TrueAlert Ceiling-Mount A/V Wiring 

 

Warning: 

Make sure that all electrical power is disconnected before starting the installation. 

 

Caution: 

Connect wiring to terminals as shown.  Do not loop wires under terminals.  Break wire runs to provide 
supervision of connections.  Do not bring conduit through the rear of the electrical box.  Strip lead insulation to 
a maximum of 3/8-inch.

 

 

1.  At the electrical box, connect the wires to the CKT + and CKT - terminals at the rear of the A/V unit. Torque terminal 

block screws 12-15 in/lbs. to ensure proper continuity.  See Figure 2. 

2.  Ensure that correct polarity is maintained for each A/V unit. 

3.  SLC wiring must be twisted pair (TWP). 

 

 

 

 

 

 

 
 

4903

A/V

4903

A/V

4903

A/V

SLC -

CKT

SLC +

SLC -

SLC+

SLC -

SLC +

-

+

CKT

-

+

CKT

-

+

SLC -

SLC +

SLC -

SLC+

 

Class A Wiring (See Notes)

 

 

 

4903

A/V

1

2

4903

A/V

1

2

4903

A/V

1

2

4903

A/V

1

2

SLC -

SLC +

SLC -

SLC +

SLC -

SLC +

SLC -

CKT1

-

+

CKT1

-

+

CKT1

-

+

CKT1

-

+

SLC +

 

Class B Wiring (See Notes) 

 

Notes: 

1. 

Maximum 43 appliances per circuit.  Maximum 30 ohms wire resistance between appliances.  Refer to Field Wiring Diagrams of the driving 
TrueAlert compatible Fire Alarm Control Panel for further instructions. 

2. 

Notification appliances are rated per individual nameplate label. 

3. 

Maintain correct polarity on terminal connections.  Do not loop wires under terminals. 

4. 

All TrueAlert SLC wiring connections are supervised and power-limited. 

5. 

These appliances were only tested to the operating voltage limits of 17V to 31V.  Do not operate these appliances outside these limits: doing so 
may cause appliance to fail to operate as intended, and/or cause permanent damage to this equipment. 

6. 

The TrueAlert A/V can only be operated through a 4009 TrueAlert Addressable Controller or TrueAlert-compatible FACP. 

7. 

T-tapping is not allowed for Class A wiring. 

 

Figure 2.  TrueAlert Ceiling-Mount A/V Wiring

 

FROM TrueAlert-COMPATIBLE 

SLC CONTROLLER 

(SEE NOTES) 

CKT TERMINALS ACCEPT 

2 WIRES: #12 – 18 AWG TWP 

(SEE NOTE 3) 

FROM TrueAlert-COMPATIBLE 

SLC CONTROLLER 

(SEE NOTES) 

TO NEXT APPLIANCE OR 

TrueAlert-COMPATIBLE SLC 

CONTROLLER 

(SEE NOTES) 

CKT - INPUT 

CKT + INPUT 

ADDRESS SWITCH 

(SW1) 

firealarmresources.com

Summary of Contents for 4903

Page 1: ...e TrueAlert Ceiling Mount A V Operation The 4903 TrueAlert Audible Visible A V unit see Figure 1 is a ceiling mount notification appliance that provides an audible and or visible warning indication of an alarm condition when activated from a TrueAlert compatible control panel of a UL listed Simplex Fire Alarm System When the notification appliance emits sound and or light it indicates the possibil...

Page 2: ... Maximum 30 ohms wire resistance between appliances Refer to Field Wiring Diagrams of the driving TrueAlert compatible Fire Alarm Control Panel for further instructions 2 Notification appliances are rated per individual nameplate label 3 Maintain correct polarity on terminal connections Do not loop wires under terminals 4 All TrueAlert SLC wiring connections are supervised and power limited 5 Thes...

Page 3: ...unted Ensure correct orientation of the box in relation to the location of the mounting screws and the A V s position 2 For installation in a concrete or plaster ceiling flush mount the box with a inch recess maximum 3 For installation in a suspended ceiling use a suitable tile bridge that rests on tile to support the box 4 Address Switch SW1 is accessible with the Ceiling Mount A V removed Figure...

Page 4: ... 1 THRU 4 RESERVED FOR FUTURE USE NOT USED ON OFF 1 ON 0 OFF DIP SWITCH SHOWN IS SET AT ADDRESS 7 Ceiling Mount A V Magnetic Test Note The TrueAlert Addressable Controller must be configured to support the Ceiling Mount A V diagnostic testing Position magnet tester 553 810 to the bottom right side of the A V cover near the LED indicator see Figure 4 Hold the magnet tester in place for a minimum of...

Page 5: ... volume settings Table 4 TrueAlert Ceiling Mount A V Units Sound Pressure Level Measurements Sound Pressure Level Measurement dBA Voltage Vrms Horn Mode See Note 1 Reverberant Room at Ten Feet Per UL464 See Note 2 Steady 84 6 Coded 80 6 Steady 86 3 Coded 82 4 Steady 88 4 High Volume Setting via Addressable Controller See Note 3 Coded 84 5 Steady 79 1 Coded 75 5 Steady 81 5 Coded 77 2 Steady 84 3 L...

Page 6: ...ese occupants cannot hear and or see the effect of the notification appliances within the protected area s you must increase the intensity of the sound light output or add additional notification appliances so that the occupants can hear an or see the effect of the notification appliances when activated Refer to National Fire Protection Association NFPA National Fire Alarm Code 72 Chapter 4 Notifi...

Reviews:

Related manuals for 4903