579-1203 Installation Instructions

Setting the address DIP switch

Each addressable TrueAlert IDNAC notification appliance has a unique address that is set using an eight-position DIP switch 

(ADDR1). Up to 127 unique addresses can be assigned to an SLC; however, total appliance loading available may be less due to 

appliance current requirements.

To set the address

1. Unclip the cover from the appliance by inserting a slotted screwdriver (or similar sized object) into the opening at either end of the 

cover. See Figure 3.

2. Use a small screwdriver or pen to set the switches.
3. Record the set address.
4. DIP switch position 8 determines whether this appliance is viewed by the system as an 'ALARM' (OFF) or 'ALERT' (ON) type 

appliance. Confirm the setting for the appliance at this address with the FACP system configuration documentation.

Figure 3. Setting the DIP switch address

Setting the strobe candela setting

Figure 4. Setting the strobe and appliance 

configuration

1. Jumpers are factory set as FACP. Leave the appliance at this setting if 

the candela setting is to be programmed from a 4100ES FACP. The 

candela setting is visible through the slot on the side of the case.

2. If manual selection is required, remove the cover and slide the CD 

selector to the required setting: FACP or 15/30/75/110 for standard 

strobe, FACP or 185/135/110 for HiCD strobe.

3. When the appliance is mounted, the candela rating is visible through the 

side-window of the appliance. 

Note: 

One of the 4 candela outputs must be programmed for each appliance by 

authorizing service personnel or a programming mismatch trouble will result. 
To set the candela through the Programmer set it to FACP. Additional 
information is contained in the 

4100ES Programmer’s Manual

 (574-849). 

Audio circuit configuration (S/V and SO)

Use the slide switches depicted in 

Figure 4

 for required audio circuit 

voltage and power tap selection.

Move jumper P2, on the PCB on the back-side of the unit, to position 2-3 
for 70 V/2 W operation. Use position 1-2 for all other audio levels, see 

Figure 4

.

To Access Switches: 

SO Appliance

S/V Appliance

ALARM/
ALERT

001

101

011

111

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93

94

95

96

97

98

99

100

101

102

103

104

105

106

107

108

109

110

111

112

113

114

115

116

117

118

119

120

121

122

123

124

125

126

127

DIP SWITCHES 5 THROUGH 

7

000

100

010

110

Hgh Candela

Std Candela

Audio Circuit Configuration

P2

J2

1

P1

DEFAULT = 1-2
1-2 : 25V, 1/4W
2-3 : 70.7V, 2W

PCB on the back
side of the unit

P2

J2

1

DEFAULT = 1-2
1-2 : 25V, 1/4W
2-3 : 70.7V, 2W

Summary of Contents for 49SVC-CWFIRE

Page 1: ...ted TrueAlert ES indoor product identification reference Mounting instructions 1 Select the desired location and install the electrical box using screws suitable for the mounting surface 2 Connect the building wires to the terminal block on the rear of the appliance See Wiring instructions on page 2 3 Secure the appliance to the electrical box by using the provided hardware 4 Set the appliance set...

Page 2: ...gh 4 can each accommodate two wires one wire going in and one wire going out to the next appliance 5 These appliances are rated to the operating voltage limits of 23 30 volts DC VDC The appliance may fail to operate as intended and may cause permanent damage to this equipment if it operates outside of these limits 6 The TrueAlert IDNAC S V and SO can only be operated through a compatible power sup...

Page 3: ...ual selection is required remove the cover and slide the CD selector to the required setting FACP or 15 30 75 110 for standard strobe FACP or 185 135 110 for HiCD strobe 3 When the appliance is mounted the candela rating is visible through the side window of the appliance Note One of the 4 candela outputs must be programmed for each appliance by authorizing service personnel or a programming misma...

Page 4: ...55 129 55 45 104 55 45 123 60 40 103 60 40 111 65 35 98 65 35 120 70 35 87 70 35 103 75 30 90 75 30 75 80 30 96 80 30 83 85 25 96 85 25 70 90 25 83 90 25 47 Speaker specifications Input voltage 25 VRMS or 70 7 VRMS speakers are for connection to compatible fire alarm audio circuits Power taps via jumper J1 1 4 W 1 2 W 1 W and 2 W Frequency Response Fire alarm 400 Hz to 4000 Hz SV SO 200 Hz to 1000...

Reviews: