background image

EXHAUST

 

HOSE INSTALL

ġġ

1.

 

Circumrotate the exhaust hose according to the direction as the arrowhead 

ķ

 

indicates and then the exhaust hose can be took out from the unit. 

2.

 

Circumrotate the exhaust hose according to the direction as the arrowhead 

ĸ

 

indicates and then make it connect with the unit. 

 

 

 

 

 

 

 

   

 

 
 
 
 
 
WINDOW KIT

 

INSTALL

   

‹

  Install the Exhaust Hose and the Adjustable Window Slider Kit as 

depicted in Fig.1 

˂

  Fig.1a. 

Summary of Contents for AMC-11P

Page 1: ...LOCAL AIR CONDITIONER AMC 11P AMC 14P EN User manual Ver 1 18 03 2019 Original instructions ...

Page 2: ...ion sources for example open flames an operating gas appliance or an operating electric heater 3 Do not pierce or burn 4 Be aware that refrigerants may not contain an odour 5 Appliance AMC 11P shall be installed operated and stored in a room with a floor area larger than 12m2 and AMC 14P larger than 13m2 6 Servicing shall be performed only as recommended by the manufacturer 7 The appliance shall b...

Page 3: ...s 13 The heating function of the unit should be operated in an indoor ambient temperature between 7 and 23 14 Clean air filter periodically to enjoy the most efficient cooling 15 When the unit is shut off please wait at least 3 5 minutes before restarting this is to prevent the compressor from being damaged 16 This unit needs at least 7 Amps of electricity to have its compressor operational To avo...

Page 4: ...efore scrapping it 21 This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shal...

Page 5: ...able refrigerants Compliance with national regulations 4 Storage of equipment appliances The storage of equipment should be in accordance with the manufacturer s instructions 5 Storage of packed unsold equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge The maximum number of piece...

Page 6: ...trol of flammable material ATTENTION For effective heating and cooling functions please ensure that the following steps are undertaken 1 Extend the exhaust hose to a length of not more than 400mm The exhaust hose must be kept parallel and must not be bent up or down 2 A distance of 500mm minimum must be kept between the filter side of the unit and wall or any other obstacles 3 When this appliance ...

Page 7: ...m room to room on easy glide castors No installation required just plug into any household power outlet Powerful refrigerated air system cools down the ambience instantly whenever you want Dehumidified and filtered air cycle improve breathing environments effectively Besides the remote control your one touch electronic pad also provides easy identifying manual operation 24 hour programmable timer ...

Page 8: ...and it will release from the base 4 Grip the carry handles located on either sides of the unit and carefully lift until it slides out of the foam base 5 Remove the air outlet and take out the exhaust hose as the picture 6 Install the exhaust hose on the unit before operating the unit CONTENTS 1 Air conditioner unit 2 Remote control 3 Batteries 4 Window Kit A ...

Page 9: ...E PARTS 1 Control panel 2 Remote control receiver 3 Adjustable air vent 4 Joint tube 5 Exhaust hose 6 Upside drain hole 7 Cool air inlet 8 Cool air filter 9 Hot air inlet 10 Hot air filter 11 Downside drain hole ...

Page 10: ... and the maximum limit is 25ć 4 TEMPERATURE REGULATION KEY DOWN During cooling function This key lowers the preset temperature by 1ć each time it is pressed and the minimum limit is 17ć During heating function This key lowers the preset temperature by 1ć each time and the minimum limit is 15ć 5 L E D DISPLAY The display indicates the current setting temperature or the timer setting When the set te...

Page 11: ...led and the unit will turn on 4 You can set the function and fan speed while setting the timer TIMER OFF The timer off is used to turn off the unit automatically after the setting time is over 1 Press the TIMER key at operating status to set the time you desired 2 Once the set hour has come to an end the unit will turn off automatically 3 Press the POWER key before the time out the setting time wi...

Page 12: ...urs 3 Press the SLEEP key again can cancel the setting 9 ALARM When the water tank is full E4 will be displayed on the display panel To resume operation please remove the rubber cap of the drain hose to drain out the water firstly The E4 warning will disappear after draining and then you can restart the unit by pressing the POWER key ...

Page 13: ...POWER 2 FUNC 3 TIMER 4 AUTO 5 HI 6 MID 7 LOW 8 SLEEP 9 TEMP On Off switch Function MODE selector Hourly programming Automatic fan speed High fan speed Medium fan speed Low fan speed Night operation selector Temperature selector ...

Page 14: ... function the ķ rubber cap on drain hose should be pulled out and install a proper drain hose ƽ Please remove the air exhaust hose connect a drain hose to the drain hole and lead the water to the outside in order to intensify dehumidifying capacity Ć When the water tank is full E4 will be displayed on the display panel Please remove the rubber cap ĸ of the drain hole to drain out the water first A...

Page 15: ... brush attachment with a vacuum cleaner Casing Wipe with a damp cloth and polish with a soft cloth To remove the air filter please follows the arrow direction and pull the filter lightly and then take out the filter for cleaning ...

Page 16: ...r operate in a narrow place 2 In case of dangerous leak don t work the machine in a humid place 3 Don t place the machine in a sunlit corner otherwise the unit might shut down due to the overheat and the color of the machine may soon fade out HELPFUL HINTS The unit is fitted with a special thermal cut off device Please ensure the unit is not placed against objects which will obstruct air intake e ...

Page 17: ... indicates and then the exhaust hose can be took out from the unit 2 Circumrotate the exhaust hose according to the direction as the arrowhead ĸ indicates and then make it connect with the unit WINDOW KIT INSTALL Install the Exhaust Hose and the Adjustable Window Slider Kit as depicted in Fig 1 Fig 1a ...

Page 18: ...y heating function When operating heating function Disassemble the outlet and the exhaust hose as arrow direction in Fig 01 and then exchange the two subassemblies to install The finished illustration is as Fig 03 ...

Page 19: ...equipment being used is suitable for use with flammable refrigerants i e non sparking adequately sealed or intrinsically safe 4 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available to hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 5 No igniti...

Page 20: ... followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigerant containing parts are installed The ventilation machinery and outlets are operating adequately and are not obstructed If an indirect refrigerating circ...

Page 21: ...arth bonding 2 Repairs to sealed components 1 During repairs to sealed components all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it isabsolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn o...

Page 22: ...mosphere from a leak 4 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 5 Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used...

Page 23: ...ess 7 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important that best practice is followed since flammability is a consideration The following procedure shall be adhered to Remove refrigerant Purge the circuit with inert gas Evacuate Purge again with inert gas Open the circuit by cutt...

Page 24: ...el the system when charging is complete if not already Extreme care shall be taken not to overfill the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commissioning A follow up leak test shall be carried out prior to leaving the site 9 Decommissioning Before carrying out this procedure i...

Page 25: ... j When the cylinders have been filled correctly and the process completed make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off k Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked 10 Labelling Equipment shall be labelled stating that it has been de com...

Page 26: ...atisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not mix refrigerants in recovery units and ...

Page 27: ... repair E2 Electrical short of temperature sensor copper tube and PCB wiring Contact an electrician for repair E4 Indicates water tank full or possibly the incorrect wiring of plug User needs to pull out the rubber stopper which is located at the bottom of the unit to drain the water away Check that the plug has been wired correctly ...

Page 28: ...ENERGY LABEL ...

Page 29: ...0 W 965 W 1535 W 1290 W Cooling Capacity 3000 W 4000 W Heating Capacity 3000 W 4000 W Moisture Removed 50 liters day 70 liters day Refrigerant R290 0 23kg R290 0 27kg Allowable Pressure Suction 0 6MPa 6Kgf cm 2 Discharge 2 5MPa 25Kgf cm 2 Maximum Allowable Pressure 4 0MPa 40Kgf cm 2 Dimensions mm 300 W 532 D 760 H ...

Page 30: ...se of quality problem or other please contact your local supplier or authorized service center Emergency number 112 This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible hazards to the environment or human health from uncontrolled waste disposal please recycle it to prove the sustainable reuse of material resources Please ...

Page 31: ...inclair world com The device was made in China Made in China REPRESENTATIVE SERVICE SINCLAIR Global Group s r o Purkyňova 45 Brno 612 00 Czech republic Phone sales 420 541 590 140 Phone service 420 541 590 150 Fax 420 541 590 124 www sinclair solutions com info sinclair solutions com ...

Page 32: ......

Reviews: