2m
1. Always isolate mains power prior to installation.
2. Remove cover by turning anti-clockwise and remove the 2 screws as shown.
3. Use the base to mark the drill holes on the mounting surface.
4. Drill holes and insert wall plugs if required.
5. Feed power cable and load cable through base holes and securely affix base.
6. Connect the power wire and the load wire to the connection terminal according
to the electrical connection Fig 1. Do not exceed the max rated load.
7. Replace & secure base cover, calibrate (Fig 2) and replace front cover.
N L' L
Reach setting (Sensitivity)
Reach is the term used to describe the diameter of the more or less
circular detection zone produced on the ground after mounting the
sensor at a height of 2.5m.
Turn the reach control fully anti-clockwise to select minimum reach
(approx. 2m dia), and fully clockwise to select maximum reach
(approx. 20m dia). Adjust according to location and site requirements.
Time setting
The light can be set to stay ON for any period of time between approx.
5sec (turn fully anticlockwise) and a maximum of 12min (turn fully
clockwise). Any movement detected before this time elapse will re-start
the timer. It is recommended to select the shortest time for adjusting
the detection zone and for performing the walk test.
NOTE:
after the light switches OFF, it takes approx. 1sec before it is
able to start detecting movement again. The light will only switch on in
response to movement once this period has elapsed.
Light-control setting
The chosen light response threshold can be adjusted from approx.
2-2000lux. Turn it fully anti-clockwise to select dusk- to-dawn
operation at about 2 lux.
Turn it fully clockwise to select continuous daylight operation .
The knob must be turned fully clockwise when adjusting the detection
zone and performing the walk test in daylight, then adjust setting
according to site requirement.
INSTALLATION PROCEDURES
ELECTRICAL CONNECTION (FIG 1)
Connect N and L with power
Connect N and L
1
to the load
!
5sec~15min
5sec~12min
2~2000LUX
2~2000LUX
1-8m dia
2-20m dia
CALIBRATION SETTINGS (FIG 2)
Fig 1
DETECTION ZONES FOR CEILING MOUNTING
(AT 2.5 METRES)
1. Minimum reach 2m dia.
2. Maximum reach 20m dia.
fig.1
fig.2
fig.3
fig.1
fig.2
fig.3
Step Process
Important:
People or objects
moving towards the sensor are
more likely to be detected.
!
MIN
MAX
Important:
1. This microwave sensor cannot penetrate through metal objects.
2. For reliable operation, avoid installing in areas with notable air
turbulence or ceiling movement e.g. below mezzanine floors.
!
Fig 2
20m
NOTE:
The high-frequency output
of this sensor is <10Mw - that is
just one 50th of the transmission
power of a mobile phone or the
output of a microwave oven.
!