Preferred Mounting.

 For surface 

mounting of these addressable 
manual stations, the preferred 
electrical boxes are shown in the 
illustration to the right.  

Additional Mounting 
Reference. 

Refer to page 4 for 

Wiremold box mounting 
compatibility. 

 

 

 

S4099-0005  10/2014

 Application Reference 

 

Refer to NFPA 72, the 

National Fire 

Alarm and Signaling Code

, and all 

applicable local codes for complete 
requirements for manual stations. The 
following summarizes the basic 
requirements. 

1.

 

Stations shall be located in the 
normal path of exit and distributed 
in the protected area such that they 
are unobstructed and readily 
accessible.  

2.

 

Mounting shall be with the 
operable part not less than 42 in 
(1.07 m) and not more than 48 in 
(1.22 m) above floor level. 

3.

 

At least one station shall be 
provided on each floor. Additional 
stations shall be provided to obtain 
a travel distance not more than 
200 ft (61 m) to the nearest station 
from any point in the building.  

4.

 

When manual station coverage 
appears limited in any way, 
additional stations should be 
installed.

  

2975-9178 Box

5-3/16" H x 4" W x 2-3/16" D 

(132 mm x 102 mm x 56 mm)

(ordered separately)

Knockouts located 

top and bottom

2975-9022 Cast Box

5" H x 3-7/8" W x 2-3/16" D 

(127 mm x 98 mm x 56 mm)

(ordered separately)

Access for 3/4" threaded 
conduit located top and bottom

5" 

(127 mm)

FIR

E

ALARM

FIRE

PULL    DOWN

4099 Series Addressable Manual Station

1" (25.4 mm)

3-3/4" (95 mm)

 

 

 

Station cover

hinges open for

installation access

Simplex 2975-9178 box
(shown for reference)

Address setting under

resealable label (accessible

with cover open)

Switch wiring

(prewired)

Field wiring

(shown for reference)

1-1/4"

(32 mm)

2-5/8"

(67 mm)

 

 

 Addressable Manual Stations Surface Mounting 