4
7. Specifications
Model
SF-250F3
Power supply
V/Ph/Hz
220-240/1/50
Air flow (H/M/L)
m
3
/h
400/315/190
CFM
235/185/112
External static pressure
Pa
Cooling
Capacity (H/M/L)
kW
2.35/1.94/1.19
Water flow rate
L/h
410/350/230
Water pressure drop
kPa
13.3/9.98/4.59
Heating
Capacity (H/M/L)
kW
2.60/2.11/1.34
Water flow rate
L/h
470/390/240
Water pressure drop
kPa
14.3/10.33/4.5
Power input (H/M/L)
W
17/12/7
Rated current
A
0.20
Sound power level
(H/M/L)
dB(A)
43/37/29
Fan motor
Type
Low noise DC
fan motor
Quantity
1
Fan
Type
Centrifugal, forward-curved Blades
Quantity
2
Coil
Row
3
Max. working pressure
MPa
1.6
Diameter
mm
Φ7.94
H2 Body
Net dimensions (W×H×D)
mm
495×200×1020
Packing size (W×H×D)
mm
595×300×1125
Net weight
kg
21.5
Gross weight
kg
27.5
H3 Body
Net dimensions (W×H×D)
mm
455x200x858
Packing size (W×H×D)
mm
595×300×1125
Net weight
kg
16.5
Gross weight
kg
22.5
Water inlet/outlet pipe
inch
G3/4
Drain pipe
mm
ODΦ18.5
Notes:
1. H: High fan speed; M: Medium fan speed; L: Low fan speed.
2. Cooling conditions: Entering water 7
℃
, leaving water 12
℃
, Entering air temperature 27
℃
DB/19
℃
WB.
3. Heating conditions: Entering water 45
℃
, leaving water 40
℃
, Entering air temperature 20
℃
DB/15
℃
WB.
4. Noise is tested in a reverberation chamber.
Summary of Contents for SF-250F3
Page 1: ...SF XXX 3 SERVICE 0 18 FAN COIL AIR CONDITIONING...
Page 3: ......
Page 5: ......
Page 25: ...46 10 Service Spaces Cased type Footing a mm 150 b mm 90 c mm 50...
Page 28: ...49 For all the model...
Page 43: ......
Page 44: ...9 9 1 9 2 9 4 7 9 1 6 33 8 9 1 6 33 8 163 833 33 68 163 1 3 61 A...