MultiXplo / MultiTox
Page 15 / 60
NOSP15759-Rev 10
2.
TECHNICAL FEATURES
GENERAL
Type
Gas detector
DM-TX6-X
MultiXplo (catalytic gas detector)
DM-TT6-K
MultiTox (catharometer gas detector)
DM-RX6 or DM-RT6
Network detector
Calibration
Factory set, recommended test every 6 months
OUTPUT SIGNALS
4-20mA loop signal
Type active (source) maximum load impedance 700
Ω
« 4-20mA » format
4-20mA with one fault level
- 0% full scale
4 mA
- 100% full scale
20 mA
- 105% full scale
20.8 mA
- Ambiguity function
21.7 mA (DM-TX6-X)
- Fault or inhibition
2 mA
« 0-22mA » format
4-20mA with several fault levels, for PLC and some recent
control units
- 0% full scale
4 mA
- 100% full scale
20 mA
- >105% full scale
20.8 mA
- Ambiguity function
21.7mA (DM-TX6-X)
- Inhibition
3.4 mA
- Fault measure
2.6 mA
- Device fault (HW/SW) 2.0 mA
Output relays
2 x configurable relays max 1A / 30V
AC/DC
ELECTRICAL
Power supply
24VDC,
(18 – 28 V DC versions DM-T#6)
(18 – 30 V DC versions DM-R#6)
Consumption
1,5 W typical, 5 W maximum
2.2 W typical, 5W maximum for a network detector
Wiring
0,5mm² (20AWG)-1,5mm² (16AWG).
MTBF
164 000h (Version DM-T#6) out of the sensing element)
1
Typical power: voltage 24 Vdc, current 4 mA, 1 relay activated
Maximum power: voltage 30 Vdc, current 22 mA, 2 relays activated
Summary of Contents for DM-TT6-K
Page 9: ...MultiXplo MultiTox Page 9 60 NOSP15759 Rev 10 Figure 1 Layout Drawing Congestion see Figure 2...
Page 32: ...MultiXplo MultiTox Page 32 60 NOSP15759 Rev 10...
Page 48: ...MultiXplo MultiTox Page 48 60 NOSP15759 Rev 10...
Page 56: ...MultiXplo MultiTox Page 56 60 NOSP15759 Rev 10 10 CONFORMITY CERTIFICATE...
Page 57: ...MultiXplo MultiTox Page 57 60 NOSP15759 Rev 10...
Page 58: ...MultiXplo MultiTox Page 58 60 NOSP15759 Rev 10...
Page 59: ...MultiXplo MultiTox Page 59 60 NOSP15759 Rev 10...