Step 2: 

Module check 

 

1)  DC voltage between terminal P and terminal N should be 1.41 times of the local power supply voltage. 
2)  DC voltage between terminal 1 and 2 should be 510V

580V. 

3)  Disconnect the terminal 3, 4, and 5 from inverter compressor. Measure the risistance between any two 

terminals among terminal 1, 2, 3, 4, 5. All the values should be infinity. If any of the value approximates to 0, 
the inverter module is damaged and should be replaced. 

After replaced the inverter module, if the system is still abnormal, then go to step 3. 

Step 3: 

DC generatrix check 

Direction of the current in DC supply wire which is running through the inductor should be the same as the 
direction of arrow marked on the inductor. 

 

2) L1/L4 troubleshooting 
Step 1: 

Check the DC voltage between 1  and  2 terminal,  the  normal  value should be 510V~580V, if the 

voltage is lower than 510V, go to step 2. 

4  5 

Summary of Contents for ASDH-96AI

Page 1: ...HIGH STATIC PRESSURE DUCT SERIE ASDH 96AI SERVICE MANUAL EN ...

Page 2: ... Original instructions IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference ...

Page 3: ...1 Content Part 1 General information 2 Part 2 Outdoor Unit 5 Part 3 Indoor Unit 13 Part 4 Installation Troubleshooting 24 Part 5 Controller 52 ...

Page 4: ...2 Part 1 General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 3 3 Nomenclature 4 ...

Page 5: ... Units Type Indoor unit Outdoor unit Model Power supply Model Power supply Hi static pressure duct type ASDH 96AI 220 240V 1Ph 50Hz ASDH 96AI 380 415V 3Ph 50Hz 2 External Appearance 2 1 Indoor units ASDH 96AI 2 2 Outdoor unit ASDH 96AI ...

Page 6: ...3 Nomenclature Nominal cooling capacity 96 1 000Btu h High static pressure Duct Sinclair Air conditioner Inverter R410A A S D H 96 A I 4 ...

Page 7: ...5 Part 2 Outdoor Unit 1 Specifications 6 2 Dimension Unit mm 7 3 Refrigerant circuit 8 4 Wiring Diagrams 9 5 Electric Characteristics 11 6 Sound Levels 12 7 Accessories 12 ...

Page 8: ...Type DC Quantity 2 Brand Panasonic Insulation class E Safe class IP 4 Input W 250 up 185 down Output W 200 up 150 down Rated current A 1 7 up 1 4 down Outdoor fan Material Plastic Type Axial fan Quantity 2 Diameter mm 560 Height mm 170 Outdoor coil Number of rows 2 Tube pitch a row pitch b mm 21 19 4 Fin spacing mm 1 5 Fin type Hydrophilic fin Tube outside diameter mm Ф7 Tube type Inner groove tub...

Page 9: ...ased on the following conditions Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB 2 The nominal heating capacity is based on the following conditions Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 3 The noise is measured in the semi noise suppression lab 4 Specifications are subject to change without prior notice for product improvement 2 Dimension Unit ...

Page 10: ...rcuit High pressure switch Oil seperator Oil return capilary Compressor Low pressure switch Low pressure liquid accumulator can Condensor High pressure liquid accumulator can Electronic expansion valve Evaporator SV5 SV6 ...

Page 11: ...9 4 Wiring Diagrams ...

Page 12: ...3 Outdoor unit network address dial up 0 8HP 25 2kW 26kW 1 10HP 28kW F 7HP 22 4kW 0 F indicates 0 15 Code Name Code Name COMP Inverter compressor T5 Inverter compressor discharge temperature sensor FAN UP FAN DOWN Fan motor KM B Contactor STF1 4 way valve E1 E2 Filter capacity SV 2 4 5 6 7 Solenoid valve R1 R2 Cement resistor PTC Thermal resistor HEAT1 Crankcase heating XT2 Big 4 phase terminal L ...

Page 13: ... than 5 minutes in Heating mode Eb 2 times of E6 protection in 10 minutes P0 Inverter compressor top high temperature protection P1 High pressure protection P2 Low pressure protection P3 Outdoor input current protection P4 Compressor discharge high temperature protection P5 Outdoor condenser high temperature protection P6 Inverter module protection P8 Typhoon protection PE Evaporator high temperat...

Page 14: ...s Unit Number Model Noise level under three speeds of fan dB A 1 ASDH 96AI 59 7 Accessories Accessory name of outdoor unit Qty Purpose Connection pipe 1 Connecting pipe of system Curved connection pipe 1 1m 1 3m Front ...

Page 15: ...rt 3 Indoor Unit 1 Features 14 2 Specifications 15 3 Dimensions Unit mm 16 4 Wiring Diagrams 17 5 Capacity Table 20 6 Static Pressure Curve 21 7 Electric Characteristics 22 8 Sound Levels 22 9 Accessories 23 ...

Page 16: ...air flow is up to 4800m3 h 1 3 Flexible duct design for different room styles Multi diffusers from one indoor unit supply airflow to multi rooms at the same time The unit is suitable for various applications such as restaurants connect halls and hotels 1 4 High efficient DC fan motor High energy efficient thanks to the DC fan motor Contrast with the AC fan motor the power consumption of DC fan mot...

Page 17: ...t pipe Liquid side Gas side mm Ф9 52 Ф25 4 Max refrigerant pipe length m 50 Max difference in level Outdoor upper m 25 Max difference in level Outdoor lower m 30 Connection wire Power wire 5 4 0mm2 outdoor 3 2 5mm2 indoor Signal wire 3 0 75mm2 Drain pipe size OD mm Ф31 outdoor Ф33 indoor Controller KJR 29B Wired controller Operation temperature C 17 30 Indoor unit Dimension W x H x D mm 1 470 512 ...

Page 18: ......

Page 19: ...16 3 Dimensions Unit mm Air outlet duct connection screw hole location diagram Return air duct rivet screw hole location diagram 122 194 194 272 272 254 390 1138 ...

Page 20: ...17 4 Wiring Diagrams ...

Page 21: ...ash Slowly or Show E7 Outdoor Unit Error Alarm_LED Flash Slowly or Show Ed Water Level Error Alarm_LED Flash or Show EE CODE TITLE T1 ROOM TEMP T2B OUTER PIPE TEMP T2 MIDDLE PIPE TEMP PUMP PUMP MOTOR XP2 6 CONNECTOR XS2 6 CONNECTOR XT1 3 TERMINAL BD 1 BRIDGE RECTIFIER Function setting indication For Setting Power ENC1 Code 0 1 2 3 POWER 8HP 10HP 12HP 14HP Factory setting According to related model...

Page 22: ... TYPE 6 2 4 0 Factory Setting SW6 1 TYPE Digital Tube Display Board New Display Board LED Indication Display Board Old Display Board Factory Setting SW6 2 SW6 3 SW6 4 TYPE RESERVED Factory Setting For Setting Auto Restart J1 Mode Auto Non auto Factory Setting For Setting Auto Restart J2 Mode One for One Multi Split Factory Setting ...

Page 23: ...19 0 TC kW 30 52 29 12 28 56 26 32 25 62 24 36 22 96 SC kW 25 64 24 75 24 56 23 95 24 08 23 39 22 27 S T 0 84 0 85 0 86 0 91 0 94 0 96 0 97 PW kW 8 28 8 73 9 09 9 63 10 17 10 62 11 07 32 0 23 0 TC kW 30 80 29 68 29 12 26 88 26 04 25 20 23 52 SC kW 26 18 25 82 25 63 25 00 25 00 24 44 23 28 S T 0 85 0 87 0 88 0 93 0 96 0 97 0 99 PW kW 8 46 8 82 9 45 9 81 10 35 11 07 11 34 Notes 1 DB Dry Bulb Tempera...

Page 24: ...the installer must set the electronic control dial code based on the actual value of the static pressure of the product Otherwise there will be problems 3200 3400 3600 3800 4000 4200 4400 4600 4800 0 20 40 60 80 100 air flow m3 h Static pressure Pa 0 1 0 1 High air Mediumair Low air Static curve ENC2 1 3000 3500 4000 4500 5000 5500 6000 0 25 50 75 100 125 150 air flow m3 h Static pressure Pa 0 1 0...

Page 25: ...6AI 50 220 240V 198V 254V 15 0 75 5 1 Note MCA Min Current Amps A MFA Max Fuse Amps A IFM Indoor Fan Motor kW Fan Motor Rated Output kW FLA Full Load Amps A 8 Sound Levels 3000 3500 4000 4500 5000 5500 0 50 100 150 200 0 1 0 1 High air Mediumair Low air Static curve ENC2 3 air flow m3 h Static pressure Pa ...

Page 26: ...e 1 Sealed tube interface Water connective pipe 1 Connect to water drainage pipe Protective sleeve for refrigerant inlet and outlet pipes 2 Wired controller 1 Copper nut 1 Connect to liquid side pipe Water outlet connection pipe 1 Centralized drainage Straight screwdriver 1 Inspection and DIP Sealing ring 1 Centralized drainage Waterproof chassis cover 2 Chassis auxiliary drainage plug ...

Page 27: ...roubleshooting 1 Notes 25 2 Installation of Duct Type Indoor Units 25 3 Installation of Outdoor Units 29 4 Connection of Refrigerant Pipe 32 5 Electric Connection 33 6 Duct Design Scheme 35 7 Trial Run 35 8 Trouble shooting 36 ...

Page 28: ...cabin Place like kitchen where oil permeates Place where strong electromagnetic waves exist Place where flammable gases or materials exist Place where acid or alkali gases evaporate or other special environments Other special environments Install the unit where the air inlet and air outlet are free from obstacles and strong wind Install the unit in a dry and well ventilated place Install the unit ...

Page 29: ...side 2 2 Install Φ10 pendant bolts or ground bolts Use Φ10 or bigger screws The screw material is high quality carbon steel whose surface is zinc plated or undergoes other rustproof treatment or stainless steel ...

Page 30: ...ructure Put rectangular sticks across the beams and set pendant bolts B New concrete roughcast Use embedded bolts embedded pulling plugs and embedded stick harness C New concrete roughcast Set it with embedded bushes or embedded bolts D Steel beam and girder structure Set and use supportive angle steel 2 3 Suspending the indoor unit Use a hoisting device to hoist the indoor unit align it with the ...

Page 31: ...ee the indoor unit outline diagram Use M6X20 screws configured on site for connection All pipelines must be connected closely and soundly without leak of air The pipelines must be adiabatic and free from condensation Key points of duct connection 2 5 Install the drainpipe 1 Install the indoor unit drainpipe Install a drain stream trap in the drainpipe to prevent water from overflowing The drainpip...

Page 32: ...r unit pour the water in to see whether it drain smoothly and whether there is water leakage 3 Heat insulation After confirming that drainage is smoothly and there is no leakage wrap the drainpipe with insulation material or there will be condensed water 3 Installation of Outdoor Units 3 1 Installating space Single unit installation Parallel connect the two units or above ...

Page 33: ... 45 and do not lay it sidelong Make concrete foundation according to the specifications of the outdoor units refer to Fig 4 6 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind 3 3 Centralized chassis drainage When the outdoor unit requires centralized drainage install the chassis and two waterproof covers for the chassis Install the w...

Page 34: ...ve B is high pressure side stop valve C and D is connecting pipes interface of indoor and outdoor units 3 6 Heat Insulation Do the heat insulation to the pipes of air side and liquid side separately The temperature of the pipes of air side and liquid side when cooling for avoiding condensation please do the heat insulation fully The air side pipe should use closed cell foamed insulation material w...

Page 35: ...32 4 Connection of Refrigerant Pipe 4 1 Size of outdoor unit pipes and piping methods Model Gas side Liquid side ASDH 96AI Φ25 4mm Φ9 5mm ASDH 96AI Φ25 4mm Φ9 5mm ...

Page 36: ...cific to the indoor unit and outdoor unit The supply voltage must comply with the nominal voltage The external supply circuit of the air conditioner must have a ground wire and the power supply ground wire of the indoor unit must be connected with the external ground wire firmly The wiring must be performed by professional technicians according to the circuit diagram labels Distribute the wires ac...

Page 37: ...regulations 5 2 Specifications of power supply Model ASDH 96AI ASDH 96AI Power 220 240V 50Hz 380 415V 3N 50Hz Switch capacity of the main power supply Fuse A 16 16 40 40 Indoor unit power cable 3 2 5mm2 Includes grounded wire Outdoor unit power cable 5 6 0mm2 Includes grounded wire Indoor Unit Outdoor Unit Signal Wire mm2 Weak electric signal 3 core shielded wire 3 0 75 5 3 Schematic diagram ...

Page 38: ...nd ventilation pipeline design scheme 7 Trial Run Please conduct in accordance with the nameplate of Trial Run Tenor on the electric control box Perform the trial run only after the outdoor unit has been powered on for over 12 hours Check whether all valves are opened before trial run Check the electric safety before trial run ...

Page 39: ...on or leak of water occurs especially at the drain stopper 8 Trouble shooting 8 1 Malfunction code of outdoor unit Fault code Content Note E1 Phase sequence error E2 Indoor outdoor unit communication error E4 Ambient temperature T4 pipe temperature T3 sensor error E5 Voltage error E6 DC fan motor fault E7 Discharge sensor error EA A fan in the A region run for more than 5 minutes in HEAT mode Eb 2...

Page 40: ...h outdoor unit is according to A B C phase sequence when the quantity of outdoor units is large the current difference between C phase and A B phase will be very large for the power supply load of each outdoor unit is on C phase it is very easy to lead to air switch break and wiring terminal burnout So when the quantity of outdoor units is large the phase sequence should be staggered then the curr...

Page 41: ...ge power Communication wires are close to electromagnetic interference source Such as transfer strong fluorescent lamp etc The length of communication wire is over 1200m Outdoor main control board is damaged Reconnect the communication wires Connect the communication wires in line shape Ensure the communication wires and high voltage wires do not twining Remove the interference source or use devic...

Page 42: ...ing a multimeter to measure resistance if the resistance is too small the sensor is short circuit Outdoor main control board is damaged Fasten the T3 T4 T7 port Replace the sensor Replace the outdoor main control board Yes Yes No E5 Voltage error Voltage of power supply is too high or too low the normal voltage between A and N B and N C and N should be 163V 268V Check the high voltage circuit Whet...

Page 43: ...k whether the inverter module is output error Dial the multimeter to diode file black pen on P and red pen respectively on U V W if the multimeter displays 0 4 0 7 V it is normal Red pen on N black pen respectively on U V W if the multimeter displays 0 4 0 7 V it is normal Satisfying the above two conditions at the same time indicates that the inverter module has no problem E8 Outdoor unit address...

Page 44: ...ransformer 2 terminals are abnormal Provide normal power supply The transformer on main control board is disabled There is electromagnetic interference nearby the unit Such as high frequency transmitter or other high strength radiation device Outdoor main control board is damaged Replace the transformer Remove the interference Replace the outdoor main control board Yes Yes Yes Yes No No No ...

Page 45: ...re side is blocked The discharge temperature is higher than normal value low pressure is lower than normal value current is lower than normal value and suction pipe may be frosting H8 High pressure sensor error High pressure sensor connection port on main control board is loose High pressure sensor is short circuit or disabled Fasten the connection port System is lack of refrigerant Refrigerant re...

Page 46: ...maged Repair the leakage and recharge refrigerant Clean the evaporator or repair the indoor fan Repair the refrigerant pipe Vacuum the system and recharge refrigerant oil Replace the PCB board Yes Yes Yes Yes Yes No No No No No P1 High pressure protection The heat exchanger of condenser is not good It may be caused by dirty heat exchanger abnormal ODU fan running ODUs are too near to each other et...

Page 47: ...lter etc The heat exchanger of evaporator is not good It may be caused by dirty heat exchanger abnormal IDU fan running some barriers in front of the air outlet etc Outdoor main control board is damaged Add refrigerant or check up the leakage of the system Check the system and fixed up the error Make sure all valves are open clean the filter if the filter is blocked by ice the system should be cle...

Page 48: ...other etc The high pressure side of the system is blocked for squashed pipe blocked valve or closed stop valve Refrigerant is excess System contains air or nitrogen High voltage short circuit or compressor error Outdoor main control board is damaged Discharge part of refrigerant Add some of oil if it leaks during the discharge Check the system and fixed up the error Make sure all valves are open c...

Page 49: ...ystem is blocked for squashed pipe blocked valve or closed stop valve System contains air or nitrogen Outdoor main control board is damaged Fasten T3 port Replace the sensor Make sure the ratio of connectable IDU is less than 130 or add ODU Check the system and fixed up the error Make sure all valves are open check the system and remove the obstacle Discharge the entire refrigerant Then vacuum the...

Page 50: ... trend to infinity Fig D otherwise the compressor has been malfunction needs to be replaced Fig A Fig B Fig C Fig D If the resistance value are normal then go to step 2 H4 will display if P6 occurs 3 times in 30 minutes Check whether inverter module is broken and eliminate the situation that DC generatrix is connected inversely P6 L0 L9 error codes can t display on digital tube automatically these...

Page 51: ... be infinity If any of the value approximates to 0 the inverter module is damaged and should be replaced After replaced the inverter module if the system is still abnormal then go to step 3 Step 3 DC generatrix check Direction of the current in DC supply wire which is running through the inductor should be the same as the direction of arrow marked on the inductor 2 L1 L4 troubleshooting Step 1 Che...

Page 52: ...heck the DC voltage between 1 and 2 terminal the normal value should be 510V 580V if the voltage is higher than 580V go to step 2 Step 2 Check the voltage between the two electrolytic capacitors the normal value should be 510V 580V Turn the measure range of the meter to 1kV measure the voltage between two electrolytic capacitors 1 2 1 2 3 Phase bridge rectifier Filter board ...

Page 53: ...the resistance value are normal then go to step 2 Step 2 Disconncet the power wiring from the compressor named compressor A of the faulted system named system A If there is a system running normally nearby named system B Extend the power line of the inverter compressor of system B connect compressor A to the control box of system B make sure that the U V W terminals are connected in right order th...

Page 54: ...eat dissipation or high ambient temperature Some power wires or signal wires of fan module are loose The fan motor is blocked or disabled Output voltage between P and N on fan module is abnormal Fan module is disabled Make sure the fan module working in the normal temperature range Well connect the power wires and signal wires Clear away the block or replace the fan motor Replace the power supply ...

Page 55: ...52 Part 5 Controller 1 Wired Controller KJR 29B 53 2 Touch Key Centralized Controller CCM30 62 ...

Page 56: ...oor setting temperature range 17 C 30 C 4 LCD Liquid Crystal Display 5 Touch key 6 Can switch Fahrenheit degree and Centigrade degree New function Basic function Air filter cleaning reminding function ON and OFF the air conditioner Indoor unit address setting function Auto restart function Remote control receiver function Time ON and Time OFF setting Lock the wired controller Clock setting Silent ...

Page 57: ...e controller to control swinging through the display panel of the indoor unit or use the swing button on the wired remote controller to control the indoor unit for swinging 2 On and off the air conditioner Press the On Off button to control the indoor unit on and off status When the unit is turned off press the On Off button the unit will be turned on and the operating icon lights up When the unit...

Page 58: ...24 hours After finish adjusting the timer on setting press the button or wait for 5 seconds to confirm and exit the timer on setting Under the timer on setting status press the timer clock setting button then enter into the timer off setting status and the screen will display and The setting method of timer off is the same as the timer on Under timer setting state set the timer on and the timer of...

Page 59: ...function is 2 500 hours and it can change to be 5 000 hours or 10 000 hours The setting methods refer to the part of wired controller initial parameter setting 11 Swing function If the indoor unit supports swing function press the right button to adjust the air outlet direction of the indoor unit Press this button for 3 seconds can turn on or turn off the auto swing function the swing icon will be...

Page 60: ... on the 86 electrician box Switching wires for signal receiving board 1 For connecting the signal receiving board and 4 core shield wire Switching wires for wired controller signal 1 If needed For connecting the main control panel and 4 core shielding wire 3 Supplied assemblies on the site Name Qty Embedded into wall Specification Only for reference Remarks 4 core shielded cable 1 0 5mm2 4 The lon...

Page 61: ...t two terminals of embedded 4 core shielding wire with the switching wires of wired controller and signal receiving board Make sure the sequence of 4 terminals A B C and D should correspond to the wire sequence of signal switching wires A B C and D ...

Page 62: ...r back cover installation Use straight head screwdriver to insert into the buckling position in the bottom of wired controller and spin the screwdriver to take down the back cover Pay attention to spinning direction otherwise will damage the back cover Use three M4 20 screws to directly install the back cover on the wall Use two M4 25 screws to install the back cover on the 86 electrician box and ...

Page 63: ... screw will lead to deformation of back cover Neaten the wires of the wired controller There are three positions of signal wire outlet around the wired controller when the wired controller directly is installed on the flat wall When the wired controller is stalled with electrician box the back cover of wired controller is already reserved one hole for wire outlet It is also available for the shiel...

Page 64: ...eters The wired controller initial parameter includes two codes XY The first code X means the function class the second code Y means detailed configuration of this function Step1 Simultaneously press the mode button and fan speed button of the wired controller for 5 seconds to enter the parameter setting state Step2 The value of the first code X is 0 press the temperature setting buttons and to ad...

Page 65: ...t None 6 Centigrade Fahrenheit display Centigrade Default Fahre nheit Notes The second code of the filter cleaning reminding is 2500hours which as default 2 Touch Key Centralized Controller CCM30 CCM30 is new designed and it is a touch key centralized controller It can be connected up to 64 indoor units and the connection length can be up to 1200m The CCM30 centralized controller has the air filte...

Page 66: ...ner By default the first in service air conditioner will be queried 2 Setting key In other display modes press this key can enter the setting mode By default it is a single setting and the first in service air conditioner is displayed In setting the operation mode press this key again and the operation will be performed for all air conditioners in the network Press ...

Page 67: ...ingle operation mode the air conditioner of the previous in service address number will be selected when this key is pressed if it is in the global operation mode no effect will result when this key is pressed In the main page press the key to enter the query mode By default it is the first in service air conditioner 9 Rightward key In the query mode when the key is pressed the next in service air...

Page 68: ...select the next setting time If you hold down this key the next data will be selected one by one When reached the max allowed setting time it cannot increase 13 Reduce key 1 Query mode Press this key display the data of the previous page If it is now in the first page press is key again and the last page will be displayed 2 Setting operation mode Temperature adjusting method Press this key the set...

Page 69: ...y is pressed the centralized controller will reset The result is the same as the result of restoring power on after power failure 17 Lock key Any time when this key is pressed the selected air conditioner can be locked or unlocked ...

Page 70: ...2 2 LCD display 2 3 Other operations Various locking functions 1 Centralized controller locking The centralized controller locking state will be recorded when powered off It won t dismiss when re power on ...

Page 71: ...ler locking of the air conditioner is remained 2 Remote controller locking 1 Effect When the air conditioner is under remote controller locking state it will not receive the remote signals from remote controller or wired controller until unlocking The air conditioner can be operated by the centralized controller 2 Operation Can lock or unlock through the computer Can operate by a centralized contr...

Page 72: ...ncurrently the emergent stop switch shall have preference ON and OFF operation Use the key or key can turn on and turn off the air conditioners in the centralized controller network The ON mode will accord to the system mode locking or other limit conditions for judging if there is conflict it will auto adjust to the next mode without conflict if all the modes have a conflict then it cannot operat...

Page 73: ...or under other interfaces the centralized controller will send the default ON order to all air conditioners The default ON order is cooling mode high fan speed setting temperature is 24 or 76 operates the swinging function Air filter cleaning remind display description 1 The centralized controller records the total running time of the indoor unit When the accumulated running time reaches the pre s...

Page 74: ... 2 2 Code of different times of reminding clear filter Function code Function setting Parameter code Time hour 00 Only display no function 00 0 01 Cleaning filter screen reminding 01 1250 02 2500 03 5000 04 10000 Dial code operation specification Table 2 3 Dial code definition ON OFF Dial code 1 CCM30 for 3 pipes CCM30 for 2 pipes Dial code 2 Fahrenheit Centigrade Dial code 3 With the optional fun...

Page 75: ...e 07 06 05 04 03 Communication malfunction between centralized controller and PC gateway 02 Communication malfunction between centralized controller and functional module 01 Communication malfunction between centralized controller and network interface module 00 Communication malfunction between network interface module and main control board Protection code Content PF Other protection PE Reserved...

Page 76: ... displayed constantly If all indoor units lock the cooling mode this flag will display and if all indoor units lock the heating mode the flag will display 2 Data display handling Indoor unit code address display display range 00 63 and with being luminous concurrently Indoor temperature display display range 00 99 C or 99 The indoor temperature is displayed concurrently If the temperature is highe...

Page 77: ...pad is locked and the centralized controller communicates with the computer normally Description of the query page The LCD displays the query page and the air conditioner with the address of 01 is being queried Mode of the air conditioner with the address 01 is cooling high speed air supply swing on indoor temperature 22 C setting temperature 20 C and cooling mode locked In the matrix only the big...

Page 78: ...ller communicates with the computer normally 2 6 Centralized controller installation Dimensions Unit mm There are two kinds of appearance for your choice The main difference is the controller cover and you can choose you like 1 The structure A must be embedded into the wall of the installation mode taken from the walls of the interior wiring way would be more appropriate and you must reserve a chi...

Page 79: ...76 CCM30 ...

Page 80: ...77 Installation diagram Terminal instruction ...

Page 81: ...HIGH STATIC PRESSURE DUCT SERIE ASDH 96AI PARTS GUIDE EN ...

Page 82: ...Exploded view of indoor unit ASDH 96AI 25 26 1 2 3 4 5 6 7 8 9 24 10 19 18 17 16 11 12 13 22 21 20 14 15 23 ...

Page 83: ...or 202301000897 1 7 5 Wire joint 3p 202301400224 1 7 6 Six Terminal Block 202301400240 1 7 7 Wire joint 5p 202301450037 1 7 8 Wire joint 2p 202301450042 1 7 9 Display box ass y 203370190008 17223000002836 1 8 E box cover ass y 201270990025 1 9 Drainage pan ass y down 201270900041 1 10 Motor clamp up 201286000008 1 11 Fan Motor boarding 201285500066 1 12 Motor clamp down 201286000052 1 13 Motor 202...

Page 84: ...ter collector ass y 201270900024 1 21 Strengthen board 201270990054 1 22 Pipe Temp sensor ass y 202301300710 1 23 Room Temp sensor ass y 202301300197 1 24 Evaporator ass y 201570990120 1 25 Top cover ass y 201270990067 1 26 Rear board 201270900069 1 The data are subject to change without notice MODEL ASDH 96AI Indoor Air filter 12923000000262 ...

Page 85: ...Exploded view of outdoor unit ASDH 96AI ...

Page 86: ...00100906 2 9 6 Capacitor 202300300109 2 9 7 Wire joint 4P 202301450112 1 9 8 Reactor 202301000979 1 9 9 DC fan module board assembly 201395100648 1 9 9 1 Radiactor 202301901197 1 9 9 2 Three phase bridge 202300500348 1 9 9 3 Power drive assembly board components 201395100649 1 9 10 Terminal block 201395100431 1 9 11 E box 201295100641 1 9 12 Installation board 201295100640 1 9 13 Resistance 202300...

Page 87: ...637 1 25 Rear panel ass y right 201295100644 1 26 Front cover ass y pipe 201295100634 1 27 Front panel ass y right 201295100643 1 28 Condenser ass y down 201595190041 1 29 Condenser ass y up 201595100222 1 30 Base 201295100633 1 31 Axial fan ass y 201100320624 2 32 DC motor 202400300063 2 33 Discharge Temp sensor ass y 202301300124 1 34 Room Temp sensor ass y 202301300197 1 35 Pipe Temp sensor ass...

Page 88: ... unit is containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personnel Type of refrigerant R410A The composition of the cooling medium R410A 50 HFC 32 50 HFC 125 The quantity of the refrigerant please see the unit label The value GWP 2088 1 kg R410A 2 088 t CO2 eq GWP Global Warming Potential In case of quality problem or...

Reviews: