RS-232 Wiring

RS-232 devices can be wired to either the terminal blocks on the motherboard or they can be connected to the 25-pin D connectors on the RS-232

daughter card. In both cases, cables and/or connectors are not supplied.
Refer to Figure 10 for the pin-outs of these terminal blocks and connectors.

Figure 10: RS-232 Pin-outs

Note:

•  If PROM size equals 256 K, install jumper at P1-1 & P1-2. If PROM size equals 512 K, install jumper at P1-2 & P1-3.
•  RS-232 Power – 10 mA (maximum).
•  All wiring is supervised.
•  For a DC-operated printer, the maximum distance is 395 feet (120 meters) for 14 AWG (2.081 mm

2

) or 625 feet (191 meters) for 12 AWG

(3.309 mm

2

).

•  All wiring is 18 AWG (0.8321 mm

2

) or to local code.

•  Use of CTS line is required (with or without supervised circuit).
•  When using Service Modem 565-279, connect to Board 565-415 using Cable 733-808 in Shipping Group 740-850. Use Cable 171-095 to

connect the modem to a phone jack and/or a telephone termination block. Cut off one end of Cable 171-095 if connecting to a telephone

termination block. Strip back the cable to connect the two center wires to the red and green wires in the block. Refer to Test Specification

576-241 for instructions on how to communicate with the modem. Place jumpers across 1-2 of P4 and 2-3 of P5 on the service modem.

page 11

579-221  Rev. F

4100-6038 Dual RS-232 Module Installation Instructions

Summary of Contents for 4100-6038

Page 1: ...ested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when...

Page 2: ...igned to each jumper pin The specific jumper settings required on the dual RS 232 card depend on the type of device being attached to the card Refer to Table 1 for specific jumper configurations Figur...

Page 3: ...1 2 1 2 AC Printer 3rd Party Computer Supervised 2 3 2 3 1 2 1 2 1 2 1 2 None 2 3 2 3 2 3 AC Printer Unsupervised 2 3 2 3 1 2 1 2 1 2 1 2 1 2 2 3 2 3 1 2 Setting Switches Switches Switch SW1 on the R...

Page 4: ...Figure 3 4100 Daughter Card Addresses page 4 579 221 Rev F 4100 6038 Dual RS 232 Module Installation Instructions...

Page 5: ...When installing 2 51 mm x 11 inch 292 mm motherboards in a 4100ES expansion bay adhere to the following guidelines Each expansion bay assembly includes a chassis two end supports one LED switch frame...

Page 6: ...nd fill to the right 1 Orient the motherboard with the connector labeled J1 on the right and the header labeled P1 on the left 2 Attach four metal threaded standoffs and lockwashers into the screw hol...

Page 7: ...eight pins Insert the harness connector on either the top four pins or the bottom four pins not in the middle Insert the harness connector with the white wire into the P7 connector Note that the P7 co...

Page 8: ...bay Insert the harness connector with the blue wire into the P2 connector Note that the P2 connector has eight pins Insert the harness connector on either the top four pins or the bottom four pins no...

Page 9: ...tinuity of the shield must be maintained throughout the entire cable length The entire length of the cable must have a resistance greater than 1 Megohm to earth ground Underground wiring must be free...

Page 10: ...be kept to a minimum inside the back box enclosure The wiring should be neatly dressed and bundled together using the wire ties provided with the equipment Anchor power limited wiring to tie points as...

Page 11: ...G 2 081 mm 2 or 625 feet 191 meters for 12 AWG 3 309 mm 2 All wiring is 18 AWG 0 8321 mm 2 or to local code Use of CTS line is required with or without supervised circuit When using Service Modem 565...

Page 12: ...tional listings may be applicable contact your local Autocall product supplier for the latest status Listings and approvals under Tyco Fire Security GmbH and the product names listed in this material...