background image

Features 

 

Model VLC-600 addressable, analog output air 
aspiration smoke sensor provides: 

 

VESDA

 

 LaserCOMPACT operation communicating 

with the established TrueAlarm analog sensing process 

for area coverage up to 8000 ft

2

 

 

Compact 8 

” (225 mm) square size 

 

Dual stage dust filter that is used on larger systems 

 

Obscuration measurements communicated to the fire 

alarm control panel for status determination 

 

Panel selected sensitivity from 0.016%/ft to 4.08%/ft

 

 

Local computer port access for the VESDA Vconfig 

Pro software program as used on larger systems 

 

Single LED that indicates local status information 

 

Capability of driving a remote LED (ordered 

separately) 

Trouble conditions are also communicated: 

 

Mechanical problems are received as sensor troubles 

 

Electrical problems are received as “no answer” troubles 

 

Additional details are indicated by the sensor LED and 

by accessing sensor diagnostics 

Compatible with Simplex

®

 4100ES, 4010ES, 

4100U, or legacy 4100/4120 fire alarm control 
panels: 

 

Communications via 4100ES/4010ES/4100U IDNet 

or 4100ES/4100U MAPNET II addressable formats 

 

Connection is to the same SLC (signaling line circuit) 

with other devices such as addressable manual 

stations, TrueAlarm area smoke sensors, addressable 

control modules, etc. 

 

Communications are as a single device and connection is 

direct to the SLC without requiring a dedicated interface 

 

4100/4120 requires revision 8.01 or higher software 

Three threshold levels are programmable from the 
fire alarm control panel with typical selections as: 

 

Stage 1 – Alert at 0.016 to 0.6218% obscuration/ft 

 

Stage 2 – Pre-Alarm at 0.03 to 0.6234% obscuration/ft 

 

Stage 3 – Alarm at 0.05 to 4.08% obscuration/ft 

 

NOTE:

 UL listed evacuation alarm sensitivity is not 

to be less sensitive than 0.625%/ft 

Sampling pipe network: 

 

Uses standard Vision Systems pipe and inlet in 

accordance with Vision Systems Aspire design tool 

UL listed to Standard 268 (URXG) 

*

   This product has been approved by the California State Fire Marshal (CSFM) pursuant to 

Section 13144.1 of the California Health and Safety Code. See CSFM Listing 

7259-1728:0109 for allowable values and/or conditions concerning material presented in 

this document. This product was not approved by FM as of document revision date. 

Additional listings may be applicable; contact your local Simplex product supplier for the 

latest status. Listings and approvals under Simplex Time Recorder Co. are the property of 

Tyco Fire Protection Products. 

Typical air inlet

VLC-600 TrueAlarm 
LaserCOMPACT Air 
Aspiration Smoke Sensor

Fire Alarm Control Panel requires 4100ES/4010ES/4100U 

IDNet or 4100ES/4100U MAPNET II communications

(4100ES shown for reference)

4100ES/4010ES/4100U IDNet 
or 4100ES/4100U MAPNET II 
addressable communications

Tr ue Ala rm

Laser

COMPACT

Addressable manual stations, 

TrueAlert sensors and other devices 

ALARM

FIRE

PULL    DOWN

24 VDC power

A LA R M

Clean room cable tray

Remote LED indicator

CLEAN ROOM 
SMOKE DETECTOR 

ALARM

 

TrueAlarm LaserCOMPACT System Connections

 

Description 

 

Air aspiration technology

 smoke detection operates 

by actively drawing in air for sampling in a high intensity, 
stable detection chamber. The Model VLC-600 
TrueAlarm LaserCOMPACT smoke detector uses the 
latest in VESDA sampling technology including a highly 
efficient laser light source and a dual stage dust filter. 

TrueAlarm analog sensing 

occurs when the 

TrueAlarm LaserCOMPACT sensor communicates 
smoke chamber information to the connected fire alarm 
control panel. The panel evaluates the smoke sensor 
information against three programmed thresholds and 
declares an alarm or pre-alarm condition depending on 
smoke chamber activity. 

Status communications.

 In addition to smoke 

chamber information, the TrueAlarm LaserCOMPACT 
also advises the fire alarm control panel of local trouble 
conditions. Troubles may include dirty filter, airflow 
restriction or failure, etc. Specific details are stored in 
memory at the sensor location.

 

TrueAlarm

 

Analog Sensing  

UL, ULC, CSFM Listed*

 

VLC-600 TrueAlarm LaserCOMPACT Smoke Sensor with

 

 

4100ES/4010ES/4100U IDNet and MAPNET II Communications

 

 

 

S4098-0036-7  7/2013

 

 