Page
12
3.4
Safety
In the interest of safety, the load bank is equipped with an automatic system to de-
energize all the load if conditions are met that may be dangerous to the operator or
could damage the hardware. If the load elements aren’t cooled properly due to a fan
failure or high exhaust temperature, the load bank will de-energize any applied load.
After operation, the load bank has an auto cool down feature to prevent burns and
injury during transportation after use.
3.5 Specifications
The table below shows the operation KW at the various voltages across the Powerstar
and the different model of Northstar Load Banks.
Model
KW
Rating
600VAC, 3Ph 480VAC, 3Ph 240VAC, 3Ph 240VAC, 1Ph 230VAC, 1Ph
208VAC, 2Ph
208VAC, 1Ph
PowerStar 110
110 480VAC, 3Ph
110KW/132A 110KW/264A
70.4KW/293A 64.7KW/281A 82.5KW/229A 52.9KW/254A
NorthStar 125
125 208VAC, 3Ph
125KW/345A
80KW/385A
NorthStar 150
150 600VAC, 3Ph
150KW/145A
96KW/115A
24KW/58A
Table 1 Specifications of Load Banks
Summary of Contents for NORTHSTAR 125 KW
Page 1: ...110 KW POWERSTAR DIGITAL LOAD BANK 125 KW NORTHSTAR 150 KW NORTHSTAR Document Number DOC 00668...
Page 2: ......
Page 9: ...Page 7...
Page 10: ...Page 8...
Page 11: ...Page 9...
Page 12: ...Page 10...