BIG GENNEY OPERATOR
’S MANUAL | 7
•
Audible Alarm
(internal to the inverter): The inverter makes a buzzing sound when it senses a
low battery condition. At this time, the user should reduce the connected loads and charge the
battery.
Note
:
The
audible alarm may make a momentary “chirp” sound when the inverter is turned OFF.
This is a normal occurrence.
Product Details: The
Big Genny’s LCD Meter Fuel Gauge
•
The inverter’s normal operating range is between 11 and 15 Volts DC.
•
The inverter’s low battery alarm will sound when the battery’s voltage drops to 10.5V.
•
Push the momentary button located directly below the LCD Meter Fuel Gauge screen to
read
the battery’s voltage.
Table 2
– Big Genny Voltage Readings VS. State of Charge
LCD Meter Reading
Battery Status
≥ 13.3V with no load
Fully Charged*
13V
50% State of Charge
12.5V
Empty
Note
: The meter reading is
approximate
.
The meter’s reading is accurate when no loads are
connected and the Big Genny is not being charged.
*A fully charged battery is also indicated by a solid green
light on the Big Genny’s plug-in
charger.
Neutral (left)
Ground (middle)
Live/Load (right)
LCD Meter Fuel Gauge