2

Ensure the air inlet and outlet are not blocked or performance 

may suffer or it may activate protection, which will stop the 

unit from running.

In extremely strong winds, please prevent the air from flowing 

backwards into the outdoor unit.

Choose an appropriate place where the noise and hot or cold 

wind blown out of the outdoor unit will not cause 

inconvenience to your neighbors or affect the growth of an 

animal or plant.

Do not place appliances that have naked flames under or 

near the unit, as heat from the appliance can damage the 

unit.

Do not allow children to play near this unit, as doing so risks 

injury.

This unit should not be operated by children or by adults that 

are not capable of operating the unit safely. 

When disposing of this unit, ensure that all applicable 

legislation regarding the disposal of refrigerant, oil and other 

materials is adhered to.

Leave the power on for a minimum of 12 hours prior to 

running the system to ensure that the crankcase heaters 

have heated the compressor oil sufficiently.

2.    PARTS  NAMES

3.    OPERATION AND PERFORMANCE

NOTE

All pictures in this manual are for explanation purposes only. 

They may be slightly different from the air conditioner you 

purchased (depend on model).

The cooling and heating operation in a VRF system

Each indoor unit can be controlled alone. The indoor units in the 

same system cannot run cooling and heating at the same time.

Explanation of priority mode operation

Fig.2-1

Air inlets (left, right, rear and front ( 24-32HP )
Refrigerant piping and wiring connection port

Fixed foot

Air outlet 

1
2
3
4

Priority mode can only be set on the master unit. When  an indoor 

unit is in mode conflict with the outdoor units the unit displays the 

mode conflict error. 
1. 

Auto priority mode (default): 

In auto priority mode, the 

outdoor unit will operate in heating priority mode or cooling 

priority mode according to the outdoor ambient temperature.

2. 

Heating priority mode:

 

a) 

During  cooling operation:

  If  an indoor unit requests 

heating, the outdoor units stop and then restart in 

heating mode after 7 minutes. Indoor units requesting 

heating then start in heating mode and indoor units 

requesting cooling display the mode conflict error. 

 

b) 

During  heating operat ion:

  If an indoor unit requests 

cooling, the outdoor units ignore the request and 

 

continue to run in heating mode. The indoor unit 

requesting cooling displays the mode conflict error. If all 

 

the indoor units requesting heating are later turned off 

and one or more indoor units are still requesting cooling,

 

the outdoor units restart in cooling mode after 7 minutes 

and any indoor units requesting cooling then start in 

cooling mode. 

 

3. 

Cooling priority mode:

 

a) 

During heating operation:

 

  If an indoor unit requests 

 

cooling, the outdoor units stop and then restart in 

cooling mode after 7 minutes. Indoor units requesting 

cooling then start in cooling mode and indoor units 

requesting heating display the mode conflict error. 

 

b) 

During cooling operation:

 

  If an indoor unit requests 

heating, the outdoor units ignore the request and 

 

continue to run in cooling mode. The indoor unit 

 

requesting heating displays the mode conflict error. If all 

 

 

the indoor units requesting cooling are later turned off 

and one or more indoor units are still requesting heating, 

the outdoor units restart in heating mode after 7 minutes 

 

and any indoor units requesting heating then start in 

heating mode.

 

 

 

4. 

VIP priority mode or voting priority mode : 

63 is the VIP 

 

address. If the VIP indoor unit is operating, the outdoor units 

operate in the mode of the VIP indoor unit. Indoor units that 

are in a mode different to that of the VIP unit display the mode 

conflict error. If there is no unit with address 63 or the unit at 

address 63 is in standby, the outdoor units operate in voting 

 

 

priority mode. In voting priority mode, the outdoor units 

operate in whichever of heating and cooling modes is being 

requested by the larger number of indoor units. 

 

5. 

Heating  only  mode :

 The outdoor units only operate in 

heating mode. Indoor units requesting heating operate in 

heating mode. Indoor units requesting cooling or in fan only 

mode display the mode conflict error. 

 

6. 

Cooling  only  mode:

  The outdoor units only operate in 

cooling mode. Indoor units requesting cooling operate in 

cooling  mode; indoor units in fan only mode operate in fan 

only mode. Indoor units requesting heating display the mode 

conflict error. 

1

2

3

4

1

4

1

Summary of Contents for SDV5 EAM Series

Page 1: ...MODULAR OUTDOOR UNITS SDV5 XXXEAM C O M M E R C I A L A I R C O N D I T I O N E R S S D V 5...

Page 2: ...Original instructions IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference...

Page 3: ...or maintenance can cause electric shock fire or leakage of water Contact your dealer for servicing and maintenance The appliance must be installed in accordance with national wiring regulations Ensur...

Page 4: ...n start in heating mode and indoor units requesting cooling display the mode conflict error b During heating operat ion If an indoor unit requests cooling the outdoor units ignore the request and cont...

Page 5: ...nal air conditioning service engineer Incorrect servicing or maintenance can cause electric shock fire or leakage of water If the unit displays protection or error code contact your dealer for servici...

Page 6: ...ks Only displayed on the slave unit with the error Displayed on the unit with the error Only displayed on the master unit with the error Displayed on the unit with the error Displayed on the unit with...

Page 7: ...ster unit 90 capacity output Only available for the master unit 80 capacity output Only available for the master unit 70 capacity output Only available for the master unit 60 capacity output Only avai...

Page 8: ...seconds Display n1 Press menu Display nX Press up or down to choose X Press OK to confirm X Display nXY Display nXY Press up or down to choose Y Press OK to confirm Y Press OK to confirm Y Press OK to...

Page 9: ...Temp of compressor B C Inverter module heatsink Temp A C EXVA position Compressor discharge pressure MPa Reserved Number of indoor units currently in communication with master unit Number of indoor un...

Page 10: ...e 3 8 Super silent mode 1 9 Super silent mode 2 10 Super silent mode 3 11 Super silent mode 4 Static pressure mode 0 Standard static pressure 1 Low Static pressure 2 Medium static pressure 3 High stat...

Page 11: ......

Page 12: ...01 01 2314 5 67 314 5 0738 9 71 20 01 7 1 7 8 9 9 0 90 2 8 3 07 11 5 3 07 11 71 11 011 7 3 A 71 3 0 3B1 07 C...

Reviews: