3
S49VO-0001-3 8/2014
Removable cover (when
installed, use flat bladed
screwdriver to release
latch on left side)
Mounting is compatible with single gang,
double gang, and 4" (102 mm) square boxes,
1-1/2" (38 mm) deep, supplied separately
Mounting Holes:
Single gang (2)
Double gang (4)
4" square (4)
Magnetic test location
(bottom of housing)
LED indicator
location
Transparent
housing assembly
Mounting plate
Electrical test point access holes
(on bottom)
Wiring access
hole
Wiring terminals and
connection clips
Strobe intensity
viewing slot on
side of appliance
(not to scale)
Intensity selection
plug, accessible
from rear of
housing; factory
setting is FACP,
controlled by panel
110
75
30
15
FACP
135
185
Address setting DIP
switch, accessible
from rear of housing
NFPA 72 requires
that the entire lens be
not less than 80" and
not greater than 96"
above the finished
floor (confirm with
your local codes)
Electrical
box outline
80" (2.03 m)
minimum
IMPORTANT! WALL MOUNT
INSTALLATION HEIGHT REFERENCE
Bottom of lens is
either even with, or
slightly above bottom
of compatible boxes
TrueAlert ES
Addressable Strobe
2975-9145 Box
4905-9931 Adapter Plate
4905-9931 Adapter Plate
4905-9961 Optional Wire Guard
(shown here for reference only, can be used on other mounting options)
Optional
4905-9961
Wire Guard
4" square box profile,
1-1/2" (38 mm) deep
(Surface mount conduit and
box shown for reference)
Optional surface mount adapter skirt,
1-1/2" deep: 4905-9937, Red;
4905-9940, White (conduit knockouts
are provided on all four sides)
TrueAlert ES
Addressable
Strobe
Surface Mount Side View Reference
2975-9145 Box Mounting Reference
Service Port
Page 1
REPORT 5 : TrueAlert Device Report
12:34:56am MON 18-Aug-14
POINT ID
CUSTOM LABEL
DEVICE
TYPE
CANDELA
T14-1-1
Location Label . . . up to 40 characters
V/O
15
T14-1-2
Break Room 5
A/V
110
T14-1-3 Boiler
Room
A/V
75
T14-1-4
Elec. Room 7
A/V
135
Adapter Plate and Surface Mount Installation Reference
Installation Reference
TrueAlert Device Reports Reference