It can only be repaired by the method suggested by the equipment’s manufacturer.

Qualification requirement for installation and maintenance man

Installation notes

The air conditioner is not allowed to use in a room that has running fire (such as fire source, working coal gas ware, 

operating heater).

Maintenance notes

Welding

Check whether the maintenance area or the room area meet the requirement of the nameplate.

- It’s only allowed to be operated in the rooms that meet the requirement of the nameplate.

Check whether the maintenance area is well-ventilated.

- The continuous ventilation status should be kept during the operation process.

Check whether there is fire source or potential fire source in the maintenance area.

- The naked flame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged.

Check whether the appliance mark is in good condition.

- Replace the vague or damaged warning mark.

If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below: 

It is not allowed to drill hole or burn the connection pipe.

The air conditioner must be installed in a room that is larger than the minimum room area. The minimum room area is 

shown on the nameplate or following table a.
Leak test is a must after installation.

table a- Minimum room area ( m  )

2

Charge amount (kg)

≤1.

2

1.

3

1.

4

1.

5

1.

6

1.

7

1.

8

1.

9 2

2.

1

2.2 2.3 2.4 2.5

/

/

/

/

14.

5

16.

8

19.

3 22 24.8 27.8 3

1

34.3 37.8

41.

5 45.4 49.4 53.6

5.2 6.

1

7 7.9 8.9

1

0

11.

2

12.

4

13.

6

1

5

16.

3

17.

8

19.3

1.

6

1.

9 2.

1

2.4 2.8 3.

1

3.4 3.8 4.2 4.6

5 5.5

6

1.1 1.

3

1.

4

1.

6

1.

8 2.

1

2.3 2.6 2.8 3.

1

3.4 3.7

4

floor location

wall mounted

window mounted

ceiling mounted

Minimum

room

2

area( m  )

INSTALLER

1

7

SAFETY OPERATION OF FLAMMABLE REFRIGERANT

All the work men who are engaging in the refrigeration system should bear the valid certification awarded by the 

authoritative organization and the qualification for dealing with the refrigeration system recognized by this industry. 

If it needs other technician to maintain and repair the appliance, they should be supervised by the person who 

bears the qualification for using the flammable refrigerant.

Filling the refrigerant

Safety instructions for transportation and storage

a. Shut down the unit and cut power supply

b. Eliminate the refrigerant

c. Vacuuming

d. Clean it with N2 gas

e. Cutting or welding

f. Carry back to the service spot for welding

The refrigerant should be recycled into the specialized storage tank.

Make sure that there isn’t any naked flame near the outlet of the vacuum pump and it’s well-ventilated.

Use the refrigerant filling appliances specialized for R32. Make sure that different kinds of refrigerant won’t 

contaminate with each other.

After filling is finished, please do the leakage detection before test running; another time of leak detection should be 

done when it’s removed.

Please use the flammable gas detector to check before unload and open the container.

No fire source and smoking.

According to the local rules and laws.

The refrigerant tank should be kept upright at the time of filling refrigerant.

Stick the label on the system after filling is finished (or haven’t finished).

Don’t overfilling.

Summary of Contents for MV-42BI

Page 1: ...MULTI VARIABLE OUTDOOR UNIT MV ExxBI USER S MANUAL EN...

Page 2: ......

Page 3: ...Original instructions IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference...

Page 4: ......

Page 5: ...appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or ins...

Page 6: ...d to indicate risk of property damage Indicates a hazard that would be assigned a signal word WARNING or CAUTION WARNING CAUTION DANGER NOTICE CONFORMITY AND RANGE GENERAL INFORMATION Please read this...

Page 7: ...repair be necessary contact your nearest authorized Service Centre The appliance shall be stored in a room without continuously operating ignition electric heater Do not pierce or burn s instructions...

Page 8: ...ectric shock Donot spray wateronindoorunit It may cause electric shock ormalfunction After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoi...

Page 9: ...Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Air Conditioner should be properly grounded Incorrect grounding may cause electric...

Page 10: ...and outdoor unit should be connected by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending the wire by yourself For the ai...

Page 11: ...turned on or off according to your requir ement automatically please do not turn on or turn off the unit freque ntly otherwise disadvantage effect may be caused to the unit Rated voltage of this air c...

Page 12: ...tube Note The above figures are only intended to a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased Note The above figures are only intend...

Page 13: ...ock Make sure not to wash your air conditioner in any case Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner Only use soft dry cloth moist cloth clean...

Page 14: ...NICAL DATA GENERAL INFORMATION TECHNICAL DATA GENERAL INFORMATION OUTDOOR UNIT WORKING TEMPERATURE RANGE GENERAL INFORMATION 9 Indoor side DB WB Outdoor side DB WB Maximum cooling 32 23 43 26 Maximum...

Page 15: ...4 13 6 15 16 3 17 8 19 3 1 6 1 9 2 1 2 4 2 8 3 1 3 4 3 8 4 2 4 6 5 5 5 6 1 1 1 3 1 4 1 6 1 8 2 1 2 3 2 6 2 8 3 1 3 4 3 7 4 floor location wall mounted window mounted ceiling mounted Minimum room 2 ar...

Page 16: ...UM This unit is containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personnel Type of refrigerant R32 The quantity of the r...

Reviews: