SIN.EQRPT868XT - QuickStart Guide
SIN.EQRPT868XT_QSG_2.5_en
Wireless M-Bus GATEWAY
DOCUMENTATION DOWNLOAD:
http://www.sinapsitech.it/en/area-download/
those exceeding 500 are ignored, and may in fact belong to the plant to be checked.
In this case it is necessary to charge, in the same Gateway, a
fi
le with a list of devices that are part of
its plant (Maximum 500); after uploading the
fi
le, the signal of the devices that are not included in the list
is ignored by the Gateway.
The
fi
le, whose name must be
list.rpt
, must be a CSV
fi
le with a format such as the one shown in the
following
fi
gure.
SPECIAL CASES OF USE
The following image shows an installation in which, or for di
ff
erent properties reasons , or for number of
devices to be controlled exceeds 500 (Max 500 for each RTU1T), it is necessary to create four
di
ff
erent networks of SIN.EQRPT868XT Gateways.
Obviously the following is valid also in cases where there are 2, 3, 5 or a higher number of Gateways
networks.
In order to avoid interferences between the various systems, assign to each RTU1T a di
ff
erent
Mesh
network ID
. The setting is done on RTU1T through its web interface;
Settings / Wireless Devices /
Wireless Setup / Setup Mesh Network
.
The same
Mesh network ID
setting must be carried out also on all Gateways that are part of the
network of the RTU1T which they have to communicate with.
For this procedure it is necessary to connect a PC to the Gateway to be con
fi
gured (via USB cable).
Use the
SIN.EQSW1
software (downloadable from the dedicated section of sinapsi.store) and follow
the instructions in the manual.
Note
: It is recommended not to change the Mesh Network Channel (default = 13 both on RTU1Ts
and on Gateways), because the change may involve the transmission power of the devices.
LOADING ON GATEWAYS OF A W. M-Bus DEVICES LIST IN THE PLANT
(ONLY ON GATEWAYS WITH FIRMWARE VERSION FWRPT1_V1R20.hex ONWARDS)
Referring to the same image of the previous installation, the various Gateways receive W. M-Bus signal
from their plant devices but they can also receive the signal from devices of adjacent plants.
If one or more Gateways receive the signal from more than 500 devices (Max 500 for each gateway),
For this procedure it is necessary to connect a PC to the Gateway to be con
fi
gured (via USB cable).
Use the
SIN.EQSW1
software and follow the instructions in the manual.
GATEWAY CONFIGURATION THROUGH FUNCTIONALITY OF KEYS
GATEWAYS FIRMWARE UPGRADE
You should always check the possible release of the latest
fi
rmware available version of the Gateways,
compared to the one installed on the devices in the production phase.
For this procedure it is necessary to connect a PC to the gateway to be con
fi
gured (via cable
USB). Use the
SIN.EQSW1
software (downloadable from the dedicated section of sinapsi.store) and
follow the instructions in the manual.
SETTING OF MESH NETWORK ID
Sinapsi Srl
reserves the right to make changes to this product without any notice
Manufactured by SINAPSI SRL - Via delle Querce 11/13 - 06083 Bastia Umbra (PG) - Italy
Change ID MESH - SIN.EQRPT868XT
1. Press keys 2 and 3 (2s. < T <6s) simultaneously.
2. On release all the LEDs (8) will
fl
ash at the same time to indicate
that you have entered edit mode ID MESH
3. Now press button 3 (at least 1s.) to switch the ID MESH.
- ID MESH 1 => Green LED (8.1) on - the others o
ff
- ID MESH 2 => Green LED (8.2) on - the others o
ff
- ID MESH 3 => Green LED (8.3) on - the others o
ff
- ID MESH 4 => Green LED (8.4) on - the others o
ff
4. To SAVE press keys 2 and 3 simultaneously for more than 1s.
Press the 2 button to exit without saving.
5. Verify that the blue LED does not remain on steady.
Otherwise, restart from point 1. by selecting another MESH ID.
6. If, after switching on all four MESH IDs, the blue LED continues to
remain on steady, it will be necessary to con
fi
gure the
SIN.EQRPT868XT via SIN.EQSW1 software.
7. Repeat for each SIN.EQRPT868XT.
Activate SND_IR mode (Installation Mode) - SIN.EQRPT868XT
a) It typically involves the installation of the AMR system and
subsequently the installation of the heat cost allocators
b) Both the AMR system and the distributors must be con
fi
gured to work
in this mode
c) SND_IR mode activation procedure on a newly installed
SIN.EQRPT868XT
1. Press button 2 (t> 6s.). When pressing button 2, the green LED (8.1)
fl
ashes every second, until you are under the 6s. Once the 6s have
passed, the LED (8.1)
fl
ashes every 500ms => this indicates that the
"SND_IR" scan mode has been changed.
2. RPT enters the "SND_IR" scan mode. RPT receives and takes over all
the devices that transmit the installation W. M-Bus telegram.
(This frame contains no data)
3. Scan duration without user intervention 12 hours -> Manual stop of
the scan => press key 2 (no coded pressure time)
Note: SIN.EQRPT868XT automatically exits the SCAN mode after
12 hours.
Accept mode activation ALL - SIN.EQRPT868XT
a) It is used when the commissioning is carried out after with respect to
the installation of the heat cost allocators
b) To activate the accept ALL mode on a newly installed SIN.EQRPT868XT
1. Press button 2 (2s. < T < 6s)
2. When pressing button 2, the LED (8.1)
fl
ashes every second. When the
key 2 is released, the LED (8.1.) remains lit to indicate the activation of
the accept ALL mode.
3. RPT receives and takes charge of all devices transmitting in W.M-Bus
including frames in Installation Mode (SND_IR) - The
fi
rst green LED
lights up permanently - Scan duration without user intervention 12 hours
4. press the button 2 (no coded pressure time) to stop the scan manually
Note: if during the scan the RPT connects into the MESH network the mode
of operation will automatically change with the value set on the RTU.
SIN.EQRPT868XT - S - T - C Mode of operation modi
fi
cation
1. Press keys 2 and 3 simultaneously (t > 6s.)
─
during the simultaneous pressing of keys 2 and 3, the green LEDs
(8.1) and (8.2) will
fl
ash every second, until you are under the 6s.
Exceeded the 6s. they
fl
ash every 500ms
─
When keys 2 and 3 are released, one of the green LEDs (8) starts to
fl
ash (500ms) to indicate the currently active mode of operation on
that SIN.EQRPT868XT
2. The mode of operation is changed by pressing the 3 key brie
fl
y
• Mode C+T => Green LED (8.1) on - the other o
ff
Factory setting
• Mode S => Green LED (8.2) on - the other o
ff
• Mode T => Green LED (8.3) on - the other o
ff
3. save settings by pressing the 2 and 3 button (t> 2s.)
4. exit => key 2 for ESC function without saving (during programming
status). Automatic ESC from programming status after 10 minutes
later.
Note: SIN.EQRPT868XT automatically exits the SCAN mode after
12 hours.
Restore factory settings
1. Press and hold keys 2 and 3 simultaneously.
2. Then press the reset button 4, without releasing the keys 2 and 3
3. As soon as all the LEDs (8) and (9)
fl
ash quickly, release all three keys.
9
1
2
1 - 100..240Vac power supply input (screw clamps)
2 - “Multi-function” button
3 - “Multi-function” button
4 - Reset button
5 - USB Port
3 4
6 - MESH network TX-RX LED
7 - W. M-Bus network TX-RX LED
8 - Signal level LED
9 - Status LED
5
6 7
8