Simpson Electric Hawk H340 Operator'S Manual Download Page 6

6

3.56

90.7mm

3.93"

99.8mm

2.04"

51.8mm

0.52"

13.2mm

3.24"

82.3mm

1.76"

44.7mm

1.77"

45mm

3.62"

92mm

Engineering Label

Figure 4-1. Installation and Panel Cutout

1.

Activated set point indicators (4)

2.

4-button Keypad

3.

Units Window

4.

Numeric and message

Figure 2-1

2.

DISPLAY AND KEYPAD CONTROLS

3.1

Mounting Requirements

The Hawk 3 Advanced Digital Controller 1/8 DIN counters require a panel
cutout of 1.77” (45mm) high be 3.62” (92mm) wide. To install the counter into
the panel cutout, remove the clips from the side of the meter. Slide the meter
through the panel cutout, then slide the mounting clips back on the meter.
Press evenly to ensure a proper fit.

3.

INSTALLATION AND PANEL CUTOUT

19

seconds the alarm will trip and remain in alarm until the display drops below
the setpoint for at least 2.5 seconds

9.1.3 Latch

When choosing 

Ltch

, the relay output will latch immediately after crossing the

setpoint. The unit can then only be unlatched with a front panel reset or a reset
command from the RS-485 port.

NOTE:

 If the display is still beyond the setpoint threshold, the reset will have

no effect and the unit will remain latched.

9.1.4 Alarm

The 

Alr

 mode allows choice between High, Low, or Off. The High Alarm means

that the display value must be greater or equal to the setpoint to go into Alarm.
The Low Alarm means that the display value must be less than or equal to the
setpoint to into alarm The Off Alarm means that all features of this setpoint is
disabled. No action will occur when display crosses a setpoint and the relays
will revert to a normally de-energized state.
When selecting 

St 

(State) from the menu, the display will alternate between

Stand the current setting.
To edit the setting press RE     . Otherwise press 

T

 to move to the next choice.

If choosing 

ND 

(Normally De-energized) the relay will turn “on” the alarm con-

dition. This is a typical configuration. The one and two-relay outputs will act as
abeled; the normally closed contact will be closed until an alarm condition
occurs, and the opposite is true for the normally open connection. The four-
relay output only has the choice of normally open.
If choosing 

NE 

(Normally Energized) the relay will turn on at power up and

remain on until in an alarm condition. This mode can be used to create a fail-
safe condition or reverse the action of the four-relay configuration. In the fail-
safe example, the relay output would be wired to protect some device during
an alarm condition. During a power failure, the relay would be in the same
position as though it were in alarm thus protecting a device that may be on a
separate and possible active circuit.

9.2

Display Control

The next item that will appear in the menu is

 Dctl

 (Display Control). If this is

the item to be edited press  

Enter

   , otherwise press the down arrow 

T

 to move

to the next choice.

The display degrees, Deg, will allow you to select either °F or °C for the tem-
perature indication.  There is no need to change this value if you prefer the
default °C indication.

The display refresh, 

frsh, 

will slow the numbers of updates to the display. This

setting ranges from as fast as 480 updates per minute (8 updates per second)
to as slow as 1 update per minute.

RESET
ENTER

RESET
ENTER

Summary of Contents for Hawk H340

Page 1: ...venue Lac du Flambeau WI 54538 0099 715 588 3311 FAX 715 588 3326 Printed in U S A Part No 06 117489 Edition 5 06 07 Visit us on the web at www simpsonelectric com Hawk 3 Temperature H340 4 Digit Adva...

Page 2: ...stomer Service at 715 588 3311 Internet http www simpsonelectric com Warranty and Returns SIMPSON ELECTRIC COMPANY warrants each instrument and other articles manufactured by it to be free from defect...

Page 3: ...3 NOTES 22 NOTES...

Page 4: ...1 Sp4 18 9 1 1 Response 18 9 1 2 Delay 18 9 1 3 Latch 19 9 1 4 Alarm 19 9 2 Display Control 19 9 3 Output Control 20 21 20mA When the display reaches 0 percent the analog output would be 4mA The limit...

Page 5: ...configured by default for HI 100 0 and LO 0 When the display reaches 100 volts the analog output would be 20mA When the display reaches 0 volts the analog output would be 4mA The Hawk3 is purchased as...

Page 6: ...y crosses a setpoint and the relays will revert to a normally de energized state When selecting St State from the menu the display will alternate between Stand the current setting To edit the setting...

Page 7: ...ss T to move to the next choice Hysteresis will be used above and below the setpoint in equal amounts The value represents a percentage of the setpoint For example If the setpoint is set to 100 00 wit...

Page 8: ...ces T Scrolls DOWN through menu choices RE Selects a menu or submenu to edit 5 3 In Edit Mode W Moves Edit Cursor to the left Flashing cursor shows value to edit Nu meric Values Only S Increases Numer...

Page 9: ...i g r e n E d e z i g r e n e e D t n e s e r p f i 2 y a l e R 2 t n i o P t e S 2 P S 2 l a V e u l a V 2 e s n o p s e R 2 p s R t s y H y a l D h c t L 9 9 2 o t 0 0 1 0 s d n o c e S 0 0 0 6 o t...

Page 10: ...e t a d p u 0 8 4 o t 1 e u l a V d n a B e u l a v t n e r r u c m o r f s t n u o c 9 9 o t 0 e u l a V s s e n t h g i r B t i r B S d n a T s s e n t h g i r b D E L e v o m s w o r r a y a l p s...

Page 11: ...ded for resistive circuits only Use a snubber circuit to protect the contacts from inductive loads 7 2 Frequently Asked Questions What is a Form A or Form C relay The form A relay is a 1 contact switc...

Page 12: ...r o d r o w s s a p t n e r r u c 0 0 0 NOTE If you forget your password turn power off in unit press and hold the Tkey and the RE key Turn power on and wait until the display reads noPas then press t...

Reviews: