background image

 

4901 TrueAlert Non-Addressable Horn Installation Instructions 

 

WARNING: Make

 

sure that all power is disconnected before starting the installation.

 

 

CAUTION: Connect the wiring to terminals as shown. Do not loop wires under the terminals. Break the 
wire runs to provide supervision of connections. Strip  the  lead insulation to a maximum of 3/8-inch 
(9.5 mm).

 

 

1.

 

At the enclosure box, connect the contractor wires to the NAC+ and NAC- terminals at the rear of the horn unit. See 
Figure 2. 

2.

 

When connecting more than one horn to a circuit, ensure that correct polarity is maintained for each unit. 

3.

 

When connecting the last horn on a circuit, connect an end-of-line resistor (EOLR) to the horn terminals. 

 

 

 

TrueAlert Horn (Rear View) 

 
 
 

 

 

Figure 2. TrueAlert Horn Wiring 

 
 
 
 
 
 
 

 
 

 
 

 

TrueAlert 
Non-
Addressable 
Horn Wiring 

Notes: 
 

1. 

Notification appliances are rated per individual nameplate label. 

2. 

Maintain correct polarity on the terminal connections.

  

 

3. 

Refer to the field wiring diagrams supplied with the FACP for detailed NAC wiring information. 

4. 

These appliances were only tested to the operating voltage limits of 16 VDC and 33 VDC. Do not 
operate these appliances outside these limits, as this can cause the appliance to fail to operate, and/or 
cause permanent damage to this equipment. 

NAC+ TERMINAL 

NAC- TERMINAL 

 

NAC TERMINALS ACCEPT 

2 WIRES: #12 - #18 AWG 

16-33 VDC POWER INPUT 

(See Note 4) 

PRODUCT ID 

NAMEPLATE LABEL 

IF LAST APPLIANCE 

ON CIRCUIT, 

CONNECT EOLR  

(See Notes) 

16-33 VDC FROM 

NOTIFICATION APPLIANCE 

CIRCUIT OR PRECEEDING 

APPLIANCE 

(See Notes) 

 

Reviews: