 

the compressor stops operation for more than 3 hours, or the outdoor temperature is lower 

than 3

 and the power is just put on, the compressor enters into pre-heating condition. When 

outdoor temp. is more than 5

 or user operate it, pre-heating condition will finish. 

7.2    Operating mode   

7.2.1    Cooling mode 

1.Indoor fan keeps running, fan speed can be set in high/mid/low/ Auto:   

2.Auto fan at cooling mode: (T=Indoor Temp.-Setting Temp.) 

 

Condition 

Indoor fan speed 

T<1.5

 

Low 

1.5

<T<4

 

Mid. 

Room temp. up 
 

T>4

 

High 

T> 3

 

High 

1 <T<3

 

Mid. 

Room temp. down 

T<1

 

Low 

3.Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) 

 

Evaporator Temp.    Compressor 
T< 4

 

Off 

 

T > 8

 

On 

Summary of Contents for SMF-4E27AI

Page 1: ...1 MULTI SPLIT TYPE HEAT PUMP AIR CONDITIONERS Technical service manual R410A Cassette Inverter multi Series Indoor Models SMF C09AI SMF C12AI SMF C18AI Outdoor Models SMF 4E27AI...

Page 2: ...2 CONTENTS 1 Features 2 Specification 3 Outline and dimension 4 Indoor unit combination 5 Capacity table 6 Wiring diagram 7 Electronic control functions 8 Exploded view...

Page 3: ...3 1 Features 1 Fashion design quality life 2 Low operation noise 3 High efficiency screw fan 4 Equal fast wide angle cooling more comfortable...

Page 4: ...of rows 2 2 2 b Tube pitch a x row pitch b mm 21x13 37 21x13 37 21x13 37 c Fin spacing mm 1 3 1 3 1 3 d Fin type code Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium e Tube outside...

Page 5: ...28 28 36 Dimension W H D mm 650x30x650 650x30x650 650x30x650 Packing W H D mm 715x115x715 715x115x715 715x115x715 Indoor unit panel Net Gross weight panel Kg 3 5 3 5 3 5 Application area m2 14 21 18...

Page 6: ...city range Btu h 9000 18000 16000 25000 21000 27000 28000 Rated input power range W 850 1790 1470 2520 2020 2650 2700 Rated current range A 3 5 7 5 6 1 10 5 8 43 11 1 11 3 Heating COP 10 4 Max input c...

Page 7: ...Outdoor air flow m3 h 3500 Outdoor noise level dB A 57 Dimension W H D mm 895X860X330 Packing W H D mm 1043X915X395 Outdoor unit Net Gross weight Kg 80 84 Refrigerant type and charge g R410A 2700 Des...

Page 8: ...nation 7K X4 setting temp 17 setting fan speed high speed 2 Nominal heating capacities are based on the following conditions Indoor temp 20 CDB Outdoor temp 7 CDB 6 CWB Equivalent ref Piping 8m horizo...

Page 9: ...18k 580 Body 67 600 Ceiling hole 650 Panel 401 Hook location 611 Hook location 580 Body 422 28 5 600 Ceiling hole 650 Panel Drain side and Tubing side A 600 Hook 265 Panel Chart 4 Body Nut Ceiling Out...

Page 10: ...e indoor unit capacity will attenuate That means you can not gain the nominal capacity but smaller than it We are out of responsibility if customers don t follow the notice below 1 You can connect two...

Page 11: ...9 63 9 09 8 72 8 45 Sensitive capacity kW 8 36 7 99 7 70 7 27 6 98 6 76 32 C D 23 C W Input kW 2 50 2 85 3 21 3 57 3 92 4 28 HEATING OUTDOOR CONDITIONS Indoor Conditions 24 C D 18 C W 12 C D 11 C W 7...

Page 12: ...12 6 WIRING DIAGRAM Indoor unit...

Page 13: ...13 Outdoor unit SMF 4E27AI...

Page 14: ...n 25A the compressor stops 9 Outdoor condenser high temperature protection Under cooling mode if T3 65 for 3 minutes the compressor will stop When T3 52 the protection is not valid 10 Outdoor low temp...

Page 15: ...on T Indoor exchanger temp Indoor fan speed T 34 Off 34 T 37 Breeze 37 T 44 Low speed Indoor exchanger temp up T 44 Setting fan speed T 38 Setting fan speed 33 T 38 Low speed 24 T 33 Breeze Indoor exc...

Page 16: ...heating at same time Heating mode has a priority 7 3 1 Definition Cooling mode Heating Mode Fan Off Cooling mode No Yes No No Heating Mode Yes No Yes No Fan No Yes No No Off No No No No No No mode con...

Page 17: ...y locked When test the cooling capacity the frequency can be locked at 78Hz by following the below 1 Set the indoor temp to 17 and high speed 2 Push the outdoor check button for 5 seconds then its fre...

Page 18: ...tdoor communication error P0 Compressor top protection against temperature P1 High pressure protection P2 Low pressure protection P3 Compressor current protection P4 Inverter module protection P5 Outd...

Page 19: ...speed is controlled according ambient temp After the compressor stop 30 seconds later the fan stop When cooling 27 High speed Ambient temp rise 27 Low speed 25 High speed Ambient temp decline 25 Low...

Page 20: ......

Page 21: ...lle 2 50112111024 2114200446 26 4 Filter 1 50112111025 2114200443 26 5 Control box 1 50112111026 2114200441 26 6 LED holder 1 50118121041 2114200420 26 7 Control board 1 50118121042 2334209008 26 8 Co...

Page 22: ......

Page 23: ...3 Switch air inlet grille 2 50112111024 2114200446 26 4 Filter 1 50112111025 2114200443 26 5 Control box 1 50112111026 2114200441 26 6 LED holder 1 50118121041 2114200420 26 7 Control board 1 5011812...

Page 24: ......

Page 25: ...box 1 50112111026 2114200441 26 6 LED holder 1 50118121041 2114200420 26 7 Control board 1 50118121042 2334209008 26 8 Cover control box 1 50112111027 2114200447 26 9 Fan guide 4 50112111028 21142004...

Page 26: ...550002 3 Holder for fan motor 1 2123549027 4 fan motor 1 2240041722 5 Front net 1 2124550017 6 Front clapboard 1 2124532935 7 Separating board 1 2124820000 8 Left clapboard 1 2124530063 9 Little handl...

Page 27: ...2165739000 21 Rear right clapboard 1 2125739003 22 Cabinet Front Right 1 2124532903 23 installation board for valve 1 2125739002 24 drain pan 1 2113560000 25 Capillary pipe Ass y 1 2165739006 26 Base...

Reviews: