20
Basic test procedure
11 Basic
test
procedure
11.1 Defective
compressor
Compressors are single phase, 115 or 120 volt, depending on the model unit. All compressor
motors are permanent split capacitor type using only a running capacitor across the start and run
terminal.
All compressors are internally spring mounted and externally mounted on rubber isolators.
11.1.1 Compressor
wiring
test
Remove compressor terminal box cover and disconnect wires from terminals. Using an ohmmeter,
check continuity across the following:
Terminal "C" and "S" - no continuity
- Open winding - replace compressor.
Terminal "C" and "R" - no continuity
- Open winding - replace compressor.
Terminal "R" and "S" - no continuity
- Open winding - replace compressor.
11.1.2 Ground
test
Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of
contact as a good connection is a must) and the other probe in turn to each compressor terminal
(see Figure 2.) If a reading is obtained, the compressor is grounded and must be replaced.
11.1.3 Checking
the
compressor
efficiency
The reason for compressor inefficiency is normally due to broken or damaged suction and/or
discharge valves, reducing the ability of the compressor to pump refrigerant gas.
This condition can be checked as follows:
1. Install a piercing valve on the suction and discharge or liquid process tube.
2. Attach gauges to the high and low sides of the system.
3. Start the system and run a “cooling or heating performance test.”
Summary of Contents for AMC-15A
Page 1: ...SERVICE MANUAL AMC 15A MOBILE SERIES ...
Page 2: ......
Page 7: ...4 Out dimension 3 Out dimension ...
Page 16: ...25 Characteristic of temperature sensor 12 Characteristic of temperature sensor ...
Page 26: ...25 Characteristic of temperature sensor 12 Characteristic of temperature sensor ...
Page 31: ...PARTS GUIDE AMC 15A MOBILE SERIES ...
Page 32: ......