MX

 Digital Loop Card provides 

MX

 loop communications for the Simplex 4100ESi 

fire alarm panel via a single electrically isolated 

MX

 Digital loop. It supports up to 250 

MX

 devices - detectors and modules - and provides up to 500mA of loop power.

The 4100-6077AU 

MX

 Digital Loop Card (Figure 1) is a flat, 4x10-inch form-factor 

module that plugs into the Power Distribution Interface (PDI) of the 4100ESi panel.

An earlier version of the card was supplied as 4100-6077LIM, which included an extra 

bracket on which two LIM800 Loop Isolators were mounted and wired.  

This version of hardware has been withdrawn, as the 4100-6077AU now includes loop 

short circuit protection.

Overview

Physical 
Specifications

Status LEDs

Address 

Dipswitch

Status LEDs

Figure 1. 

MX

 Digital Loop Card

Summary of Contents for 4100ESi

Page 1: ... programming operation or change in site specific software Reacceptance testing is required after any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions known to be affected by a change must be 100 tested In addition to ensure that other operations are not inadv...

Page 2: ...100 6077AU MX Digital Loop Card Figure 1 is a flat 4x10 inch form factor module that plugs into the Power Distribution Interface PDI of the 4100ESi panel An earlier version of the card was supplied as 4100 6077LIM which included an extra bracket on which two LIM800 Loop Isolators were mounted and wired This version of hardware has been withdrawn as the 4100 6077AU now includes loop short circuit p...

Page 3: ...channel fault On steady when no device response on left channel Slow blink open circuit loop Fast blink short circuit loop Yellow R Loop MX loop communications right channel fault On steady when no device response on left channel Slow blink open circuit loop Fast blink short circuit loop Yellow MX Download Service Mode and Download in progress On steady for Service Mode and download in progress Ye...

Page 4: ...igital Loop Card mounts in a Cardcage PDI bay of a 4100ESi panel It can be mounted on any available block see Figure 2 Secure with the screws supplied in the MX Digital Loop Card kit Installation of the 4100 6077 in Card Cage Figure 2 4100ESi MX Digital Loop Card Installation ...

Page 5: ...ncreased density two 4100 6077AU cards can be mounted on a ME0516 Legacy Dual Bracket in either the 8U or 15U cabinets The ME0516 bracket is not suitable for mounting 4100 6077AU cards in the standard Simplex expansion bay The earlier 4100 6077LIM version of the loop card should not be mounted on the ME0516 Legacy Dual Bracket ME0516 as the resulting module width is too wide and may interfere with...

Page 6: ...Control Panel FACP Refer to Table 2 for a complete list of switch settings for all of the possible module addresses Note Set these switches to the value assigned to the MX Digital Loop card by the 4100ES Programmer Setting the MX Loop Card Address Step 2 Configuring the MX Digital Loop Card Figure 4 DIP Switch SW100 LT0638 Iss 1 1 7 2017 6 Use DIP Switches SW100 2 through SW100 8 to set the Module...

Page 7: ...p 2 Configuring the MX Digital Loop Card Table 2 Module DIP Addresses 7 LT0638 Iss 1 1 7 2017 SW100 2 SW100 8 SW100 7 SW100 6 SW100 5 SW100 4 SW100 3 SW100 2 SW100 8 SW100 7 SW100 6 SW100 5 SW100 4 SW100 3 ...

Page 8: ...ance 0 2 uF Inductance 1 5 mH Shield terminates at the loop card only if used Maximum voltage 40V Maximum current 500mA peak Ground fault detection 10K All loop wiring is supervised Note T tapped wiring is permitted as long as the overall wiring complies with the previously mentioned inductance capacitance and resistance parameters and all devices on the spur map to the same zone Table 3 MX LoopTe...

Page 9: ...rs at the start and end of the loop to provide short circuit protection These are not shown in Figure 5 These are not required with the 4100 6077AU as it includes short circuit protection Full details of the MX Device and Loop wiring can be found in LT0432 4100ESi Field Wiring Diagrams Figure 5 MX Digital Loop Wiring LOOP RIGHT MX DIGITAL LOOP CARD LOOP LEFT DET DET DET DET DET MX DIGITAL ADDRESSA...

Page 10: ...IO800 VESDA Interface Module 555 800 065 MIO800 Multi I O Module 516 800 960 LPSY800R Loop Powered Sounder Indoor Red 516 800 961 LPSY800W Loop Powered Sounder Indoor White 516 800 962 LPSY865R Loop Powered Sounder Outdoor Red 516 800 963 LPAV800R Loop Powered Sounder Beacon Indoor Red 516 800 964 LPAV800W Loop Powered Sounder Beacon Indoor White 516 800 965 LPAV865 Loop Powered Sounder Beacon IP6...

Reviews: